You are on page 1of 66

Knowledge Is Power

SM

Apparatus Maintenance and Power Management


for Energy Delivery

Brief Introduction for Power Swing


Detection Methods & Testing
Kamin Dave
Application Engineer (Protective Relaying)

DOBLE ENGINEERING COMPANY


Doble Conference - 2007

Basic definitions:
Power Swing: A variation in three phase power flow which occurs when
the generator rotor angles are advancing or retarding relative to each other
in response to changes in load magnitude and direction, line switching,
loss of generation, faults, and other system disturbances.
Pole Slip: A condition whereby a generator, or group of generators,
terminal voltage angles (or phases) go past 180 degrees with respect to
the rest of the connected power system.
Stable Power Swing: A power swing is considered stable if the generators
do not slip poles and the system reaches a new state of equilibrium, i.e. an
acceptable operating condition.

Unstable Power Swing: A power swing that will result in a


generator or group of generators experiencing pole slipping for
which some corrective action must be taken.
Knowledge Is Power

SM

Apparatus Maintenance and Power Management


for Energy Delivery

Power swing due to;


Power system faults (System more affected on 3-ph
fault, so power gain is very less)
Sudden changes to electrical power due to rejection of
load or generators
These type of disturbances causes oscillation in
machine rotor angles (Load Angle = 900 or 1200) & can
result in sever power flow swings. Power swings are
variations in power flow that occur when the internal
voltages of generators at different network locations of
the power system slip relative to each other.

Knowledge Is Power

SM

Apparatus Maintenance and Power Management


for Energy Delivery

Vector diagram: two machines


Two Machine Problem
E1

E2
ZL

ZS1

ZS2

UB

UA

L ZS1

L ZS2

L ZL

E2 = E'2

E1

UA

UB
U'B

U'A
E'1

'

'L

Pmax = {(E1*E2)/X}*SIN(theta)
If the Load angle becomes too large, the system stability can be lost
Knowledge Is Power

SM

Apparatus Maintenance and Power Management


for Energy Delivery

Figure:-1

Power diagram:
Power Diagram
300

Pmax = {(E1*E2)/X}*SIN(theta)

250

Power

200

Critical Angle

150

Stability region

100

Stability limit

50
0
0

50

100

150

200

Angle in Degree

Rotor Angle

If the Load angle becomes too large, the system stability can be lost
Knowledge Is Power

SM

Apparatus Maintenance and Power Management


for Energy Delivery

Figure:-1A

Power swing detection methods:


Conventional Rate of Change of Impedance
(Dz/Dt) Methods:
Concentric characteristic schemes.
Continuous Impedance calculation schemes.
Blinder Schemes:
1) Single Blinder
2) Double Blinder

Knowledge Is Power

SM

Apparatus Maintenance and Power Management


for Energy Delivery

Conventional PSB detection methods:


It measures the Positive sequence impedance
During a system swing, the measured impedance
moves slowly on the impedance plane, and the rate of
impedance change is determined by the slip frequency
of an equivalent two-source system
Travel Time (Delta-t) from one point to next point is to
differentiate between fault & swing.
Travel time is more than set value then, distance relay
sense as swing.
Travel time less than set value then, it sense as fault

Knowledge Is Power

SM

Apparatus Maintenance and Power Management


for Energy Delivery

Conventional PSB detection methods:


Concentric circle characteristic schemes:
It is simplest method to detect rate of change of
impedance
Two impedance zones. Inner zone & outer zone
Figure-3 shows, Relay indicates PSB when transition
time of impedance from outer zone to inner zone is
more than set value (impedance locus move slowly).
PSB: Blocks the zones when swing is stable (Figure:-3)
OST: Trip zones when swing is un stable (Figure-4)
Major drawback of this characteristic is load
encroachment.
Knowledge Is Power

SM

Apparatus Maintenance and Power Management


for Energy Delivery

Concentric characteristic scheme: MHO Circle


Set Zin & Zout on line angle

Swing Locus
Stable Swing

t = time for transition of Z from outer to inner zone

Knowledge Is Power

SM

Apparatus Maintenance and Power Management


for Energy Delivery

Figure:-3

Concentric characteristic scheme: MHO Circle


t

Un stable Swing

t = time for transition of Z from outer to inner zone


Knowledge Is Power

SM

Apparatus Maintenance and Power Management


for Energy Delivery

Figure:-4

Concentric characteristic scheme: MHO Circle


Set Zin & Zout on line angle

R & X reach are


dependent on Z value
Difficult to set on
Load Encroachment

Load

t = time for transition of Z from outer to inner zone

Knowledge Is Power

SM

Apparatus Maintenance and Power Management


for Energy Delivery

Figure:-5

Concentric characteristic scheme: Lens


Avoid mal operation during
load encroachment

Load

Knowledge Is Power

SM

Apparatus Maintenance and Power Management


for Energy Delivery

Figure:-6

Conventional PSB detection methods:


Concentric characteristic schemes:
Polygon Characteristic concept is much more better
than concentric circle characteristic.
Rset & Xset for out zone can able to set independently.
Rset of outer zone can not reach in to Load region

Knowledge Is Power

SM

Apparatus Maintenance and Power Management


for Energy Delivery

Concentric characteristic scheme: Polygon


Characteristic in relay type REL511
Polygon Characteristic for Power swing detection: Set R & X reach independently

Set X reach

X
ZS1

Dz2/Dt2
Dz4/Dt4

ZL
2

Dz1/Dt1
1

Dz3/Dt3

0
0

ZS1

Inner boundary = Zin

Zload

Set R reach

Outer boundary = Zout

Knowledge Is Power

SM

Apparatus Maintenance and Power Management


for Energy Delivery

Figure:-7

Concentric characteristic scheme: Polygon


Characteristic in relay type 7SA610
Polygon Characteristic: Set R reach according to Load Encroachment

Angle = 45o
Load Angle = 120o or 90o

t = time for transition of Z from outer to inner zone

Knowledge Is Power

SM

Apparatus Maintenance and Power Management


for Energy Delivery

R reach reduce for


Load encroachment

Figure:-8

Concentric characteristic scheme: Polygon


Characteristic in relay type 7SA610

E1 > E2

ZS2

E1 = E2

ZL

'

A
ZLoad

E1 < E2

load point
R

ZS1

Knowledge Is Power

SM

Apparatus Maintenance and Power Management


for Energy Delivery

Figure:-9

Concentric characteristic scheme: Quadrilateral


Quadrilateral Characteristic: Set R reach according to Load Encroachment
Line Angle

Load

t = time for transition of Z from outer to inner zone

Knowledge Is Power

SM

Apparatus Maintenance and Power Management


for Energy Delivery

Figure:-10

Concentric characteristic scheme: Polygon


Characteristic in relay type RELZ 100
Quad + Polygon

Stable Swing
Z4(t4)
Z3(t3)
Z2(t2)

Z1(t1)

Unstable Swing

Zone 3 limit
Zout boundary

Timer unit count to starts travel time when Power swing locus crosses Zout boundary
Travel time (Delta T) more than set time, relay detect as a Power swing

Knowledge Is Power

SM

Apparatus Maintenance and Power Management


for Energy Delivery

Figure:-11

Concentric characteristic scheme: Polygon


Characteristic in relay type P442

Line Angle

Knowledge Is Power

SM

Apparatus Maintenance and Power Management


for Energy Delivery

Figure:-12

Continuous Impedance calculation for PSB


detection methods:
Scheme determine Power swing condition based on a
continuous impedance calculation. i.e for each 2ms or 5ms
step an impedance calculation is performed & compared with
the impedance calculation of previous 2ms or 5ms.
This step value is depend on sampling freq. rate.
The next impedance that should be calculated 2ms or 5ms
later is predicted based on impedance difference of the
previous measured impedances.
Not required any delta impedance settings
Require delta time settings
Drawback is; if prediction is correct, then only distance prot.
consider as a traveling impedance & a power swing condition
is detected.
For security reason additional predictive calculation is
required

Knowledge Is Power

SM

Apparatus Maintenance and Power Management


for Energy Delivery

Continuous Impedance calculation for PSB


detection methods:

Knowledge Is Power

SM

Apparatus Maintenance and Power Management


for Energy Delivery

Figure:-13

Continuous Power calculation for PSB detection


methods: Polygon characteristic in relay type P437
X

Setting Parameters:

Stable Swing

Rset
Xset
Line Angle

Zpos(t)
Unstable Swing

-R

-X

Detect as Fault:
Zpos(t1) = 0 ms
Zpos(t2) < 40 ms

Knowledge Is Power

SM

Apparatus Maintenance and Power Management


for Energy Delivery

Detect as Swing:
Zpos(t1) = 0 ms
Zpos(t2) > 40 ms

Figure:-14

Continuous Power calculation for PSB detection


methods: Polygon characteristic in relay type P437

Relay measures the rate of change of Positive sequence


Apparent Power:
Delta-SPOS = (SPOS2 SPOS1) / (SPOS2)
Let,
SPOS1 = Positive sequence Apparent Power at time (t1)
SPOS2 = Positive sequence Apparent Power at time (t1 + 40 ms)

Knowledge Is Power

SM

Apparatus Maintenance and Power Management


for Energy Delivery

Pole slip detection method: Relay type REM54


Scheme is applicable for Out of Step tripping of Generator
Pole slip detection = OMHO characteristic + Counter
Counter count number of operation
Reset time required to set properly other wise it will detect loss of field function
Normally counter setting is 3 or 4
-R

Xd / 2

1
2

XS

Counter Reset

Counter

-X

Offset mho
characteristic
Operating Region

Knowledge Is Power

SM

Apparatus Maintenance and Power Management


for Energy Delivery

Figure:-15

Pole slip detection method: Relay type REG 316


Pole-Slip Characteristic

Trip When Load angle is


More than Trip Angle

Tripping Angle

X in Ohm

ZA

Warning Angle

-7

-5

-3

-1

-1

ZC
-3

ZB

-5

-7
Knowledge
Is Power

SM

R in Ohm
Apparatus Maintenance
and Power Management
for Energy Delivery

Figure:-16

Pole slip detection method: Relay type REG 316


System Load angle is more than set value with calculated slip
freq., relay will detect pole slip (Power swing)
Relay calculating Freq slip based on T-Slip time (say 55 ms)
Tripping Angle setting should be based on critical angle of
machine
Without system study, recommended angle setting is 120o

Knowledge Is Power

SM

Apparatus Maintenance and Power Management


for Energy Delivery

Blinder Schemes: Single Blinder


Blinder schemes:
Single Blinder (one pair) scheme (Figure:-17):
One sets of blinders: Resistive reach inner (RRI) & Resistive
reach outer (RRO)
It can be used to restrict tripping of the distance relay for loads
outside of the blinders.

Knowledge Is Power

SM

Apparatus Maintenance and Power Management


for Energy Delivery

Blinder Schemes: Single Blinder


DR/DT schemes:
Single Blinder scheme (Figure:-17):
One sets of blinders:
It can be used to restrict tripping of the distance relay for loads
outside of the blinders.
If travel time is more than set time & it crosses blinder-1, a
power swing situation is detected further it crosses blinder-2
then it gives a tripping.
Scheme is more suitable for out of step protection for
generators.
Correct settings of blinder-2 & RRR are very difficult to set,
again its require high skilled expert to do grid analysis &
effect on machines.

Knowledge Is Power

SM

Apparatus Maintenance and Power Management


for Energy Delivery

Blinder Schemes: Single Blinder


DR/DT scheme:
How to set timer?
T = {(Critical load angle Rotor angle)*Fn}/{(360)*(slip frequency)}
Where;
Critical load angle = 150 degree
Rotor angle = 90 degree
Fn = 50Hz
slip freq. = 4Hz
T = {(150 90)*(50)} / {(360)*(4)}
= 2.0833 Cycles
T = 2.0833 * 20 = 41.66ms
Knowledge Is Power

SM

Apparatus Maintenance and Power Management


for Energy Delivery

Blinder Schemes: Single Blinder


Single Blinder

Relay Type: ZTO 11

OST-REGION
Un stable swing
Stable swing
RRR

Blinder-2

Blinder-1

RRR = Reverse Resistive Reach in Ohms


OST = Out of Step trip

Knowledge Is Power

SM

Apparatus Maintenance and Power Management


for Energy Delivery

Figure:-17

Blinder Schemes: Single Blinder


Single Blinder

Rset is not adjustable in forward


direction

Un stable swing
Stable swing

Blinder-2

MHO supervising unit

Blinder-1

Mho supervising unit will restrict mal-operation of relay


Knowledge Is Power

SM

Apparatus Maintenance and Power Management


for Energy Delivery

Figure:-18

Blinder Schemes: Single Blinder


CEB + CEH Relays
Swing Locus

Blinder 1
XT+XS
Line Angle

Load Angle = 90o or 120o

Xd

MHO supervising control

Swing Centre = {Xd + (XT + XS)} / 2


Knowledge Is Power

SM

Apparatus Maintenance and Power Management


for Energy Delivery

Figure:-19

Blinder Schemes: Double Blinder


Blinder schemes:
Double Blinder (Two Pair) scheme (Figure:-20):
Two sets of blinders: Resistive reach inner (RRI) & Resistive
reach outer (RRO)
Time Counter starts when the impedance vector crosses outer
limit (RRO) & stops when it crosses inner limit (RRI)
If travel time is more than set time, power swing situation is
detected
Scheme is applicable for independent of the distance zones
Correct setting for Blinders are very difficult & it requires
good expert who can able to do power grid analysis.

Knowledge Is Power

SM

Apparatus Maintenance and Power Management


for Energy Delivery

Blinder Schemes: Double Blinder


Double Blinders

Blinder-2 Blinder-1

Blinder-1

Blinder-2

Knowledge Is Power

SM

Apparatus Maintenance and Power Management


for Energy Delivery

Figure:-20

Testing methods with F6150:


Asynchronous method by using Doble
advance transient creator

Dz/Dt simulation by using State simulation


module

Knowledge Is Power

SM

Apparatus Maintenance and Power Management


for Energy Delivery

Power Swing Testing: Asynchronous method


Asynchronous method by using doble advance
transient creator
Two machines

Knowledge Is Power

SM

Apparatus Maintenance and Power Management


for Energy Delivery

Power Swing Testing: Asynchronous method

Select Swing

Knowledge Is Power

SM

Apparatus Maintenance and Power Management


for Energy Delivery

Power Swing Testing: Asynchronous method


Slip freq. = 2Hz

Source-1 parameters

Line parameters

Knowledge Is Power

SM

Apparatus Maintenance and Power Management


for Energy Delivery

Source-2 parameters

Power Swing Testing: Asynchronous method

Save datc file


Knowledge Is Power

SM

Apparatus Maintenance and Power Management


for Energy Delivery

Asynchronous method: Power swing Waveform

Knowledge Is Power

SM

Apparatus Maintenance and Power Management


for Energy Delivery

Power Swing Testing: Asynchronous method

Save comtrade file for test

Knowledge Is Power

SM

Apparatus Maintenance and Power Management


for Energy Delivery

Power Swing Testing: Dz/Dt Method


Dz/Dt simulation by using State simulation
module
Total 25 nos. of states
Each state having independent magnitude,
phase angle & frequency controlled
Individual time setting for each state
Each state having option to enter individual
value for L/R constant
Phasor diagram for each state to show
voltage & current vectors
Knowledge Is Power

SM

Apparatus Maintenance and Power Management


for Energy Delivery

Power Swing Blocking Testing: REL100


Figure: 11 shows relay characteristic
Module Type: State Simulation
Test Sequence:
Load condition: State 1
Apply 3-phase Fault in PSB locus(Z1): State 2
Apply 3-phase Fault in Zone 3: State 3
Travelling time between State 2 & State 3
should be more than time out setting of relay
(Say: 70 ms if relay setting = 50ms)
Remove fault: State 4

Knowledge Is Power

SM

Apparatus Maintenance and Power Management


for Energy Delivery

State Simulation

Z1

Z2

Travel Time

Z3

Phasor

State: 2

State: 3

State: 4
Knowledge Is Power

SM

Apparatus Maintenance and Power Management


for Energy Delivery

Excel Spread sheet Control:


Micro Soft Excel Spread sheet for Custom
Application
Easy to use
State Simulation up to 20 states
Easy to simulate any Power System Events
More flexibility to calculate numerical functions
Interface with F6150 via serial communication
Engineers choice
Knowledge Is Power

SM

Apparatus Maintenance and Power Management


for Energy Delivery

REL100: PSB Testing


REL100:
Relay settings:
ZONE-3:
Rin = 7.97 Ohms, Xin = 43.97 Ohms
PSB settings (Polygon char.):
Rout = 7.97*1.2 = 9.56 Ohms
Xout = 43.97*1.2 = 52.76 Ohms
Knowledge Is Power

SM

Apparatus Maintenance and Power Management


for Energy Delivery

Power Swing Testing: REL100

PSB settings

Knowledge Is Power

SM

Apparatus Maintenance and Power Management


for Energy Delivery

Power Swing Testing: REL100


State: 1/2/3/4/5

Knowledge Is Power

SM

Apparatus Maintenance and Power Management


for Energy Delivery

Power Swing Testing: REL100

PSB Polygon

Plot Dz/Dt locus

Knowledge Is Power

SM

Apparatus Maintenance and Power Management


for Energy Delivery

Power Swing Testing: REL100

Assign Trigger

Auxiliary DC

Run Test
Select Com Port

Knowledge Is Power

SM

Apparatus Maintenance and Power Management


for Energy Delivery

REL521: PSB Testing


Dz/Dt simulation by using State simulation

module
REL521:
PSB settings:
Inner zone settings (Polygon char.):
RIN = 3.0 Ohms, XIN = 3.0 Ohms
Outer zone settings:
KR = 125%, KX = 125%
RIN = 3*1.25 = 3.75 Ohms
XIN = 3.*1.25 = 3.75 Ohms
Knowledge Is Power

SM

Apparatus Maintenance and Power Management


for Energy Delivery

REL521: PSB Testing

PSB settings

Knowledge Is Power

SM

Apparatus Maintenance and Power Management


for Energy Delivery

Enter values in states

Enter travel time in states

Knowledge Is Power

SM

Apparatus Maintenance and Power Management


for Energy Delivery

REL521: PSB Testing

Zin

Dz/Dt locus
Zout

Knowledge Is Power

SM

Apparatus Maintenance and Power Management


for Energy Delivery

Pole Slip Relay Testing with F6150 &


Excel Spread sheet control

Knowledge Is Power

SM

Apparatus Maintenance and Power Management


for Energy Delivery

Basic definitions: Pole Slip


Pole Slip: A condition whereby a generator, or group of
generators, terminal voltage angles (or phases) go past
180 degrees with respect to the rest of the connected
power system.
High level Transient torque develop in machine shaft
can break the shaft
High Stator Iron flux can over heat generator stator core
Protection is also known as a out of step Protection of
machine
Protection is applicable for synchronous machines
Knowledge Is Power

SM

Apparatus Maintenance and Power Management


for Energy Delivery

Basic definitions: Pole Slip


Theta = Line Angle

XT + Xs = 18%

G
Xd

Rotor Angle

Theta
90o
90o

Electrical Centre

Xd = 25%

Knowledge Is Power

SM

Apparatus Maintenance and Power Management


for Energy Delivery

Xs
XT

Relay Details:
MAKE : GEC ALSTHOM
MODEL : ZTO 11

Relay Settings:

K1 = 1
K2 = 1
K3 = 8
R = K1*K2*k3 = 8 Ohms
Blinder 1 = 65 Degree
Blinder 2 = 65 Degree
Time = 55ms
Knowledge Is Power

SM

Apparatus Maintenance and Power Management


for Energy Delivery

Relay Characteristic: Blinder Scheme

-R

Ope
rati
ng

Reg
ion

ZTO 11

65o

A
Blin
der
1

Blin
der
2

Power swing Locus

65o

Traveling Time (Dt) should


be more than 55 ms from
one point to next point

-X

Knowledge Is Power

SM

Apparatus Maintenance and Power Management


for Energy Delivery

Relay Characteristic: Blinder Scheme

65o

-R

A
Blin
der
1

Optional Scheme:
ZTO 11 + YTGM15

Blin
der
2

Power swing Locus

65o

Traveling Time (Dt) should


be more than 55 ms from
one point to next point

-X

Mho Characteristic to reduce the mal operation of relay


Knowledge Is Power

SM

Apparatus Maintenance and Power Management


for Energy Delivery

Pole Slip Protection: ZTO11


Four Elements
Over current starter
Blinder 1 Unit (A-Unit)
Timer Unit (T-Unit)
Blinder 2 Unit (B-Unit)
Alarm: Operation of A & T units with O/C starter
Fault condition: Operation of A & B units with O/C
starter
Pole Slip condition: Operation of A, T & B units in
sequence with O/C starter
Knowledge Is Power

SM

Apparatus Maintenance and Power Management


for Energy Delivery

ZTO11: Stable Swing

Swing
Locus

Enter Time out


Time more than
Set value

Knowledge Is Power

SM

Apparatus Maintenance and Power Management


for Energy Delivery

ZTO11: Pole Slip Condition

VTest & ITest values set for Test

Swing
Locus

Enter Time out


Time more than
Set value

Knowledge Is Power

SM

Apparatus Maintenance and Power Management


for Energy Delivery

ZTO11: Fault Condition

VTest & ITest values set for Test

Swing
Locus

Enter Time out


Time less than
set value

Knowledge Is Power

SM

Apparatus Maintenance and Power Management


for Energy Delivery

ZTO11: Reverse Resistive Reach Test

Swing
Locus

Enter Time out


Time less than
set value

Knowledge Is Power

SM

Apparatus Maintenance and Power Management


for Energy Delivery

DOBLE ENGINEERING PVT. LTD


305-SAKAR, OLD PADRA ROAD,
VADODARA-390 015, INDIA.
Cell: +91 94267 47545
PH: (+91)(265) 655 77 15 & Fax: (+91)(265) 235 62 85
E-MAIL: kdave@doble.com
Website: www.doble.com

Knowledge Is Power

SM

Apparatus Maintenance and Power Management


for Energy Delivery