PRESSURE DROP CALCULATION SHEET

Project : Subject : Prepared : Date : Data: Length of pipe (L) Density () : : 1,500 4,922 0.87 870 54.31 34 0.034 136 599 4 13.12 8 0.67 0.20 meter feet gr/cm3 kg/m3 lb/cuft cP Ns/m2 m3/hr gpm m/second ft/second in feet meter Design Engineering CPO Tank Farm & Facilities Project Pressure Drop Calculation AM Checked : AG December 16, 2012

Approved :

ARL

Viscocity () Flow rate (Q) Velocity (v) Diameter of pipe (d)

: : : :

Detail Calculation: Pressure Drop (P) =


(0.000216 x f x L x x Q2) / (d2)

f = Darcy Friction Factor


k A4 D 2.8257 1 k 4. log D 3.7065 5.0452 . Re log A 4 D=inside diameter in feet Re= Reynolds number
1.1098

7.149 Re

0.8981

.4

k=Roughness in feet

Reynolds number (Re) Roughness of pipe (k) A4 f Then P

= = = = =

13,866.09 0.00015 0.0011 0.0288 45.4583 Psi / 100 ft feet (for Commercial Steel and Stainless Steel)