400-220 KV Substation Presentation
400-220 KV Substation Presentation
Sub-station
S.M. MUJUMDAR
General Manager
(sub-station Engineering)
Jyoti Structures Ltd.,
Agenda
Design Process
Design considerations
Question / Answer
System parameters
Sr.
Description
400kV
220kV
1.
400kV
220kV
2.
420kV
245kV
3.
Rated frequency
50Hz
50Hz
4.
Number of phases
5.
Effectively earthed
6.
320kV
156kV
7.
25mm/kV
25mm/kV
8.
40kA
40kA
1000 mV
(320kV)
1000 mV
(156kV)
Description
400kV
220kV
11.
1550kVp
1300kVp
1425kVp
1050kVp
950kVp
1050kVp
Remarks
1050kVp
680kV
520kV
610kV
630kV
460kV
460kV
530kV
460kV
(Line-ground)
(open terminals)
400kV Isolator
400kV CVT
Wave Trap
Function
1. Bus-Bar
2. Circuit Breaker
3. Isolators
4. Earthing switch
5. Current Transformer
6. Voltage Transformer
7. Lightning Arrester
9. Neutral-Grounding
resistor
Function
Contd..
4. Protection system
-- protection relay panels
-- control cables
-- circuit breakers
-- CTs, VTs etc.
5. Control cable
6. Power cable
Contd
8. Fire Fighting system
-- Sensors, detection system
-- water spray system
-- fire prot. panels, alarm system
-- watertank and spray system
Supporting drawings
Structural layout
Earthmat layout
Civil layout
Lighting Layout
Electrical layout
Electrical Section
Structural layout
Earthmat Layout
@
@
@
@
@
Civil layout
EW1
4I1
4C2
4C1
4W1
4I2
4I2
4I2
4I1
4I1
4C2
4C2
4C1
4W1
4W1
4C1
4B
4B
4B
4B
4B
4I1
4I2
4B
4I1
4I1
4I
4I2
4P1
4W1
4IC2
4P1
4P1
4I1
4I1
4I2
4I2
4C2
4C2
4I2
4C1
4C1
4I1
4W1
4W1
4C2
4B
4C1
4W1
4B
4B
4B
4B
4I1
4I1
4B
4I1
4DTQB-2
4I2
4DTTM-1
4I2
4W1
4IC2
4P1
4I
4DTTM-1
4DTQB-2
EW2
4W1
4IC1
4IC1
4I
4I
4DTTM-1
4I
4I
4DTTM-2
4DTQB-1
4DTTM-1
4I
4I
4DTTM-2
4DTTM-1
4DTTM-1
4I
4I
4I
4DTTM-2
4P3
R2
4P3
N1
4DTTM-1
4P3
4DTTM-2
4DTTM-1
4DTQB-1
4I
4I
4I
4P3
4DTTM-2
4DTTM-1
4DTTM-1
4W1
4P3
4DTQB-1
4DTTM-2
4P3
R2
4DTTM-1
R1 R1 R1
N1
4DTTM-1
R1 R1 R1
4I
4I
4I
4I
4I
4I
4SSTM-D4SSTM-D4SSTM-D
4I
4I
4W
4W
4I
4I
4SSTM-D4SSTM-D4SSTM-D
4I
4W
4W
4I
4V
4V
4V
4V
4V
4V
4P
4LA
4P
4LA
4P
4LA
4P
4LA
4P
4LA
4P
4LA
4DTQB-2
EW1
EW2
EW2
EW1
EW2
EW2
EW2
4SSTM-D
4DTTM-1
4T1
4T1
4S1
4S2
4S2
4DTTM-2
4TM
4S2
4T1
4S1
4S1
4S1
4S1
4S1
4S1
4S1
4P
4S1
4V
4W
4W
4I
4I
4S2
4DTTM-1
4S2
4S2
4S2
4TBSM
4S1
R1
4LA
4S1
4P 3
4S1
4I
4S1
4I
4S1
4DTTM-2
4S1
4SSTM-D
4S1
4S1
4LA
4S2
4TBSM
4S1
4P 1 4P 1
4IC1 4IC2
4S1
4TBSM
4S1
4S1
4I2
4I
4I1
4B
4B
4I2
4IC2
Lighting Design
Demerits
Remarks
1. Low cost
1. Used for
distribution
substations upto 33kV
2. Simple to Operate
2. Difficult to do any
maintenance
3. Simple Protection
3. Sectionalizing
increases flexibility
Demerits
Remarks
2. Switching is
somewhat complex
when maintaining a
breaker
Demerits
1. Extra bus-coupler circuit
breaker necessary.
Remarks
1. Most widely
used for 66kV,
132kv, 220kV and
important 11kv,
6.6kV, 3.3kV
substations.
Demerits
Remarks
1. Most expensive
2. Has flexibility in
permitting feeder
circuits to be connected
to any bus
Demerits
Remarks
1. Preferred by
some utilities for
400kV and
220kV
important
substations.
Demerits
Remarks
1. Used for 400kV
& 220kV
substations.
2. Protection and
2. Preferred.
auto-reclosing more
complex since
middle breaker must
be responsive to
both associated
circuits.
Ring Bus
Demerits
1. If fault occurs during bus
maintenance, ring gets separated
into two sections.
2.Auto-reclosing and protection
complex.
3. Requires VTs on all circuits
because there is no definite voltage
reference point.
These VTs may be required in all
cases for synchronizing live line or
voltage indication
4. Breaker failure during fault on one
circuit causes loss of additional
circuit because of breaker failure.
Remarks
1. Most widely
used for very
large power
stations having
large no. of
incoming and
outgoing lines
and high power
transfer.
Minimum Clearances
400kV
220kV
1. Phase to Earth
3500 mm
2100 mm
2. Phase to phase
4200 mm
(Rod-conductor configuration)
4000 mm
(Conductor-conductor configuration)
2100 mm
3. Sectional clearance
6400 mm
4300 mm
Clearance Diagram
Deflection of Tube
Aeolian Vibrations
Temp
Wind Pressure
Limits
1.
Min.
No wind
2.
Min.
36%
3.
Every Day
No wind
4.
Every Day
100%
5.
Max.
(ACSR 750C/ AAAC 850C)
No wind
Clearances
Contd..
Factor of safety of 2.0 under normal condition and 1.5 under short
circuit condition
spacers
12000.00
10000.00
8000.00
6000.00
4000.00
2000.00
0.00
0
10
12
14
Earthing Design
Guiding standards IEEE 80, IS:3043, CBIP-223.
400kV & 220kV system are designed for 40kA.
Basic Objectives:
Step potential
within tolerable
Touch Potential
limit
Ground Resistance
Adequacy of Ground conductor for fault current
(considering corrosion)
FIG-4a
FIG-4b