You are on page 1of 4

Substation: FAEDA 132/33/11 kV

Contract: KRG-MOE Stage 5

DIRECTIONAL O/C and E/F PROTECTION SITE


Protected Unit:

TEST RECORD SHEET


Circuit No. and ref.: Outgoing Feeder No.

1.RELAY DATA:
Relay type designation Rated current (Amp.) Rated Frequency (Hz) Feeder/Location V.T. Ratio (kV/kV) C.T. Ratio ( A/A ) Polarizing Voltage Vn REX 521 5 50 Hz Line 132 kV 33/V3 /0.11/V3 600/5/5 110 V AC Serial Number Produced by: Auxiliary DC supply (V) Device No. ABB 110

2. SETTING RECORD O/C Setting Ip>=600A, TMS 0.2 NINV (1x In) Ip>> =2100A, 0.5 sec. DMT (3.5x In) Ip>>>=OFF RCA +60 Direction: Forward Line Incoming/Outgoing Feeder

Plant Relay Address E/F Setting

Plant Relay Address

Ie>= 75A, TMS 0.2 NINV (0.15 xIn) Ie>>=220A, 0.7 sec. DMT (0.45x In) Ie>>>=OFF RCA =0 Direction: Forward Line Incoming/Outgoing Feeder

3. GENERAL INSPECTION AND CHECKS: Installation and wiring correct to the relevant drawings: Test block connections checked: . Modules type designation or ratings information is correct: Relay case connected to the local earth bar: . Output relays contacts are operating properly:

- Operation of digital display, LED indicators, reset buttons on relay front panel:

ZOZIK Testing eng. File Name:127211429.doc

Witnessed by:

Witnessed by:

Substation: FAEDA 132/33/11 kV

Contract: KRG-MOE Stage 5

DIRECTIONAL O/C and E/F PROTECTION


4. DIRECTIONAL CHARACTERISTICS PRESENTATION:

Typical directional Characteristic

E/F O/C

Determination of current detection in a two-phase Short Circuit IL1-IL2


5. TEST RESULTS :

Operating current when the basic angle b=0 =80 and starting current 1% In

5.1 Directional Earth Fault current test by secondary current/voltage injection: Polarizing Voltage(s) Injected Angle L1=63V L2=63V L3=0V L1=0V L2=63V L3=63V L1=63V L2=0V L3=63V -30 -30 -150
0

Current (s) injected Phase(s) Angle L1= 6 6

-30 -150
0

Angle Boundaries of operating area (Current shifting ) Shifted currents L1& L2 Lead Lag

L2= L3=
L1=

Shifted currents L2& L3 6 6 6 6 Shifted currents L3& L1 Lead Lag Lead Lag

L2=
L3= L1= L2=

-150

L3=

5.2 Directional Over current test by secondary current/voltage injection: Three-Phase fault currents of all three phases shifted at a time L1=63V 00 L1 6 IL1 From +200 to -1370 L2=63V L3=63V -1200 +1200 L2 L3 6 6 IL2 From +200 to -1370 IL3 From +200 to -1370

ZOZIK Testing eng. File Name:127211429.doc

Witnessed by:

Witnessed by:

Substation: FAEDA 132/33/11 kV

Contract: KRG-MOE Stage 5

DIRECTIONAL O/C and E/F PROTECTION


Note: Values of injected quantities exceeded threshold values of I>, I0> and Vp 5.3 Sensitivity and timing test by secondary current injection:

5.3.1 Over current Ip> FWD in operating area Polarizing Voltage L1=63V L2=63V L3=63V 0
0

Phase L1 L2 L3
0

Injected (A) 10 10 10

Operation time (sec)

-1200 +120

5.3.2 Over current Ip>> Definite time Polarizing Voltage L1=63V L2=63V L3=63V 0
0 0 0

Phase L1 L2 L3

Injected (A) 17 17 17

Operation time (sec)

-120

+120

5.3.3 Earth Fault Ie> FWD in operating area Polarizing Voltage L1=63V L2=63V L3=63V Oper. area Oper. area Oper. area Phase L1 L2 L3 Injected (A) 0.8 0.8 0.8 Operation time (sec)

5.3.4 Earth Fault Ie>> Definite time Polarizing Voltage L1=63V L2=63V L3=63V Oper. area Oper. area Oper. area Phase L1 L2 L3 Injected (A) 2.5 2.5 2.5 Operation time (sec)

5.3.5 Sensitivity test to Polarizing Voltage for three phase faults in Oper. Area:
Min. Polarizing Voltage:3I> Min. Polarizing Voltage:I0> UL12= 4.5xV3 U0= 5.5 V V UL13= 4.5xV3 V UL23= 4.5xV3 V

5.3.6 Directional Test of E/F protection: Current against U0 L1: +800; -800 L2: +800; -800 L3: +800; -800 Note: Values of injected quantities exceeded threshold values of I>, I0> 6. Other Tests and Checks Circuit breaker tripping and signaling: Autoreclosing initiated by 3I>> and 3I0>>: On load tests and checks performed:

ZOZIK Testing eng. File Name:127211429.doc

Witnessed by:

Witnessed by:

Substation: FAEDA 132/33/11 kV

Contract: KRG-MOE Stage 5

DIRECTIONAL O/C and E/F PROTECTION


Observation of Testing Engineer: Testing Equipment: Freja 300 connecting leads and accessories

ZOZIK Testing eng. File Name:127211429.doc

Witnessed by:

Witnessed by: