You are on page 1of 10

1 Introduction to Per Unit Calculations Consider the simple circuit of Figure 1 in which a load impedance of Z L = 60 + j70 = 92.

2.249 is connected to a voltage source. The no load voltage of the source is E S = 1000V0 o . The internal resistance of the source is Z S = j10 . The total impedance of the circuit is Z T = 60 + j80 . The load current through the circuit is E S 10000 o IL = = = 10A 53o 60 + j80 ZT The apparent power produced by the source is SS = E S IL = 10000 o 1053o = 10,000VA53o
ZS = j10

ES = 1000V

ZL =60+ j70

Figure 1 Basic Circuit: Example of p.u. calculations

In this circuit, we will designate the magnitude of each of these values as the reference value for that quantity, i.e. the reference value will be one unit of that quantity. That is, 1000 V is equal to one unit for voltage (Vbase = 1000 V) 100 is equal to one unit for resistance (Zbase = 100 ) 10 A is equal to one unit for current (Ibase = 10 A) 10,000 VA is equal to one unit for power (Sbase = 10,000 VA) These basic units are called the base values. Therefore, the base values for our circuit are 1000 V, 100 , 10 A, and 10 kVA.
1

I L is the conjugate of the load current. In this case IL = 10A + 53o

Now we can refer any value of any quantity in the circuit to these base values. For example, the magnitude of the voltage across the load is ZL 92.2 = 1000 = 922V ZT 100

VL = E S

In terms of our chosen base voltage, the load voltage is the ratio of the actual voltage and the chosen base voltage, i.e. VL 922 = = 0.922 of the chosen base voltage. We say Vbase 1000

that the voltage is 0.922 per unit of volts. The designation is VLp.u. = 0.922 p.u. (V). We can also say that the load voltage is 92.2% of the base voltage. Similarly, in terms of our impedance base, the load impedance is Z Lp.u . = ZL 92.2 = = 0.922p.u.() . Z base 100

Just like the magnitude of the load impedance, we can express any ohmic value in terms of the base impedance. So the per unit resistance of the load is R Lp.u . = RL 60 = = 0.6p.u.() Z base 100 XL 70 = = 0.7 p.u.() Z base 100

The per unit reactance of the load is X Lp.u . =

Notice here that both, the resistance and the reactance are compared to base impedance. The power dissipated by the resistance is P = RI2 = 60 102 = 6000W. Expressed as per unit value on our base of 10,000 VA, the dissipated power is Pp.u . = P Sbase = 6000 = 0.6p.u.( W ) 10,000

The reactive power to the load is QL = XLI2 = 70 102 = 7000 VAr (ind). Expressed as per unit value on our base of 10,000 VA, the load reactive power is Q Lp.u = QL 7000 = = 0.7 p.u.(VAr) (ind) S base 10000

Similarly as in handling the per unit values of ohmic quantities, both real power and reactive power are compared to the apparent base power, usually called base MVA. All base values are only magnitude. They are not associated with any angle. The per unit values, however, are phasors. The phase angles of the currents and voltages and the power factor of the circuit are not affected by the conversion to per unit values. The per unit values can be written as phasors, and all calculations that can be done with the actual quantities can be also done with per unit values. For example, in our circuit, the per unit load impedance and the per unit load current are: Z Lp.u . = 0.92249 o p.u.() and IL = 1 53o p.u.(A) Thus the voltage across the load is VLp.u . = Z Lp.u . ILp.u . = 0.92249 o 1 53o = 0.922 4 o p.u.(V)

In general, the per unit value is the ratio of the actual value and the base value of the same quantity.
per unit value = actual value base value

Manufacturers give impedance of equipment in percent on own base. The percent value is the per unit value multiplied by 100: Z% = Zp.u. 100%. The expression own base means that the base voltage is the rated voltage of the equipment, and the base power is the rated apparent power (in VA) of the equipment. The base current and the base impedance are calculated from the base voltage and the base VA:

4 S = base Vbase
2 Vbase = Sbase

I base

and

Z base

The percent impedance is then


Z% = Z actual in 100% Z base in

Generators and Per Unit System A generator rated 1000 VA and 200 V has internal impedance of j10 .

Figure 2 Basic Circuit: Example of p.u. calculations for generators

The ratings of the generator are chosen as the base values. In this example, S base = 1000 VA Vbase = 200 V I base = Z base = S base 1000 = =5A Vbase 200
2 Vbase 200 2 = = 40 S base 1000

The generator impedance is stamped on the nameplate together with the other ratings. This generator has impedance of j25%. This means that the per unit impedance is Z j25 Z p .u . = % = = j0.25 p.u. () 100 100 The actual impedance in is Zactual = Zp.u. Zbase = j0.25 40 = j10

5 Example: The generator above is short circuited at its terminals. Find the short circuit current and the short circuit power delivered by the generator in p.u., in %, and in the actual units. Solution:

Figure 3 Example: Short Circuit on Generator Terminals

E G p.u . 1 Isc p.u . = = = j4.0 p.u.(A) Z S p.u . j0.25

Isc % = Isc p.u . 100% = j400 % Ssc % = Ssc p.u . 100% = j400 %

Ssc p.u . = E G p.u . Isc p.u . = 1 ( j4) * = j4.0 p.u. (A)

The actual values calculated from the per unit values are: Isc = Isc p.u . I base = j4.0 5.0 = j20.0 A Ssc = Ssc p.u . S base = j4.0 1000 = j4000 VA

Transformers and Per Unit System A transformer is rated 2000 VA, 200V/400V, and has an internal impedance of j4.0 as seen from the low voltage side.

(a)

(b)
Figure 4 Basic Circuit: Example of Per Unit Calculations for a Transformer (a) Transformer Impedance Referred to the Low Voltage Side (b) Transformer Impedance Referred to the High Voltage Side

The internal impedance of the transformer as seen from the high voltage side is V Z HV = Z LV 2 V 1 400 = j4.0 = j16.0 200
2 2

The rated values for power and voltage are used as the bases for the calculations. It means that the voltage base is different on each side of the transformer. Comparison of the bases and the per unit value on both sides of the transformer is in Table 1

Sbase Vbase Ibase Zbase Zp.u.

low voltage side 2000 VA 200 V S base = 10A Vbase


2 Vbase = 20 S base Z LV j4.0 = = j0.2p.u () Z base 20

high voltage side 2000 VA 400V S base = 5A Vbase


2 Vbase = 80 S base Z LV j16 = = j0.2p.u () Z base 80

Table 1 Bases for transformer low side and high side

Notice in Table 1 that the transformer per unit impedance is the same, regardless of to which side of the transformer it is referred. In the transformer equivalent circuit the different voltage levels disappear and the transformer equivalent circuit is reduced to a single impedance: Zp.u.

Figure 5 Equivalent Circuit for a Transformer in Per Unit Analysis

Three Phase System and Per Unit Calculations In three phase systems the total apparent power is given by S 3 = 3 VLL I L where VLL is the line-to-line voltage and IL is the line current.

8 Similarly, S 3 base = 3 VL Lbase I L base where S3


base

is the chosen three phase base power, usually the rated power of the equipment, or the chosen base power used for all system calculation by the power utility

VLL base is the chosen line-to-line base voltage, usually the rated voltage of the equipment or the nominal voltage level of a part of the power system IL base is the line base current, usually calculated from the base power and the base voltage. and Y Connection in Per Unit Calculations IL I Z ZY

Figure 6 - - Y Conversion

The base values are related through the same relationships as the actual quantities: VLL base I base 3 VLN base VLN base =3 = 3 Z Y base I L base I L base 3 ZY base The per unit values of the connected impedances and the Y connected impedances are Z Z base ZY Z Y base

Z base =

Z p. u . =

Z Y p .u . =

From that it is easy to show that the per unit value for the connection is the same as the per unit value for the Y connection. Z 3Z Y ZY = = = Z Y p .u . Z base 3Z Y base Z Y base

Z p. u . =

Change of Base When pieces of equipment with various different ratings are connected to a system, it is necessary to convert their impedances to a per unit value expressed on the same base. The base that we are converting from will be denoted by subscript M, the base we are converting to will be denoted by subscript N. The base impedance for the bases M and N are, respectively,
2 VM base 2 VN base

Z M base =

SM base

Z N base =

S N base

The per unit impedances on the bases M and N are , respectively Z Z M base Z Z N base

Z M p .u . =

Z N p. u . =

where Z is the actual ohmic value of the impedance of the equipment. It follows that Z = ZM p.u. ZM base = ZN p.u. ZN base Substituting for the base impedances we get

10
2 VM base 2 VN base

Z M p .u .

SM base

= Z N p .u .

S N base

Z N p. u .

2 S N base VM base = Z M p .u . 2 SM base VN base

Using the MVA and kV notation,

Z N p. u .

MVA N base (kVM base ) 2 = Z M p .u . MVA M base (kVN base ) 2

You might also like