Avaliao do A&O, Analysis and Optimization, usando Matlab/Simulink

EDP Bandeirante EDP Escelsa

SIT Clculos/Planejamento:
Eduardo Dutra da Silva Mrcia Regina Oliveira Olvio C. Santos Vincius Santos Souza

Figura 1- Distribution System - LV

Case I: Center-Tap Monophasic Power distribution system a 3-wire, single-phase and midpoint neutral system. A transformer supplying a 3-wire distribution system has a single-phase input (primary) winding. The output (secondary) winding is center-tapped and the center tap connected to a grounded neutral.
(1) MV Line Phase AN Phase AN [deg] = 0 Phase AN [V] = 7968 (2) Transformer Nominal power = 25 [kVA] Winding 1: V1 = 7968 [V] , R1 = 0,50778 [ohm] , L1 = 0,053878 [H] Winding 2: V2 = 120 [V] , R2 = 0,0001152 [ohm] , L2 = 0,000012223 [H] Winding 3: V3 = 120 [V] , R3 = 0,0001152 [ohm] , L3 = 0,000012223 [H]

Magnetization: Rm = 126950 [ohm] , Lm = 336,74 [H] Frequency: 60 [Hz] LV Line: LV Line (3) (4) (5) (6) [m] meters 30 40 30 60 [ohm/km] R1 1,2 1,2 1,2 1,2 [ohm/km] R0 1,9 1,9 1,9 1,9 [H/km] L1 9,5e-4 9,5e-4 9,5e-4 9,5e-4 [H/km] L0 4,5e-3 4,5e-3 4,5e-3 4,5e-3 [F/km] C1 13e-9 13e-9 13e-9 13e-9 [F/km] C0 8e-9 8e-9 8e-9 8e-9

phases AN ABN ABN BN

Loads: Loads (7) (8) (9) (10) (11) (12) (13) (14) phases AN AN ABN AB ABN AB BN BN kW 2 2 4 2 6 1 1 3 kVAR 0,8 0,8 1 0,5 2 1 0 0 Nominal voltage [V] 127 120 240/120 240 220/127 120 120 127

Example:

Results:

Case II: Open Y grounded Open Delta grounded Lagging Case III: Open Y grounded Open Delta grounded Leading
Case IV: Y ungrounded Closed Delta grounded Case V: 3-phases Y - Delta