Novaris Pty Ltd ABN: 33 065 427 232 72 Browns Road, Kingston, TAS. 7050 TEL: +61 3 6229 7233 AUSTRALIA FAX: +61 3 6229 9245 Copyright 2003 Novaris E-mail: sales@novaris.com.au SIGNAL LINE PROTECTORS RS422 / RS485 DIN rail DINsafe
Product Description
Novaris DINsafe signal line protectors are designed for the effective protection against lightning induced overvoltages on process control, telemetry, PLC, telecommunications and information technology systems.
The RS422 / RS485 protector is designed for the protection of PLC and other distributed control systems using RS422 and RS485 data highway protocols. Each unit provides protection for up to two circuits for the transmit and receive lines.
Operation
Multistage transient protection is utilised with gas filled arresters, as the first stage, absorb the majority of the energy.
Fine protection consisting of a secondary clamping stage absorbs residual let through energy from the gas arrester. In the RS422 / RS485 protector a unique circuit is utilised to minimise loading caused by component capacitance. This results in a usable frequency response to beyond 20MHz so that high- speed digital signals can pass without attenuation or distortion.
The secondary clamping circuit provides an exact clamping voltage of 10V regardless of the magnitude of the incoming surge.
Protection is provided for both common and transverse mode disturbances, with an isolated frame ground providing a low impedance to frame under surge conditions. However, this appears as an open circuit under normal conditions. This technique eliminates noise, which may be introduced by earth loops.
Installation
Install one unit at each item of equipment to be protected. When screened cable is used connect the screen to the SCR connection. Connect the frame ground stud to the earth of the equipment. In the two pair version 2 circuits are provided for the transmit and receive lines. If these lines are in a single cable, only one screen connection is necessary. Regardless of the direction of signal flow, always connect the LINE to the external cable side.
Specifications
Description: Multistage overvoltage protection for RS422 / RS485 signalling DIN mount Lines protected: 1 or 2 circuits Clamping voltage: 10 V DC Loop Resistance: 8 Protection modes: Transverse and common mode Protection stages: Gas arrester/Transorb network Surge withstand: IEEE C62.41 cat, A, B, C AS1768-1991 cat. A, B, C Let-through voltage (5kV 10/700s): Line-Line: 16V Line-Screen: 18V Surge rating: 20kA for 8/20s pulse Frequency response: < 1dB attenuation at 20MHz Dimensions (mm): SL1DIN-485: 80H x 116D x 18W SL2DIN-485: 80H x 116D x 28W Mounting: DIN rail. Panel mount brackets available on request.