You are on page 1of 1

Southwire Company

Nextera NY Energy Highway Project


7#7 AW
Conductor:

7 # 7 Alumoweld

Area = 0.1145 Sq. in


Diameter = 0.433 in
Data from Chart No. 1-1218
English Units
Limits and Outputs in Average Tensions.
Span = 800.0 Feet
Creep IS a Factor
Design Points
Temp
Ice
Wind
F
in
psf
0.0
0.50
4.00
15.0
0.75
4.00
32.0
0.50
2.00
32.0
0.50
0.00
60.0
0.00
21.00
-20.0
0.00
0.00
0.0
0.00
0.00
30.0
0.00
0.00
32.0
0.00
0.00
60.0
0.00
0.00
90.0
0.00
0.00
120.0
0.00
0.00
167.0
0.00
0.00
212.0
0.00
0.00
257.0
0.00
0.00
* Design Condition

Weight = 0.330 lb/ft

RTS = 19060 lb

Special Load Zone

K
lb/ft
0.30
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00

Weight
lb/ft
1.328
1.572
0.941
0.910
0.826
0.330
0.330
0.330
0.330
0.330
0.330
0.330
0.330
0.330
0.330

Sag
Ft
15.53
17.40
13.50
13.24
13.28
5.40
5.80
6.48
6.53
7.29
8.23
9.30
11.17
13.08
15.02

Final
Tension
lb
6849
7240
5584
5507
4984
4886
4553
4072
4041
3621*
3209
2841
2366
2020
1760

Initial
Tension
lb
7314
7637
6178
6113
5606
5802
5482
5007
4976
4542
4093
3667
3064
2581
2196

Sag
Ft
14.54
16.49
12.20
11.92
11.80
4.55
4.82
5.27
5.31
5.81
6.45
7.20
8.62
10.24
12.03

Certain information such as the data, opinions or recommendations set


forth herein or given by Southwire representatives, is intended as a general
guide only. Each installation of overhead electrical conductor,
underground electrical conductor, and/or conductor accessories involves
special conditions creating problems that require individual solutions
and, therefore, the recipient of this information has the sole
responsibility in connection with the use of the information. Southwire does
not assume any liability in connection with such information.