Static Pressure Calculator

L = CENTER DISTANCE INCHES


DUCT DIA

34
18

VELOCITY
Q = Air Flow Rate, CFM
D = DUCT DIA IN FEET
A = AREA, Feet Squared
V = AIR VELOCITY, Feet Per Minute
VP = VELOCITY PRESSURE
L = CENTER LINE DISTANCE, Feet
C = DYNAMIC LOSS COEFFICIENT

1500
2650.725
1.5
1.76715
1500
0.1402741
2.8333333
1.25

DUCT STATIC PRESURE = FRICTION LOSS + DYNAMIC LOSS


SPF = FRICTION LOSS
SPD = DYNAMIC LOSS

0.0051668
0.1753426

SP = STATIC PRESSURE

0.18051

1. Enter number for L in inches


2. Enter Duct Diameter
3. Enter Velocity
4. Enter C - dynamic loss coefficient
5. Then get SP for each piece of duct
6. Do this for each duct piece to get Total SP for system

ystem

PART

L Center Distance in Inches

Factory Installed Riser


Field Installed Riser
Straight Duct
Adjustable Duct
Adaptor (all sizes)
90 Elbow (8" diameter)
90 Elbow (10" diameter)
90 Elbow (12" diameter)
90 Elbow (14" diameter)
90 Elbow (16" diameter)
90 Elbow (18" diameter)
90 Elbow (20" diameter)
90 Elbow (24" diameter)
45 Elbow (8" diameter)
45 Elbow (10" diameter)
45 Elbow (12" diameter)
45 Elbow (14" diameter)
45 Elbow (16" diameter)
45 Elbow (18" diameter)
45 Elbow (20" diameter)
45 Elbow (24" diameter)
Duct Tee (8" diameter)
Duct Tee (10" diameter)
Duct Tee (12" diameter)
Duct Tee (14" diameter)
Duct Tee (16" diameter)
Duct Tee (18" diameter)
Duct Tee (20" diameter)
Duct Tee (24" diameter)
Y Tee (12" diameter)
Y Tee (14" diameter)
Y Tee (18" diameter)
Y Tee (20" diameter)
Y Tee (24" diameter)
Off Set Collar

4
4
Depends on Length
Depends on Length minus Minimum Overlap
13
15
16
17.5
18.7
21
22
23.5
26.5
8.8
9.5
10.2
10.9
11.6
12.3
13
14.4
15
17
19
21
23
25
27
31
28
30
33.5
35.5
54
4 when matched with horizontal run

8" Duct Diameter


Duct Component

Dynamic Loss Coefficient

RISER/FRISER
STRAIGHT/ADJ
ADAPTOR (8 TO 12)
90 ELBOW
45 ELBOW
DUCT TEE

0.017
See Design Guide
0.797
0.400
0.150
1.250

10" Duct Diameter


Duct Component

Dynamic Loss Coefficient

RISER/FRISER
STRAIGHT/ADJ
ADAPTOR (10 TO 14)
90 ELBOW
45 ELBOW
DUCT TEE

0.013
See Design Guide
0.470
0.420
0.150
1.250

12" Duct Diameter


Duct Component

Dynamic Loss Coefficient

RISER/FRISER
STRAIGHT/ADJ
ADAPTOR (12 TO 18)
90 ELBOW
45 ELBOW
DUCT TEE
Y TEE

0.011
See Design Guide
0.797
0.440
0.150
1.250
0.600

14" Duct Diameter


Duct Component

Dynamic Loss Coefficient

RISER/FRISER
STRAIGHT/ADJ
ADAPTOR (14 TO 20)
90 ELBOW
45 ELBOW
DUCT TEE
Y TEE

0.010
See Design Guide
0.522
0.460
0.150
1.250
0.600

16" Duct Diameter


Duct Component

Dynamic Loss Coefficient

RISER/FRISER
STRAIGHT/ADJ

0.008
See Design Guide

ADAPTOR (16 TO 24)


90 ELBOW
45 ELBOW
DUCT TEE

0.797
0.480
0.150
1.250

18" Duct Diameter


Duct Component

Dynamic Loss Coefficient

RISER/FRISER
STRAIGHT/ADJ
90 ELBOW
45 ELBOW
DUCT TEE
Y TEE

0.006
See Design Guide
0.500
0.150
1.250
0.600

20" Duct Diameter


Duct Component

Dynamic Loss Coefficient

RISER/FRISER
STRAIGHT/ADJ
90 ELBOW
45 ELBOW
DUCT TEE
Y TEE

0.005
See Design Guide
0.520
0.150
1.250
0.600

24" Duct Diameter


Duct Component

Dynamic Loss Coefficient

RISER/FRISER
STRAIGHT/ADJ
90 ELBOW
45 ELBOW
DUCT TEE
Y TEE

0.004
See Design Guide
0.540
0.150
1.250
0.600

Straight and Adjustable Dynamic Loss Coefficient Table

nt Table

Duct Velocity (V) = CFM/Area (in ft sq) = FPM


Round Area
8" = 50.24 in sq or 0.348 ft sq
10" = 78.5 in sq or 0.545 ft sq
12" = 113.04 in sq or 0.79 ft sq
14" = 153.86 in sq or 1.07 ft sq
16" = 200.96 in sq or 1.40 ft sq
18" = 254.34 in sq or 1.77 ft sq
20" = 314.00 in sq or 2.18 ft sq
24" = 452.16 in sq or 3.14 ft sq
Square Area
12" = 144 in sq or 1.00 ft sq
14" = 196 in sq or 1.36 ft sq
16" = 256 in sq or 1.78 ft sq
18" = 324 in sq or 2.25 ft sq
20" = 400 in sq or 2.78 ft sq
22" = 484 sq in or 3.36 ft sq
24" = 576 sq in or 2.00 ft sq