Professional Documents
Culture Documents
Dew Point
Dew Point
xls
Calculations for Recommended Flue Gas temperature to avoid S-dew point corrosion.
INPUTS
SO2 in flue gas ppm v/v
FD Fan outlet air temperture
Flue gas pressure-Air preheater outlet
H2O in flue gas
CALCULATION(Please do not change the formulae)
SO2 in flue gas vol %
H2O in flue gas vol %
Flue gas pressure
80
30
15
25
ppm v/v
deg.c.
mm WC
% vol
0.008
25
15
mm WC
0.59055118 inch WG
1.0015 ata
tw=tg-(tg-ti)xhi/(hi+ho)
tw=average tube wall temperature
tg,ti= flue gas and air inlet temperatures
hi,ho= tube side and gas side heat transfer coefficients
In an air preheater ,hi and ho=10 & 15 Btu/ft2hF respectively.
PH20
Ln(PH2O)
SO2 to SO3
PSO3
Ln(PSO3)
1000/Tdp
Tdp
2.4908847285
401.46378055
128.46378055
tw recomm.
128.46378055
hi/(hi+ho) =
0.4
tI =
tw=
tg =
RESULTS
S-Dew Point Temperature
Recommended Flue gas Temp
128.46378 Deg.c.
194.1063 Deg.c.
PAGE 1
190.551775
5.24992394
2%
0.00097421
-6.9338821
30
128.46378055
194.10630091
280168239.xls
Issued by
Technical Services
TCL Mithapur
18/04/2003
PAGE 2
280168239.xls
mm Hg
wt. basis
mm Hg
deg K
Deg C
PAGE 3
280168239.xls
PAGE 4