Chap.10 LSIS INV (MODBUS) PDF
Chap.10 LSIS INV (MODBUS) PDF
Kinds of machines
SV-iG
SV-iS3
SV-iV
SV-iH
SV-iS5
SV-iG5
SV-iV5
SV-iC5
SV-iP5A
SV-iG5A
Communication type
RS-485
Protocol
MODBUSRTU
Remarks
External communication type option
External communication type option
External communication type option
External communication type option
External communication type option
Embedded communication
External communication type option
External communication type option
Embedded communication
Embedded communication
Notice
(1) The maximum number of connected devices is 31EA.
(2) The total length of communication line is extended to 1,200[m], however for stable communication, it should be
within 500[m].
(3) An inverter has different communication setting and wiring depending on the kinds of machines so refer to the
inverter manual for installation.
10-1
XGT Panel
Shield
Inverter
XGT Panel
10-2
Shield
Communication option
Notice
(1) Suggestions
The array of connector and pin may be different depending on the inverter type. (Embedded communication type, external
communication type)
Check the end switch of XGT Panel. It is basically set as terminator type.
The above wiring diagram is for 1:1 connection and for 1:N connection, refer to the Chap.2.
(In the case of 1:N mode, connect a terminate resistor to the last inverter.)
A shielded wire is recommended for stable communication. For shield wiring, refer to the Chap.2.
If noise generated from an inverter or the motor connected to an inverter flows into the cable, communication may be
interrupted intermittently. In this case, connect one side to FG or remove FG to normalize communication.
4-way switch
To set the communication parameter of an inverter, select each function code with 4-way switch and apply the communication setting for
your own working circumstances.
For inverter communication of iG5A, if you set operation command type 3(communication operation), frequency setting method
7(communication operation), it will be communication operation mode. The below is detailed setting items.
(a) Set communication protocol as MODBUS RTU.
Code
I59
Function
Setting
communication protocol
Setting range
0~1
0
1
Description
Setting communication protocol
MODBUS RTU
LS BUS
10-3
Function
Inverter No.
Setting range
Description
1~32
Function
Communication
speed
Setting range
0~4
Description
XGT Panel does not provide the speed of less
tan 9,600[bps] (0~2)
3
9,600[bps]
4
19,200[bps]
I65
Function
Parity/Stop bit
Setting range
0~3
Description
Setting communication transmission format.
0
Parity : None, Stop Bit : 1
1
Parity : None, Stop Bit : 2
2
Parity : Even, Stop Bit : 1
3
Parity : Odd, Stop Bit : 1
Notice
(1) Suggestions s
When connecting several inverters, make sure to avoid overlapped No.
XGT Panel allows communication transmission speed of 9,600, 19,200, 38,400, 57,600, 115,200 so the speed of less than
9,600 is not available.
You can set the communication parameter of XGT Panel at XP-Builder(Refer to XP-Builder manual). XP-Builder provides basically
communication parameters as below.
10-4
Notice
(1) Suggestions to set inverter
For installation, make sure to refer to LS Industrial Systems inverter manual.
Especially, mind that setting methods are different depending on the kinds of machines.
(2) Suggestions to set XP-Builder
When creating project or setting communication, refer to the below.
When making RS-485 as 1:N, set transmission waiting time flexibly depending on communication composition.
(Recommended : 50~100ms)
10-5
Address
Parameter
Remarks
Common Area
0000 - 04FF
0500 - 09FF
1000 - 1FFF
2000 - 2FFF
3000 - 3FFF
4000 - 4FFF
5000 - 5FFF
6000 - 6FFF
7000 - 7FFF
8000 - 8FFF
9000 - 9FFF
A000 - AFFF
SV-IS5 parameter
SV-IG5 parameter
SV-IV5 parameter
SV-IC5 parameter
SV-IP5A parameter
SV-IG5A parameter
(1) LS SV-IG5A
Classification
DRV
FU1
FU2
I/O
Address area
A100 - A1FF
A200 A2FF
A300 A3FF
A400 - A4FF
Remarks
Displaying Hexadecimal number
Displaying Hexadecimal number
Displaying Hexadecimal number
Displaying Hexadecimal number
(2) LS SV-IP5
Classification
MAK
DRV
FU1
FU2
I/O
EXT
COM
APP
10-6
Address area
9000 - 90FF
9100 - 91FF
9200 - 92FF
9300 - 93FF
9400 - 94FF
9500 - 95FF
9600 - 96FF
9700 - 97FF
Remarks
Displaying Hexadecimal number
Displaying Hexadecimal number
Displaying Hexadecimal number
Displaying Hexadecimal number
Displaying Hexadecimal number
Displaying Hexadecimal number
Displaying Hexadecimal number
Displaying Hexadecimal number
(3) LS SV-IV5
Classification
MAK
DIS
I/O
PAR
FUN
CON
EXT
USR
2nd
E/L
Address area
7000 - 70FF
7100 - 71FF
7200 - 72FF
7300 - 73FF
7400 - 74FF
7500 - 75FF
7600 - 76FF
7700 - 77FF
7800 - 78FF
7900 - 79FF
Remarks
Displaying Hexadecimal number
Displaying Hexadecimal number
Displaying Hexadecimal number
Displaying Hexadecimal number
Displaying Hexadecimal number
Displaying Hexadecimal number
Displaying Hexadecimal number
Displaying Hexadecimal number
Displaying Hexadecimal number
Displaying Hexadecimal number
Notice
(1) Suggestions
For the method to use device with details, refer to inverter manual.
Use it within device area.
Device range may be different depending on an inverter so refer to each inverter manual.
10-7