Inspection Report Bifab Ut On Duplex Stainless Steel Piping
Inspection Report Bifab Ut On Duplex Stainless Steel Piping
for
Ultrasonic Testing on Duplex Stainless Steel Piping Material
Welding Procedure Qualification
Ultrasonic testing has been performed using angled compression wave technique and results are as follows:
Reference Block : Reference block from 10 x 21.3 WT , 8 x 18.3 WT, 6 x 14.3 WT Duplex Stainless Steel pipe
Material Type
: UNS S31803
Project
: Skarv SPC - EPC & Associated Service
Date of Inspection : 28.07.08 - 30.07.08
Location
: Burntisland Fabrication Ltd
UT Technique
: Angled Compression Wave
1. Reference Block
10 Dia x 21.3 WT
Dia. 3mm Side drilled hole (SDH) at Heat Affected Zone (HAZ)
8 Dia x 18.3 WT
Dia. 3mm Side drilled hole (SDH) at Heat Affected Zone (HAZ)
6 Dia. x 14.3 WT
Dia. 3mm Side drilled hole (SDH) at Heat Affected Zone (HAZ)
Creep Wave
Reference Block
2.Calibration Block
Based on back
surface echo
by SHEAR
WAVE
Beam path
Based on side drilled hole by
COMPRESSION WAVE
T
T
T
Expected First
back wall echo
from SHEAR
WAVE
23.1
22.6
15.1
7.5
42.14
22.6
15.1
7.5
24.2
32.0
21.3
10.6
44.0
32.0
21.3
10.6
24.8
46.7
31.0
15.5
46.7
31.0
15.5
45.0
(Note -1)
(Note -1)
Note -1: Both the echo from Shear and compression wave will be close together, but all other cases shear and compression wave will be separated in
the time base scale in the CRT screen
Transducer
TAC 45
4MHz
TAC 60
4MHz
TAC 70
4MHz
Based on back
surface echo
by SHEAR
WAVE
8 x 18.3 WT
Beam path
Based on side drilled hole by
COMPRESSION WAVE
T
T
T
Reference Block
Expected First
back wall echo
from SHEAR
WAVE
19.9
19.4
13.0
6.5
36.3
19.4
13.0
6.5
20.8
27.4
18.4
9.2
37.95
27.4
18.4
9.2
21.3
40.0
26.9
13.4
40.0
26.9
13.4
38.8
(Note -1)
(Note -1)
Note -1: Both the echo from Shear and compression wave will be close together, but all other cases shear and compression wave will be separated in
the time base scale in the CRT screen
DAC curve was not able to optimize the echo response from side drill hole of 6x 14.3mmWT reference block due to the following reason,
The available transducers shoes are shaped to suit diameter 8, so separate set of transducer need to be arrange for 6 diameter.
Even we have tried with this transducer to develop DAC for 6x 14.3mmWT reference block, and we have got reasonable response, but still
need to be optimize the echo response with suitable shoe shape to suit 6 diameter.
6 x 14.3 WT Reference Block
Transducer
TAC 45
4MHz
TAC 60
4MHz
TAC 70
4MHz
Based on back
surface echo
by SHEAR
WAVE
Beam path
Based on side drilled hole by
COMPRESSION WAVE
T
T
T
Expected First
back wall echo
from SHEAR
WAVE
15.5
15.1
10.2
5.1
28.3
15.1
10.2
5.1
16.2
21.4
14.4
7.2
29.6
21.4
14.4
7.2
16.7
31.3
21.1
10.5
21.1
10.5
31.3
(Note -1)
Note -1: Both the echo from Shear and compression wave will be close together, but all other cases shear and compression wave will be separated in
the time base scale in the CRT screen
Experienced person
Qualification
Experienced person
Qualification
Mr. Alexander
Pattie
Experienced person
Qualification
Experienced person
Qualification
6. Status of Procedure Qualification (PQR) of 10 dia of 625 clad ASTM A350 LF2 to
Duplex ( Procedure no. WPS 04)
Welding was completed on 29.07.08, and visually inspected and found satisfactory.
BiFab planning to perform NDT ( RT & PT) on 30.07.08.
Once NDT result s are satisfied, test coupon will be sent Bodycote for mechanical test.
PQR was performed very professional way by BiFab.
Prepared By : R.Baskar,
ASNT NDT Level 3 RT,UT,PT,MT
CSWIP 3.2
AWS - SCWI
Date
: 30.07.08