Water-cooling

type STATCOM
SIEYUAN Technical solution--Air-cooled

Air -cooled type STATCOM


SIEYUAN Technical solution--Air-cooled

 Hot air is directly discharged to

the outdoors, and a large amount of

indoor and outdoor air exchange

 Affected by wind, sand, salt spray,

humidity, rain and snow, etc.

 Heavy daily maintenance workload

 As the running time increases, the

STATCOM failure rate increases


SIEYUAN Technical solution--Air-cooled

 STATCOM room airtight

 Hot air discharged indoors

 Cooling by air conditioner


SIEYUAN Technical solution--Water-cooled type

Water-cooled Type STATCOM


SIEYUAN Technical solution-Water-cooled type

Water cooled power module


SIEYUAN Technical solution-Water-cooled type

Ion
Exchanger

Supplement
Tank

Spare Pump

Main Pump

Main pump and spare pump run alternately


SIEYUAN Technical solution-Water-cooled type

Cooling fans operation can be set according to the water temperature, it shall be put into
operation automatically in group.
SIEYUAN Technical solution-Water-cooled type

IGBT
Heat exchanger
Heat sink

PLC
Water-air or
Water-Water

Pump Cooling Power


system Module

Using the pump to take away the heat of STATCOM power units by water and then
exchange with outer-space water or air by the heat exchanger
SIEYUAN Technical solution-Water-cooled type

ITEM Water-cooled type Air-cooled type

Water circulation cooling, high heat


Forced air cooling, average cooling
Cooling form conduction efficiency, good cooling
efficiency
efficiency

Completely isolate the external Affected by the environment, it needs to be


environmental influences such as wind, cleaned regularly, especially dust, small
running result
sand, etc., with low failure rate and long insects, etc. The failure rate is high after
equipment life long-term operation

The maintenance workload of air-cooled


Fully enclosed water cycle, maintenance equipment is heavy, and the maintenance
Equipment
workload is small, maintenance cycle is cycle may even need to be maintained
maintenance
once every 1 to 2 years once a month according to environmental
conditions
SIEYUAN Technical solution-Water-cooled type

project Water-cooled type Air-cooled type

The investment in water-cooled

equipment is 15% to 30% more than that Generally small, but large-capacity heat

investment in air-cooled equipment on average dissipation design is difficult, requiring

But the same or lower than air-cooled additional costs

type which using air-conditioner .

There is only the sound of the water


Noise level The noise of the cooling fan is very loud
pump indoors, which is relatively small

Choose Air-cooled type when the capacity of STATCOM is under 5Mvar


SIEYUAN Technical solution——Conclusion

 The water cooling method is mature and reliable, and it is the commonly
used cooling method
 one main & one spare pump , improve the operation reliability ;
 FEP water pipe — solid and endurance, good insulation, good chemical
stability, sealing treatment at the interface ;
 Add ethylene glycol into cooling liquid, at minus 35 degrees without
freezing ;
 The coolant is filtered by deionized resin to reduce the conductivity of pure
water and ensure the equipment withstand voltage and insulation
performance ;
SIEYUAN Technical solution——Conclusion

 The high-level water tank is used as a buffer device to absorb the impact of
the pump, the thermal expansion and contraction of the coolant, and the
exhaust function ;
 Spare water tank with automatic water replenishment function ;
 Water cooling system maintenance only needs to check the water pump,
remove and wash the filter, check the instrument, etc., only once a year ;
Thanks