ULTRA-FILTRATION UNIT
START
ST-03
YES LEVEL
HIGH CUT
LEVEL LSH ST-03LS01
MANUAL
LEVEL LAH ST-03LS02
VALVE ON / 0FF SELECTOR
AUTO
BREAK POWER ON
STEP A
ON
A2=FORWARD FLUSHING A
8 SEC YES VALVE ON 30 MIN UFP-01/02
V1,V2,V3 PUMP RUN
A3=BACKWASH COUNTER-CURRENT
14 SEC RUN
STOP STEP A2
A4=FORWARD FLUSHING B ALARM END
14 SEC
ALARM VALVE ON 8 SEC PUMP ON 8 SEC
YES
RESET V4,V5 UF-BFP01
RESET TIME
STEP A
YES
YES
POWER ON STEP C COUNT
STEP C 1 DAY
YES
YES
BREAK
YES
RUN RUN
STOP STEP B2 STOP STEP C2
ALARM END ALARM END
ALARM ALARM
YES BREAK 60 SEC YES BREAK 60 SEC
RESET RESET
YES VALVE ON 14 SEC PUMP ON 14 SEC YES VALVE ON 14 SEC PUMP ON 14 SEC
V6,V7 UF-BFP01 V6,V7 UF-BFP01
YES VALVE ON 14 SEC PUMP ON 14 SEC YES VALVE ON 14 SEC PUMP ON 14 SEC
V1,V8 UFP-01/02 V1,V8 UFP-01/02
RESET TIME
RESET TIME
STEP C + STEP B +
STEP B + STEP A
STEP A
STEP B NaOCl CLEANING EVERY 60 MIN STEP C HCL CLEANING EVERY 1 DAY
B1=BACKWASH COUNTER-CURRENT WITH NaOCl DOSING C1=BACKWASH COUNTER-CURRENT WITH HCl DOSING
14 SEC 14 SEC
B2=SOAKING C2=SOAKING
60 SEC 60 SEC
A4=RING C4=RING
14 SEC 14 SEC
ROI-ET
DEG-ST01
NO
INTERLOG
HIGH CUT
LEVEL LSH DEG-ST01LS01 REVERES OSMOSIS UNIT
LEVEL LAH DEG-ST01LS02 6/8
RO-HPP01/02
YES UFP-01/02
17m³/hr.@20m
STEP 1 SERVICE PUMP RUN
STEP2 AUTO FLUSHING # 1 STEP 3 RUN
STEP3 AUTO FLUSHING # 2 15 SEC
END
OPEN VALVE
YES PUMP RUN
START MF-02V02/RO-V10 RUN AB01/02
RO-HPP01/02
/RO-V15 DGP-01/02
STEP 4 RUN
120 SEC
MANUAL END
VALVE ON / 0FF SELECTOR
OPEN VALVE
MF-02V12/RO-V10 PUMP RUN
DGP-01/02
AUTO
YES
BREAK RUN PUMP
POWER ON
SERVICE RO UNIT RIP-01/02
RO UNIT 5 SEC
YES
OPEN VALVE
BV-02 5 SEC
FREQUENCY
=2 Hz
RESET TIME
STEP 1
BUZZER LAMP
START
STEP 1 STEP 2 STEP 3
60 MIN 15 SEC 60 SEC
RUN RUN RUN
MANUAL
SELECTOR
AUTO
CONDUCT HIGH
RO-CON01
YES
STEP 4
RUN
CONDUC HIGH
10 SEC
YES YES
ALARM
ONLY
ON VALVE
VALVE ON VALVE OFF VALVE/MF-02V12
BV-05 RO-V10
RO-CON01 RO-CON01
STEP 2+STEP 3 IN TERLOG CONDUCT HIGH CONDUCT LOW
LOW CUT 10 SEC 10 SEC
ON VALVE
ON VALVE ON VALVE ON VALVE VALVE/RO-V10
VALVE/RO-V15 VALVE/RO-V13 VALVE/BV-05 (RO-V15 ON 10 SEC)
ROI-ET
3/8
START RWP-01/02
70m³/hr.@35m.
PUMP SUPPLY-AREVA
INSTALLATION-WD
RAW WATER PUMP
MANUAL
SELECTOR
AUTO
YES
ST-01
BY OTHER-RCC ON LEVEL LSH ST-01LS01
INTERLOCK
NOT HIGH CUT GROUND
LEVEL LAH ST-01LS02
(W.2,500xL.8,000xH3,000
(2,500)mm.)
YES
FREQUENCY=
2 Hz RUN
BUZZER LAMP
YES YES
ROI-ET
3/8
CP-01/02
50LPH@10BARS
START
MANUAL
SELECTOR
AUTO
CT-01
PE:1,000L.
NO
STOP D1,030xH1,490xT10mm. LEVEL LSL CT-01LS01
INTERLOCK
ALARM NOT LOW CUT (PAC)
YES
SIGNAL RWP-01/02
PUMP ON 70m³/hr.@35m.
RWP-01/02 PUMP SUPPLY-AREVA
YES
RUN
FREQUENCY
=2 Hz
BUZZER LAMP
PUMP CP-01 PUMP CP-02
YES YES
ROI-ET
3/8
CP-03/04
1.9LPH@17.3BARS
START
MANUAL
SELECTOR
AUTO
CT-02
PE:1,000L.
NO
STOP INTERLOCK D1,030xH1,490xT10mm. LEVEL LSL CT-02LS01
ALARM NOT LOW CUT (NaOCl)
YES
SIGNAL RWP-01/02
RWP-01/02 70m³/hr.@35m.
PUMP ON PUMP SUPPLY-AREVA
YES
RUN
FREQUENCY
=2 Hz
BUZZER LAMP
PUMP CP-03 PUMP CP-04
ROI-ET
3/8
CP-05/06
120LPH@7BARS
START
MANUAL
SELECTOR
AUTO
CT-04
PE:1,000L. LEVEL LSL CT-04LS01
NO
STOP INTERLOCK D1,030xH1,490xT10mm.
ALARM NOT LOW CUT (POLYMER)
YES
SIGNAL RWP-01/02
RWP-01/02 70m³/hr.@35m.
PUMP ON PUMP SUPPLY-AREVA
YES
RUN
FREQUENCY
=2 Hz
BUZZER LAMP
PUMP CP-05 PUMP CP-06
YES YES
ROI-ET
3/8
MX-01
START PAC MIXING
SELECTOR
ON / OFF
YES
STOP
RESET MOTOR MX-01
ALARM
FREQUENCY
=2 Hz
BUZZER LAMP
YES
MOTOR TRIP
ROI-ET
START MX-02
POLYMER MIXING
SELECTOR
ON / OFF
YES
STOP
RESET MOTOR MX-02
ALARM
FREQUENCY
=2 Hz
BUZZER LAMP
YES
MOTOR TRIP
ROI-ET
4/8
FFP-01/02
70m³/hr.@26m.
START
FILTER FEED PUMP
MANUAL
SELECTOR
AUTO
ST-01
BY OTHER-RCC ON LEVEL LAL ST-01LS03
STOP NO IN TERLOCK
GROUND LEVEL LSL ST-01LS04
ALARM NOT LOW CUT
(W.2,500xL.8,000xH3,000
(2,500)mm.)
YES
ST-02
NOT HIGH CUT BY OTHER-RCC ON GROUND
INTERLOCK (W8,000xL10,000xH3,000(2,500)m.)
FREQUENCY RUN
=2 Hz
BUZZER LAMP
YES YES
ROI-ET
4/8
BWP-01
START 140m³/hr.@18m.
BACK WASH PUMP
MANUAL
SELECTOR
AUTO
ST-02
NO BY OTHER-RCC ON GROUND
STOP INTERLOCK (W8,000xL10,000xH3,000(2,500)m.)
ALARM NOT LOW CUT
LEVEL LAL ST-02LS03
LEVEL LSL ST-02LS04
YES
FREQUENCY
=2 Hz
BUZZER LAMP
PUMP BWP-01
TRIP
YES
ROI-ET
4/8
WSP-01/02
53 m³/hr.@ 50M.
PUMP SUPPLY-
AREVA
INSTALLATION-WD
START
MANUAL
SELECTOR
AUTO
ST-02
BY OTHER-RCC ON GROUND
NO (W8,000xL10,000xH3,000(2,500)m.)
STOP INTERLOCK
ALARM NOT LOW CUT LEVEL LAL ST-02LS03
LEVEL LSL ST-02LS04
YES
YES
RUN
FREQUENCY
=2 Hz
BUZZER LAMP
PUMP WSP-01 PUMP WSP-02
YES YES
ROI-ET
4/8
UFP-01/02
17m³/hr.@20m
UF FEED PUMP
START
MANUAL
SELECTOR
AUTO
ST-02
BY OTHER-RCC ON GROUND
(W8,000xL10,000xH3,000(2,500)m.)
NO
STOP INTERLOCK
ALARM NOT LOW CUT LEVEL LAL ST-02LS03
LEVEL LSL ST-02LS04
YES
NO
PSL PRESSURE SWITCH
NOT LOW CUT UF-01PS01
YES
RUN
FREQUENCY
=2 Hz
BUZZER LAMP
PUMP UFP-01 PUMP UFP-02
YES YES
ROI-ET
5/8
CIP-01P01
17m³/hr.@22m.
START
MANUAL
SELECTOR
AUTO
CIP-01T01
NO
STOP INTERLOCK LEVEL LSL CIP-01LS01
ALARM NOT LOW CUT
YES
PUMP CIP-01P01
RESET
FREQUENCY
=2 Hz
PUMP CIP-01P01
BUZZER LAMP TRIP
YES
ROI-ET
5/8
UF-BFP01
68m³/hr.@24m.
START
MANUAL
SELECTOR
AUTO
NO ST-03
STOP INTERLOCK
ALARM NOT LOW CUT LEVEL LAL ST-03LS03
LEVEL LSL ST-03LS04
YES
NO
SIGNAL HIGH PRESSURE SWITCH
UF-01PS02 UF-01PS02
YES
PUMP UF-BFP01
RESET
FREQUENCY
=2 Hz
YES
ROI-ET
START 5/8
UF-CP01/02
7.6LPH@3.5BAR
S
MANUAL
SELECTOR
AUTO
UF STEP B1 ON
UF-BFP-01
UF-CT01
NO
STOP INTERLOCK PE:100L.
ALARM NOT LOW CUT D500xH660xT5.5mm. LEVEL LSL UF-CT01LS01
(CEB-01;NaOCl 10%)
YES
RUN
FREQUENCY
=2 Hz
BUZZER LAMP
PUMP UF-CP01 PUMP UF-CP02
ROI-ET
START 5/8
UF-CP03/04
7.6LPH@3.5BARS
MANUAL
SELECTOR
AUTO
UF STEP C1 ON
UF-BFP-01
NO UF-CT02
STOP INTERLOCK PE:100L.
ALARM NOT LOW CUT D500xH660xT5.5mm. LEVEL LSL UF-CT02LS01
(CEB-02;HCl 35%)
YES
RUN
FREQUENCY
=2 Hz
BUZZER LAMP
PUMP UF-CP03 PUMP UF-CP04
ROI-ET
5/8
RIP-01/02
13.3m³/hr.@23M.
START
MANUAL
SELECTOR
AUTO
ST-03
NO
INTERLOCK LEVEL LAL ST-03LS03
NOT LOW CUT LEVEL LSL ST-03LS04
YES
DEG-ST01
LEVEL LSH DEG-ST01LS01
STOP INTERLOCK LEVEL LAH DEG-ST01LS02 RO STEP3 &
ALARM HOT HIGH CUT BV-02 ON 5 SEC
YES YES
SIGNAL RO UNIT
SIGNAL ON STEP1 SERVICE&
RO UNIT STEP2 FLUSHING 1&STEP3&
BV-02 ON 5 SEC
YES
RUN
FREQUENCY
=2 Hz
YES YES
ROI-ET
6/8
CP-07/08
1.9LPH@17.3BARS
START
MANUAL
SELECTOR
AUTO
RO-PH01
NO DELAY 5SEC
ALARM SIGNAL HIGH = 8 START
RO-PH01 = 7 STOP
YES
NO SIGNAL
PUMP RUN
RIP-01/02
YES
CT-05
NO (HCl 35%)
STOP INTERLOCK
ALARM LOW CUT LEVEL LSL CT-05LS01
YES
RUN
FREQUENCY
=2 Hz
BUZZER LAMP
PUMP CP-07 PUMP CP-08
ROI-ET
START 6/8
CP-09/10
1.0LPH@20.7BARS
MANUAL
SELECTOR
AUTO
ORP
HIGH
RANG
YES
SIGNAL
PUMP RUN
RIP-01/02
YES
CT-06
(DECHLORINATION)
STOP INTERLOCK
LOW CUT LEVEL LSL CT-06LS01
ALARM
YES
RUN
FREQUENCY
=2 Hz
BUZZER LAMP
PUMP CP09 PUMP CP010
ROI-ET
6/8
CP-11/12
1.0LPH@20.7BARS
START
MANUAL
SELECTOR
AUTO
SIGNAL
RO SERVICE
YES
SIGNAL
PUMP RUN
RIP-01/02
YES
CT-07
NO (ANTI-SCALE)
STOP INTERLOCK
ALARM LOW CUT LEVEL LSL CT-07LS01
YES
RUN
FREQUENCY
=2 Hz
BUZZER LAMP
PUMP CP11 PUMP CP12
ROI-ET
START
6/8
ORP
CONTROL
VALVE
BV-02 / MF-02V02
STOP PUMP
RESET RIP-01/02
ALARM
RUN
YES
FREQUENCY
=2 Hz
SIGNAL ON RO UNIT
SIGNAL ON ( STEP SERVICE & STEP FLUSHING 1 )
RO UNIT
BUZZER LAMP
YES
ORP HIGH
DELAY TIME SIGNAL ORP
20 SEC RO-ORP01
HIGH
BREAK
SIGNAL ORP SIGNAL ORP
SERVICE
HIGH LOW
RO UNIT
START START
MANUAL MANUAL
SELECTOR SELECTOR
AUTO AUTO
YES YES
ON VALVE
ON VALVE / BV-02
VALVE/MF-02V02
ROI-ET
START 6/8
RO-HPP01/02
13.3 m³/hr.@
125 m.
MANUAL
SELECTOR
AUTO
YES
FREQUENCY
=2 Hz ONE DUTY ONE STANDBY
RUN PUMP ALTERATIVE EVERY
BUZZER LAMP RO-HPP01/02 12 OPERATION HOURS
AND EVERY TRIP
YES YES
YES YES
MANUAL
SELECTOR
AUTO
NO
STOP IN TERLOCK
ALARM CIP-02P01
LOW CUT
LEVEL LSL CIP-02LS02
YES
PUMP CIP-02P01
RESET
FREQUENCY
=2 Hz
YES
ROI-ED
6/8
MX-03
DECHLORINATION
MIXING
START
SELECTOR
ON / OFF
YES
STOP
RESET MOTOR MX-03
ALARM
FREQUENCY
=2 Hz
BUZZER LAMP
YES
MOTOR TRIP
ROI-ET
7/8
AB-01/02
START
MANUAL
SELECTOR
AUTO
SIGNAL RO
STEP 1+2+3
YES
YES
FREQUENCY=
2 Hz ONE DUTY ONE STANDBY
RUN AIR BLOWER ALTERATIVE EVERY
BUZZER LAMP AB-01/02 12 HOURS OPERATION AND
EVERY TRIP
RUN
YES YES
STOP STOP
ALARM ALARM
ROI-ET
7/8
DGP-01/02
11m³/hr.@47M.
START
RESET
MANUAL
SELECTOR
FREQUENCY
=2 Hz
AUTO
BUZZER LAMP
DEG-ST01
STOP INTERLOCK LEVEL LAL DEG-ST01LS03
ALARM LOW CUT LEVEL LSL DEG-ST01LS04
YES
SIGNAL
MAKE UP BOILER TANK 75 m³ RO-STEP 4&
MAKE UP
AREVA’S SCOPE ST04-V02
BOILER ON
YES YES
RUN
MMB-01CON02 MMB-01CON02
DELAY ON/OFF DELAY ON/OFF
10 SEC 10 SEC
NO STOP NO
SIGNAL CONDUCT SIGNAL CONDUCT
ALARM
HIGH CUT HIGH CUT
YES YES
START
OFF
SELECTOR
ON
RUN
YES YES
FREQUENCY=
2 Hz
START
SELECTOR
ON / OFF
YES
STOP
RESET PUMP CP-13
ALARM
FREQUENCY
=2 Hz
BUZZER LAMP
YES
PUMP CP-13 TRIP
ROI-ET
8/8
CP-14/15 PH01
START START
ST-04V02
MANUAL MANUAL
SELECTOR SELECTOR
AUTO AUTO
ST-04
LEVEL LSH ST-04LS01 FLOW RANG FLOW MMB-01F05
NOT HIGH CUT
>3 Q / hr RANG
>3 Q / hr
YES YES
CT-12
ON VALVE INTERLOCK LEVEL LSL CT-12LS01
VALVE/ST-04V02 LOW CUT
YES
PH RANG pH RANG
CP-14/15 PH01 CP-14/15pH01
YES
proportional
RUN
8/8
RGP-01/02
START
MANUAL
SELECTOR
AUTO
NO ST-04
STOP INTERLOCK LEVEL LAL ST-04LS02
ALARM NOT LOW CUT LEVEL LSL ST-04LS03
YES
RUN
FREQUENCY
=2 Hz
YES YES