Project Title:

PURLIN GEOMETRY
Purlin type C15024
Purlin spacing (m) 1.00
Purlin Span (m) 3.00
Roof pitch (Degree) 4.00
No. of tie rod or bridging 1.00
Building height (m) 15.00
Connection method D DOUBLE SPAN
DESIGN LOAD
Dead load (kN/m2) 0.25
Live load (kN/m2) 0.50
Wind load (kN/m2) 0.49
Yield strength of steel Fy (MPa) 450
DESIGN RESULT SUMMARY
Moment
Moment ratio due to ultimate load
= Wux/Wcx+Wuy/Wcy 0.10 <1.00 O.K.!
Moment ratio due to ultimate load with wind suction
= Wuw/Wcx+Wuy/Wcy 0.04 <1.00 O.K.!
Shear (kN) 4.60
Use 2 Nos. of M12 Bolt & Nuts Gr 4.6 O.K.!
Deflection
Deflection due to live + dead load (unfactored), mm 0.69 <L/150 Limit, O.K.!
Deflection due to deal load alone (unfactored), mm 0.26 <L/150 Limit, O.K.!
OVERALL CHECK
SECTION PROPERTIES OF PURLIN
Ixx ( x 106 mm4) 2.43
Iyy ( x 104 mm4) 0.39
Zxx ( x 103 mm3) 33.50
Zyy ( x 103 mm3) 8.78
Self weight (kg/m) 5.88
Moment capacity Mcx (kN.m) 15.08
Moment capacity Mcy (kN.m) 3.95
DESIGN ACTION
Total dead load Wd (kN) 0.92
In x-x axis Wdx (kN) 0.92
In y-y axis Wdy (kN) 0.06
Total live load Wl (kN) 1.50
In x-x axis Wlx (kN) 1.50
In y-y axis Wly (kN) 0.10
Total wind load Wwx (kN) 1.47
ULTIMATE LOAD
Ultimate load in x-x axis Wux (kN) 3.68
Ultimate load in y-y axis Wuy (kN) 0.26
Ultimate load with wind suction Wuw (kN) -1.14
MAXIMUM MOMENT
Due to ultimate load, in x-x axis Mux (kN.m) 1.38
Due to ultimate load, in y-y axis Muy (kN.m) 0.05
Due to wind suction, in x-x axis Muw (kN.m) -0.43
PURLIN DESIGN
PURLIN QUICKPICK V21 8/9/2014...8:29 AM 1 of 2
MAXIMUM SHEAR (kN)
Verical shear at supports (kN) 4.60
MAXIMUM DEFLECTION
Deflection due to live + dead load (unfactored), mm 0.69
Deflection due to deal load alone (unfactored), mm 0.26
DESIGN CHECK
Moment BS 5950
Moment ratio due to ultimate load
Mux/Mcx+Muy/Mcy = 0.10 <1.00 O.K.! Clause 1:4.8.2
Moment ratio due to ultimate load with wind suction
Muw/Mcx+Muy/Mcy = 0.04 <1.00 O.K.! Clause 1:4.8.2
Shear (kN) 4.60
Use 2 Nos. of M12 Bolt & Nuts Grade 4.6 at purlin end O.K.!
Deflection
Limit L/150 due to live & dead load, mm 20.00
Limit L/250 due to dead load alone, mm 12.00
Deflection due to live + dead load (unfactored), mm 0.69 <L/150 Limit, O.K.! Clause 1:4.12.2
Deflection due to deal load alone (unfactored), mm 0.26 <L/150 Limit, O.K.! Table 5
PURLIN QUICKPICK V21 8/9/2014...8:29 AM 2 of 2