Professional Documents
Culture Documents
Introduction
Aging of Insulation
• Aging of insulation is a function of time and temperature.
• Part of the winding operated at highest temperature undergoes
greatest deterioration.
• Improved cooling of transformer helps avoid accelerated
aging of the insulation.
Overheating due to overexcitation
Basic consideration
Type of transformer
Vector
Requirement of CT
Type of differential
Fundamental of differential
protectionBasic
consideration
TYPE of transformer
Generator transformer
Furnace transformer
Rectifier transformer
Fundamental of differential
protection
Basic
consideration
Vector
Phase shift
Fundamental of differential
protection
Basic
consideration
CT
Ratio
Class
Polarity
Connection
Fundamental of differential
protection Types of differential
High impedance differential::Here a high
impedance is added to relay circuit to prevent relay
operation due to CT saturation under through fault
conditions.This is very sensitive and fast operating for
internal faults.
Biased differential :Here the operation depends
upon differential current exceeding the bias current.
The bias characteristics is variable so that it is
applicable to a wide variation in transformer design
and configuration. This bias slope is set to stabilize
The protection for small differential currents,which
flow due to tap changer variation and CT tolerance
under through fault conditions.
Harmonic restraint
Harmonics present in transformer charging in rush current
Reduced Cooling
• Ratio should not exceed 1.1 times the ratio of rated voltage
and frequency of the transformer.
Monitors
Gas Detector
Relay
• During fault, arching occurs releasing gas.
• The current in the short circuited loop is high (50-100 times In)
and causes local damage and release of gas.
3. Internal Faults:
• Operating time of typical differential relay(ABB RADSB relay ) for a
fault current of 5 times the rated current is 27ms.
• For faults outside the protective zone of the relay a relatively large
differential current can occur due to position of the tap changer and
differences between the CTs.
• The differential relay should not operate for this differential current.
•The differential relay will protect the main winding as well as the
delta winding.
• The relays protect the main winding but not the delta connected wdg.
• All CTs should have the same ratio and auxiliary CTs can not be
used. Saturation voltage of all the CTs should be at least twice the
selected operating voltage.
Overexcitation:
Relay operates delayed for faults on the remaining parts of the windings
and for faults on the load side of the transformer.
TRANSFORMER
PROTECTION TERMINALS
Historical evolution
conventional numerical
• protection functions • fixed HW prot.functions
realised with different HW realised with SW
• Quantity and types of • Complete library of func.
protection func. fixed and available
limited
• HW-extensions difficult • Adaptation by SW
• No. of CT's and PT's • No.of CT's and PT's lower
higher • Requirement to primary
• Requirements to primary transformers lower
transformers higher
Comparison of technologies
conventional numerical
• Settings and operation • Settings and operation
locally locally or remote
• no documentation ( only • Self-documentation of all
hand-made) settings and events etc.
• Only binary information • Numerical information,
meas..values, events, etc.
• Periodical tests necessary • Selfsupervision and test
functions reduces
maintenance.
• Various spare parts • Five different types only
Comparison of technologies
conventional numerical
• integration to control • integration to control
systems difficult systems possible
• only protection • integrated protection and
control possible
• only protection • monitoring with available
information possible
• fixed solution • extension and new
developments possible
--> open architecture
Generator Terminal Transformer Terminal Control Terminal Line Terminal
M
G
LON
Line protection SPA
IEC 870-5-103
IEC 1375
Transformer
protection
Software Human-machine-
Generator
Library protection R
communication
Bay
Units
C
Control
IEC 1375
Automation
Remote
Input/Output Unit
Complete library with functions for bay control,
monitoring, protection of generators,
transformers.
Detection of Faults:
• All phase faults
• Earth faults at solidly or
Low impedance grounded systems
• Inter-turn faults
• No interposing CT's
• Standard wiring diagram
• Inputs for external functions (Buchholz, temperature sensors)
available
• Programmable indication of tripping and signaling
• Indication of measuring values
• Continuous self-monitoring
• Modular SW protection functions
• 4 serial interfaces:
- one front for local communication (PC)
- one rear for remote communication - two others (spare)
Compact Design
Flexible input and output
configuration
Open communication 5
strategy
7 4 4 4 4 321
1) Analog input unit
up to 6 transformer
6 2) Digital/Optical unit
3) CPU with serial port
R
4) Binary input/output unit
Bay
Units
5) Communication PCMCIA
6) Mother Board
7) Power Supply
Hardware concept 1 Analog input module, up to 9 input
transformers for AC voltage and current
Interbay bus
3 CPU
5 6 Connection module
7 Supply module
6
Process bus
R
RIO580
Bay
Units Up to 1024 binary I/Os
Hardware concept
DC
+5V
+15V
CPU -15V DC
Power
Supply
A/D DSP DPM Remote I/O
486DX +24V AC
Remote I/OTrip
Outputs
Remote I/OTrip
Sign.
SW-Key Outputs
Outputs
Trip Trip
PC-Card Sign.
Trip
Outputs FLASH OutputsBin.
Trip Outputs
Outputs EPROM IEC1375 Sign.Inputs
Trip Sign. I / IO/ O
Outputs Bin.
Sign.
Outputs
Outputs I / OPorts P a (MVB) Outputs
Sign. Inputs
Outputs
Sign. OPorts
I /Ports C Process bus Bin.
OutputsBin. Tranceiver
Outputs Ports - Inputs
Bin.
Inputs b
Bin.
Inputs
Bin.
Inputs C PC-Card
Inputs
RAM
A c
R e.g. LON
LON
d
D
SCS
LED's
SMS
RS Serial RS Serial
232 Controller 232 Controller SPA / IEC870-5-103 (VDEW6)
MMC
Hardware concept
RX DC
Tx
+5V
+15V
DPM CPU -15V
Power
DC Supply
A/D Remote I/O
DSP 486DX +24V AC
Remote I/OTrip
A/D DSP DPM Remote I/O
Outputs
Trip
Sign.
SW-Key Outputs
Trip Outputs
Trip
PC-Card Sign.
Trip
Outputs FLASH OutputsBin.
Trip Outputs
Outputs I/O EPROM IEC1375 Sign.Inputs
Trip Sign.
Outputs
I /Ports
O Bin.
Outputs
Sign.
Outputs
Outputs I / O P a (MVB) Inputs
Sign.
Outputs Ports Process bus
Sign. I / O
Ports C Bin.
OutputsBin.
Outputs Ports Tranceiver Inputs
Bin.
Inputs
Bin.
- b
Inputs
Bin.
Inputs C PC-Card
Inputs
RAM
A c
R e.g. LON
LON
d
D
SCS
LED's
SMS
RS Serial RS Serial
232 Controller 232 Controller SPA / IEC870-5-103 (VDEW6)
MMC
Signal data flow
S
A/I MUX A/D Analog to
H digital
conversion
COM MMI
I> Numerical
DSP U<
Z< SCS/ signal
1 DiffGen on
COM SMS processing
2 Current on
3 BinInp 2 off
etc.
Trip
Binary
B/I signal
etc.
B/O processing
Typical tripping time Algorithm and Logic
processor
Analog Binary
input Low pass Digital output
isolation Shunt filter Amplifier filter Z< isolation
S
I>
I
FUPLA
A/I MUX
H
A/D B/O
etc etc
0 3 2 7 9 4
0 ms 0 ms 3 ms 5 ms 12 ms 21 ms 25 ms
Software Library
I I I2 I TH I I I2 I TH I I I2 I TH
87G 87T 46 49 87G 87T 46 49 87G 87T 46 49
U> U< F<> U/f U> U< F<> U/f U> U< F<> U/f
59 27 81 24 59 27 81 24 59 27 81 24
Z< X< Ucos P<- Z< X< Ucos P<- Z< X< Ucos P<-
21 40 78 32 21 40 78 32 21 40 78 32
U0> CTRL Logic Timer U0> CTRL Logic Timer U0> CTRL Logic Timer
64S Counter 64S Counter 64S Counter
Metering
Metering(UlfPQ)
(UlfPQ)
Function Library
Frequency
Frequency(81)
(81)
Overexcitation
Overexcitationwith
with
Inverse
Inversetime
timedelay
delay(24)
(24)
Overexcitation
Overexcitation(24)
(24)
Instantaneous
InstantaneousOvervoltage
Overvoltage
(27/59)
(27/59)
Definite
Definitetime
time
Over
Overand
andUnder
UnderVoltage
Voltage(27/59)
(27/59)
Inverse
Inversetime
timeOvercurrent
Overcurrent(51)
(51)
Instantaneous
InstantaneousOvercurrent
Overcurrent(50)
(50)
Definite
Definitetime
time
Over
Overand
andUnder
UnderCurrent
Current(51DT)
(51DT)
Thermal
Thermaloverload
overload(49)
(49)
Restricted
RestrictedEarth
EarthFault
Fault(64)
(64)
Transformer-differential
Transformer-differential
22or
or33Winding
Winding(87T)
(87T)
Function Library
44parameter
parametersets
sets
Counter,
Counter,Timer
Timer
MONITORING
MONITORINGAND
AND Logic's
Logic's(OR,
(OR,AND,
AND,RS-FF)
RS-FF)
AUXILIARY
AUXILIARYFUNCTIONS
FUNCTIONS
Remote
RemoteInputs
Inputsand
andOutputs
Outputs
Additional
AdditionalI/O
I/Ounits
units
Operating
Operatingvalues
valuesI,I,U,
U,P,
P,Q,
Q,ff
Event
Eventrecording
recording
Disturbance
Disturbancerecorder
recorder
Self
Selfsupervision
supervision
Remote
Remotecommunication
communication
Human
HumanMachine
MachineInterface
Interface
Local
LocalDisplay
Displayunit
unit
Software concept eg. SM300
Protection Library Fupla
CPU Capacity
Hardware-key I> I>> I 3 I0
FUP1
51 50 60 67N FUP1
I> FUP1
51 FUP4
I TH I U U >>
49 87 L 60 59
I
87 L U> U< Ucos P<-
32 FUP1
59 27 78 FUP1
P<- U<
32 27 Binary Dist.
Z< Signal
21 Trans. Rec.
Z< 3 I0 Ucos
21 67N 78
AR SC Logics Timer
21 25
RE21604
HMI functionality
• LED-displays
• Measurand display
• Event list
• Operating instructions
• Disturbance recorded information
• Self supervision
• Acknowledgement functions
• Optical connector for external HMI
HMI functionality
LED indications
Availability
Start
Operation
Measurand display
Analog channels (amplitude, angle, frequency)
Functional measurands (e.g. differential current)
Binary signals (I/O signals, tripping)
Diagnostics
Operating status of the unit
Operating status of the interbay bus
Operating status of the process bus
Acknowledgement functions
Resetting the LED's
Resetting the latching outputs
Event erasing
Warm start
Transformer Differential Protection (87T)
Differential protection of two or three winding power transformers
& generator/transformer units.
Features:
• Non-linear, current dependent operating characteristic.
• High stability during through faults and in the presence of CT saturation.
• Short tripping times.
• Three phase measurement.
• Inrush current restraint.
• using the second harmonic.
• detection of the highest phase current.
• detection of the load current to determine whether the
transformer is energized or not.
• Compensation of phase group.
• Compensation of CT ratio.
• DC current component filter and harmonic filter.
Inputs & Outputs
Analogue Inputs:
Current ( 2 or 3 sets of 3 inputs)
Binary inputs:
Blocking
Binary Outputs:
Tripping
R phase trip
S phase trip
T phase trip
Measurements:
R phase summation current
S phase summation current
T phase summation current
R phase restraining current
S phase restraining current
T phase restraining current
Transformer Differential
for 2-windings
A A
D
DIFF D
AI 1,2,3 AI 7,8,9
Transformer Differential
for 3-windings
AI 4,5,6
A DIFF A
D D
AI 1,2,3
A
D
AI 7,8,9
Operating Characteristic:
Protected
I2
I1 unit
I3
I
Operation for Operating (diff.) current
IN I = | I 1 + I 2 + I 3 |
I’1
<b
3 IN
v Restraint
g I’2 = I 1 + I 2 + I 3 - I’1
IH
1 b 2 3
= ( I’1 - I’2 )
IN
Fault outside protected zone
Low short circuit current
Load I < (1.5...3) * Irated
I1 I2 I
4
cos = 1 3
IH I1 I2 cos 2
v=50%
1
IH = I1 = I2 =
ILoad < (1.5...3)*Irated g
1 2 3 4 5 IH
Fault outside protected zone
High short circuit current
I1 I2 I v= infinite
4
cos = 1
3
IH I1 I2 cos 2
1 v=50%
IH = I1 = I2
g
1 2 3 4 5 IH
b
Fault inside protected zone
I1 I2 I
4
2
cos < 0
1
IH = 0
g
1 2 3 4 5 IH
Thermal Overload Protection (49)
Features:
• 1st order thermal model
• Alarm and tripping stages
• Adjustable initial temperature
• Single or three-phase measurement
• Maximum value detection for
three-phase measurement
• Temperature rise calculated 40
49 times for each thermal time
constant setting
Inputs & Outputs
Analogue Inputs:
Current
Binary inputs:
Blocking
Binary Outputs:
Alarm
Tripping
Measurements:
Temperature rise
Power dissipation
Current
Definite time Over & Under Current (51DT)
Features:
• Single or three-phase measurement
• 2nd harmonic restraint for
high inrush currents
• Insensitive to DC component
• Maximum respectively minimum
value detection in the three-phase
mode
I<> • May also be used as REF protection
51 with additional hardware
Inputs & Outputs
Analogue Inputs:
Current
Binary inputs:
Blocking
Binary Outputs:
Pick-up
Tripping
Measurements:
Current amplitude
Setting Parameters:
Analogue Inputs:
Current
Binary inputs:
Blocking
Binary Outputs:
Pick-up
Tripping
Measurements:
Current amplitude
(only available if function trips)
Setting Parameters:
Features:
• Operating characteristic according to
British standard 142
• Single or three-phase measurement
• Detection of the highest phase value
in the three-phase mode
I >
• Wider setting range than specified
51
in B.S.142
Inputs & Outputs
Analogue Inputs:
Current
Binary inputs:
Blocking
Binary Outputs:
Pick-up
Tripping
Measurements:
Current amplitude
Setting Parameters: • c-setting: Select operating char. According
to BS142 or RXIDG char.
• k1-Setting: Time grading
Features:
• Single or three-phase measurement
• Maximum value, respectively minimum
value, detection for three-phase
measurement
• DC component filter
• Harmonic filter
U<>
59/27
Inputs & Outputs
Analogue Inputs:
Voltage
Binary inputs:
Blocking
Binary Outputs:
Pick-up
Tripping
Measurements:
Voltage amplitude
Setting Parameters:
Features:
• Processes instantaneous values and
is therefore fast and largely independent
of frequency
• Stores the peak value following pick-up
• Single and three-phase measurement
• Maximum value detection in the
three-phase mode
U>>
59/27 • Adjustable lower frequency limit fmin
Inputs & Outputs
Analogue Inputs:
Voltage
Binary inputs:
Blocking
Binary Outputs:
Pick-up
Tripping
Measurements:
Voltage amplitude
(only available if function trips)
Setting Parameters:
Features:
• Evaluation of the voltage/frequency ratio
• Single phase measurement
• Definite time delay
• Determination of frequency from the
complex voltage vector
U/ f • Over or Underexcitation mode
24
• Insensitive to DC components & harmonics
Inputs & Outputs
Analogue Inputs:
Voltage
Binary inputs:
Blocking
Binary Outputs:
Pick-up
Tripping
Measurements:
Voltage / frequency
frequency
Setting Parameters:
Features:
• Evaluation of the voltage/frequency ratio
• Single phase measurement
• Inverse time delay according to U/f ratio
• Determination of frequency from the
complex voltage vector
U/ f
24
• According to IEEE guide C37.91-1985
• Insensitive to DC components & harmonics
Inputs & Outputs
Analogue Inputs:
Voltage
Binary inputs:
Blocking
Binary Outputs:
Pick-up
Tripping
Measurements:
Voltage / frequency
frequency
Frequency (81)
Features:
• Measurement of one voltage
• Frequency calculation based on the
complex voltage vector
• Undervoltage blocking
• Insensitive to DC components & harmonics
Inputs & Outputs
Analogue Inputs:
Voltage
Binary inputs:
Blocking
Binary Outputs:
Under voltage blocking
Start
Trip
Measurements:
Frequency
Voltage
Metering (UIfPQ)
Measurement of voltage,current,real &
apparent power and frequency.
Features:
• Single phase measurement
• Phase-to-ground or optionally
phase-to-phase voltage measurement
• Suppression of DC components
and harmonics in current & voltages
• Compensation of phase errors in
main and input CT’s and VT’s
Inputs & Outputs
Analogue Inputs:
Voltage
Current
Binary inputs:
none
Binary Outputs:
none
Measurements:
Voltage (unit UN)
Current (unit IN)
Real power (unit PN (P))
Apparent power (unit PN (Q))
The right information for the right person at the right time
SCS
SMS Substation Control
Remote Substation Monitoring System
System
On-demand information
On-line information
SMS
Local Substation Monitoring System
On-demand information
TERMINAL
Remote communication and time synchronisation
GPS-Clock Modem
POWER
GPS 166
LOCK SA TELLITE CONTRO LLED CL OCK
ACQR
V1
OVP
NORMAL OPERATION
WED 11.12.1996
MEZ 11.42.25
SV 24 > SYN
CLR
MENU NEXT I NC
ACK
MEINBERG
Switch
ABB Strömberg SRIO 1000M
SRIO
FAULT
On
1
2
Serial
3
4
Local
Minute pulse
12 3 4 5 6 7 8
SPA-LOOP
ABB Network Partner AG RET 316*4 ABB Network Partner AG RET 316*4
1 9 1 9
2 10 2 10
3 11 3 11
4 12 4 12
5 13 5 13
6 14 6 14
7 15 7 15
8 16 8 16
C C
E E
RE.316
Remote communication and diagnostics
TERMINAL
Event recorder
9 analog channels
16 binary channels (function outputs, binary inputs)
12 function measurements (e.g Idelta, I2, Z )
Total record time 5s
Pre-Event 400ms,Event 3000ms, Post-Event 400ms
Selectable triggering (GFC, trip or functions and binary inputs)
Stop on full or overwrite mode
Disturbance Recorder - Recording times
t pre tf tp
t lim
FLASH SW-Key
EPROM PC-Card
3ph-Voltages Trip
Outputs IEC 1375
and-Currents a
I/O Transceiver
Sign. P Process bus
Symmetry check Outputs Ports C
- b
Bin. RAM C
Inputs PC-Card
A c
R
LON
D LON
d
Password protected
Test protection functions
send a numerical value to each function
test characteristic setting and related
outputs
Test signaling relays
Test tripping relays
Test LED's
Advantages
• Self monitoring
• Long term stability
• Event recorder
• Self documentation
• Number of CT cores reduced
• User designed performance
• Selectable protection functions
• Facility for communication to SMS/SCS
REFERENCES
ABB manuals
Alsthom manuals