Professional Documents
Culture Documents
4.1 Introduction 4.2 Error signal analysis 4.3 4 3 Sensitivity of control systems to parameter variations 4.4 Disturbance signals in a feedback control system 4.5 Control of the transient response 4.6 Steady-state error 4.7 The cost of feedback
Closed-Loop:
Input
+_ Error
Sensor The effects of plant uncertainties and external disturbances appears directly at the output of an open-loop system. This issue can be resolved by feedback control
EE 3510 Control Systems 2
C(s)
+ +
Y(s)=YR(s)+YD(s)+YN(s)
P(s)
+ + Noise N(s)
Contd
D(s) R(s)
+_
C(s)
+ +
Y(s)=YR(s)+YD(s)+YN(s)
P(s)
+ + Noise N(s)
C(s) ( )
P(s) ( ) P(s)
For open-loop systems, the change in the output due to the variation P(s) in the plant is directly amplified as:
C(s)
P(s)
Y(s)
Contd
R(s)
+_
C(s)
P(s)
Y(s)
System Sensitivity
T(s ) =
System sensitivity: it allows you to see how the changes in the plant or sensor affect the system performance It is defined as the ratio of the percentage change in the closedp g g loop transfer function T(s) to the percentage change of the functional-block transfer function
P T
T(s ) =
10
T(s ) =
11
bandwidth
0
|HCP| << 1
12
13
Example: Find SP
d(t)
r(t)
+_
K+11s C(s)
++
1 s(s + 1)
P(s)
y(t)
14
Example: The Non-inverting Amplifier Implemented by an Operational Amplifier (Op-amp) with a Gain A
Based on: R1
_
R2
v-
vo
15
vSince = 0.1:
vo
vi
Op-amp gain = A
R2 = 9R1
16
R1
R2
v-
vo
vi Op-amp gain = A
17
R(s)
+_
D1(s)
e
D2(s)
P(s)
++
C(s) controller
++
YR(s)+YD1(s)+YD2(s)
plant H(s)
sensor
EE 3510 Control Systems 18
Contd
By superposition, calculate YD1(s) and YD2(s) due to D1 and D2, respectively
19
Example
For d(t) is a unity step, what is the steady-state value of yd(t)?
D(s)
R(s) R( )
+_
C(s)
++
P(s)
YR(s)+YD(s)
H(s)
20
10
C2(s) ( )
+_
D(s)
C1(s) ( )
++
P(s) ( )
YD(s)
H1(s) H2(s)
21
R(s)
+_
C(s)
P(s)
Y(s)
H(s)
+ +
Noise N(s)
22
11
1. At low frequencies: the loop gain |HCP| is usually large ( >>1 for sensitivity reduction with respect to disturbance). Then YN(s) = -N(s), no noise reduction. 2. At high frequencies: |HCP| is small, YN(s) = -HCPN(s). Noise is attenuated.
23
System 2
System 1 0 frequency
24
12
25
R2
vo
A 1+ s p1
vi G (s ) = R2 = 9R1
26
13
Contd
27
y(t)
Steady state refers to the response at t = For open-loop systems: parameter variations in the plant (like K2) induce a change of gain such that y(t)|t= deviates from the desired value K2 changes by 10%, the steady-state error immediately becomes 10%
28
14
e(t)
C(s) K1
y(t) P(s)
K2 s + 1
29
Contd
For r(t) is a unit step: For K1K2=100: For K1K2=90: K
30
15
Example: Find the Steady-State Error due to r(t), and the Output yd() due to d(t)
r(t) = u(t)
+_
1 s(s + 1)
P(s)
yR(t)+yD(t)
31
Contd
r(t) = u(t)
+_
1 s(s + 1)
P(s)
yR(t)+yD(t)
32
16
33
y(t)
r(t)
+_
y(t)
C(s) P(s)
1. Increased complexity and the cost 2. Assume the same C(s) in both cases: the reduction in the closed-loop gain is in exchange for sensitivity reduction due to parameter variations and disturbances (important!) 3. Stability: given that the open-loop system C(s)P(s) is stable, the closed-loop system may not be stable, if C(s) is not properly designed
EE 3510 Control Systems
34
17