Southwire Company

Nextera NY Energy Highway Project


7#7 AW
Conductor: 1590.0 Kcmil

54/19 Stranding ACSR

Area = 1.4070 Sq. in


Diameter = 1.545 in
Data from Chart No. 1-1009
English Units
Limits and Outputs in Average Tensions.
Span = 800.0 Feet
Creep IS a Factor
Design Points
Temp
Ice
Wind
F
in
psf
0.0
0.50
4.00
15.0
0.75
4.00
32.0
0.50
2.00
32.0
0.50
0.00
60.0
0.00
21.00
-20.0
0.00
0.00
0.0
0.00
0.00
30.0
0.00
0.00
32.0
0.00
0.00
60.0
0.00
0.00
90.0
0.00
0.00
120.0
0.00
0.00
167.0
0.00
0.00
212.0
0.00
0.00
257.0
0.00
0.00
* Design Condition

"FALCON"
Weight = 2.044 lb/ft

RTS = 54500 lb

Special Load Zone


Rolled Rod
K
lb/ft
0.30
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00

Weight
lb/ft
3.722
4.306
3.343
3.316
3.389
2.044
2.044
2.044
2.044
2.044
2.044
2.044
2.044
2.044
2.044

Sag
Ft
16.68
18.27
17.75
17.71
19.27
12.26
13.50
15.36
15.48
17.18
18.94
20.63
22.11
23.22
24.31

Final
Tension
lb
17887
18889
15096
15008
14101
13348
12129
10662
10577
9533
8651
7949
7418
7067
6751

Initial
Tension
lb
21103
21716
18620
18552
17426
18464
17152
15260*
15139
13528
12013
10738
9179
8080
7252

Sag
Ft
14.13
15.89
14.38
14.32
15.58
8.86
9.54
10.72
10.81
12.10
13.63
15.25
17.85
20.29
22.62

Certain information such as the data, opinions or recommendations set


forth herein or given by Southwire representatives, is intended as a general
guide only. Each installation of overhead electrical conductor,
underground electrical conductor, and/or conductor accessories involves
special conditions creating problems that require individual solutions
and, therefore, the recipient of this information has the sole
responsibility in connection with the use of the information. Southwire does
not assume any liability in connection with such information.