type STATCOM
SIEYUAN Technical solution--Air-cooled
Ion
Exchanger
Supplement
Tank
Spare Pump
Main Pump
Cooling fans operation can be set according to the water temperature, it shall be put into
operation automatically in group.
SIEYUAN Technical solution-Water-cooled type
IGBT
Heat exchanger
Heat sink
PLC
Water-air or
Water-Water
Using the pump to take away the heat of STATCOM power units by water and then
exchange with outer-space water or air by the heat exchanger
SIEYUAN Technical solution-Water-cooled type
equipment is 15% to 30% more than that Generally small, but large-capacity heat
The water cooling method is mature and reliable, and it is the commonly
used cooling method
one main & one spare pump , improve the operation reliability ;
FEP water pipe — solid and endurance, good insulation, good chemical
stability, sealing treatment at the interface ;
Add ethylene glycol into cooling liquid, at minus 35 degrees without
freezing ;
The coolant is filtered by deionized resin to reduce the conductivity of pure
water and ensure the equipment withstand voltage and insulation
performance ;
SIEYUAN Technical solution——Conclusion
The high-level water tank is used as a buffer device to absorb the impact of
the pump, the thermal expansion and contraction of the coolant, and the
exhaust function ;
Spare water tank with automatic water replenishment function ;
Water cooling system maintenance only needs to check the water pump,
remove and wash the filter, check the instrument, etc., only once a year ;