Professional Documents
Culture Documents
,00
7,30
72
Fundamental value of the basic wind velocity (see European windmap):
5,988
7,2
0 vb,0 = 26 m/s (for Aachen - Germany)
[m]
30,00 Terrain category II ⇒ z0 = 0,05 m EN 1991-1-4
§ 4.3.2
z > zmin
Table 4.1
Basic data
⎣ ln ( 7 ,30 / 0 ,05) ⎦
Where: z0 is the roughness length
kT is the terrain factor, depending on the roughness length z0 Wind pressure on surfaces EN 1991-1-4
calculated using § 7.2
(pressure coefficients for internal frame)
0 , 07
⎛ z ⎞
k T = 0,19 × ⎜⎜ 0 ⎟⎟ A positive wind load stands for pressure whereas a negative wind load
⎝ z 0,II ⎠ indicates suction on the surface. This definition applies for the external wind
action as well as for the internal wind action.
Where: z0,II = 0,05 (terrain category II) EN 1991-1-4
§4.3.2
zmin is the minimum height Table 4.1 External pressure coefficients
zmax is to be taken as 200 m The wind pressure acting on the external surfaces, we should be obtained from
the following expression: EN 1991-1-4
Calculation of lv(z) we = qp(ze) × cpe §5.2 eq. 5.1
lv(z) turbulence intensity where: ze is the reference height for the external pressure
kI EN 1991-1-4 cpe is the pressure coefficient for the external pressure
lv = for z min ≤ z ≤ z max
co ( z ) × ln( z / z 0 ) §4.4 eq. 4.7 depending on the size of the loaded area A.
l v = l v ( z min ) for z < z min = cpe,10 because the loaded area A for the structure is larger
than 10 m²
Where: kI is the turbulence factor recommended value for kI is 1,0
z = 7,30 m a) vertical walls EN 1991-1-4
§ 7.2
so: zmin < z < zmax h 7,30
for = = 0,24 ≤ 0,25 Table 7.1
d 30,00
⎡ 7k I ⎤ 1
q p (z) = ⎢1 + ⎥ × × ρ × v b × (1
k T × ln( z / z 0 ) )
2
b) duopitch roofs EN 1991-1-4 The internal pressure coefficient depends on the size and distribution of the
§ 7.2 openings in the building envelope.
with α = 5,0°,
Table 7.4a Within this example it is not possible to estimate the permeability and
θ = 0° (wind direction) opening ratio of the building. So cpi should be taken as the more onerous of
EN 1991-1-4
§ 7.2.9 (6)
e = min (b; 2h) + 0,2 and – 0,3. In this case cpi is unfavorable when cpi is taken to + 0,2. Note 2
= min (72,00; 14,60)
= 14,60 m
Wind loads
1) upwind face
The wind loadings per unit length w (in kN/m) for an internal frame are
G: cpe = - 1,2 2) downwind face calculated using the influence width (spacing) s = 7,20 m:
H: cpe = - 0,6 w = (cpe + cpi) × qp × s
I: cpe = - 0,6 Internal and external pressures are considered to act at the same time. The EN 1991-1-4
J: cpe = 0,2 / - 0,6 worst combination of external and internal pressures are to be considered for § 7.2.9
every combination of possible openings and other leakage paths.
⇒ cpe = - 0,6
(see Table 7.4a , Note 1) Characteristic values for wind loading in [kN/m] for an internal frame:
- zones D, E, G, H, I and J
7,30
D: w = 4,59 E: w = 3,28
External pressure coefficients cpe (for zone D, E, G, H, I and J):
H: c pe = -0,6 J: c pe = -0,6
G: c pe = -1,2
I: c pe = -0,6
e/10 = 1,46 1,46
30,00 [m]
D: c pe = 0,7 E: c pe = -0,3
7,30
Roof shape coefficient
Shape coefficients are needed for an adjustment of the ground snow load to a
snow load on the roof taking into account effects caused by non-drifted and
drifted snow load arrangements.
EN 1991-1-3 30,00
The roof shape coefficient depends on the roof angle. [m]
§5.3
0° ≤ α ≤ 30° ⇒ μ1 = 0,8 Table 5.1