You are on page 1of 4

etc.

3kg/s 2kg/s 1kg/s

Figure 1: Shown above is the heat transfer from the heat exchanger to the ambient versus the water exit temperature. The range of water mass flows (mw) is from 1kg/s to 10ks/s (the thicker line) and represents each blue line. The red Q limit line represents the minimum value of the heat transfer which is 0kW---the values above this line are invalid and unrealistic because the heat exchanger would be heated by the ambient temperature, which cannot happen under these conditions.

Increasing water mass flow (mw)

1kg/s 2kg/s 3kg/s etc.

Figure 2: Shown above is the entropy generation verses the water exit temperature. The range of water mass flows (mw) is again from 1kg/s to 10kg/s (the bottom thicker line is the 10kg/s line). All of the data above is valid because all produce a positive Sgen.

Increasing water mass flow (mw)

Figure 3: Shown above is the entropy generation verses the water exit temperature like in Figure 2. However, the range of water mass flows (mw) extends to 20kg/s. This extension was done to show the approximate maximum mw that would be possible before the Sgen reaches 0. The Sgen limit line shows where Sgen = 0, thus everything below it is not possible.

Conclusion Therefore I conclude that the following: The water mass flow range: mw is in between 1 and 2kg/s o Figure 1: mw > 2kg/s would produce Q > 0, unless the Twe was below 300 K The exit water temperature: for 1 < mw < 2kg/s, 293.15 < Twe < 325 K The entropy generation: 0 < Sgen < 0.5583 kW/K The heat loss to the ambient: will be no more than about 350, ideally 300 < Q < 350 kW

Increasing water mass flow (mw)

You might also like