Professional Documents
Culture Documents
372 Power Applications
372 Power Applications
Applications
by
Curtis Sterud
w2
LP Superheater Stop
205C
LP Throttle Control
207
Secondary Bypass
210
Turbine Bypass
218
219
220
221
230
231
240
241
401
w3
BOILING WATER
REACTOR
w4
Drum Boilers
Drum boilers vary in size, from small boilers used to generate steam
industrial heating up to the large public utility boilers which produce
enough steam to generate up to 900 MW of power, such as the Lake
Cayuga Plant of New York Electric and Gas.
Large utility drum boilers have more severe service applications which
require DRAG valve technology. These boilers also require turbine
bypass valves.
Shown on the following pages are the typical schematics and diagrams of areas
which require a DRAG valve. These applications see either the potential for
cavitation, flashing, or a combination of high-pressure drop and low flow rate.
There are four areas that we will discuss:
I.
CONDENSATE SYSTEM
a)
b)
b)
501
ii.
502
iii. 518
iv. 519
b)
c)
d)
e)
f)
b)
w5
Heater Drains
Auxiliary Steam
SamplingVarious Locations
w6
I.
Condensate System
This is the portion of the plant where condensate is taken from the
condenser hotwell, circulated through the low pressure heaters, and to the
deaereator.
The condenser acts as a heat exchanger that serves the purpose of creating
a vacuum which increases the efficiency of the turbine and for recovery of
quality feedwater (condensate).
Shown below is a schematic of a typical condensate system:
w7
a)
The condensate pump must have a minimum amount of flow through it at all
times to prevent it from overheating and to protect it from cavitation. Therefore,
a recirculation valve and line runs from the pump outlet line back to the
condenser. When the boiler load is low the flow of condensate required is less
than the pump minimum flow requirement. The recirc. valve is used to allow
the additional flow required through the pump. The pump outlet pressure varies
from 300 psi to 600 psi with fluid temperature from 100 to 150F.
The recirc. line dumps into the condenser which is at vacuum. If a
conventional valve were used here, there would be severe cavitation. (The
outlet pressure at the valve is higher than condenser vacuum because of pipe
friction, elevation and sparger back pressure.
An 800D is the valve for this service. This valve must have positive shutoff.
To assure good shutoff, the valve must have a soft seat.
b)
High rangeability
Tight shut-off is not essential because this valve is open at all times the
plant is up and running.
w8
II.
Feedwater System
This is the portion of the plant where feedwater is taken from the deaereator by the boiler feedpumps and sent through the
high pressure heaters, the economizer, and finally into the boiler. The fluid is brought to full outlet pressure of the boiler
and its temperature raised by heat recovery for efficiency of the system.
a)
b)
The boiler pumps may be motor driven, which are generally constant speed and therefore constant outlet pressure, or
steam driven with variable output. (A fluid coupling on a constant speed motor driven pump can be utilized to get
variable output.)
In any case, a control valve for feedwater regulation to the boiler takes the fluid from the pump outlet and regulates the outlet
flow rate to the boiler demand.
The service of this valve is similar to the DEA level control valve, except at a significantly higher pressure.
The fluid is taken from the DEA into the boiler feedpump and the pressure is raised to boiler operating pressure (most cases
are over 3,000 psi). This is the inlet pressure to the feedwater regulator. At start-up and low loads, the pumping load is small
and the pump outlet pressure is high and the drum pressure is not built up yet. In this case, there is a need for cavitation
prevention and the flow capacity is very low. As the plant load increases, drum pressure increases and flow rate increases.
The pump cannot maintain the same pressure head at these higher flows. The result is lower inlet pressure to the valve and
high back pressure on the valve. These higher flows with lower pressure drops create a need for high capacity of the valve
with less resistance in the trim. Many plants utilize a start-up valve and a main valve for this service. The start-up valve
would have trim to cope with the low flow and cavitation condition, and the main valve take over the flow increased
and differential pressure decreased. The CCI DRAG valve can be built with characterized trim to cover the full range of
operation conditions in one valve.
Requirements of this valve:
n
High rangeability
w9
Feedwater Regulation
Bailey D10 and DRAG
w 10
w 11
w 12
In a power plant, the boiler water is circulated in a closed loop by a feedpump driven either by electric motor or steam
turbine. The pump takes the water from the deaereator or high pressure heaters and boosts the pressure to the system
requirements (38005500 PSI in a supercritical universal pressure boiler). These pumps require a certain minimum
amount of flow to avoid overheating and cavitation problems. In order to protect the pump when the boiler feed flow
requirement is less than the minimum permissible flow through the feedpump, a recirculation system is used to return a
portion of the high pressure flow back to the condenser (or sometimes to the deaereator) and thence to the pump. (see
diagram for a system schematic.)
Ideally, the recirculation system would meter the flow in response to the pumps requirements. This indicates the need for a
modulating control valve which normally would be closed, but if power to the valves actuator should fail, the valve would
need to open. Also, if the system is off, the valve is fully open. When the pump is turned on, the valve is flowing 100%
and closes as system flow increases. The valve would need to handle water with thermodynamic conditions at the inlet of
38005000 PSIG to 10 PSIG. Thus, during modulation of full flow conditions, the valve must handle high pressure drop
and substantial flashing, yet manage to minimize erosion, cavitation and noise problems.
While minimum flow protection would normally be required only during station startup and shutdowns, in actual practice,
such systems might be used for extended periods of peak power or in the case of nuclear plants, forced operation at reduced
percent power to qualify operating permits. It is apparent that minimum flow systems must be capable of continuous
operationtheir purpose is to protect $100,000-plus feedpumps from severe damage. Since spare feedpump capacity is
not generally used, damage to a feedpump can have serious consequences in terms of restricting full power capability for
extended periods of time. Each feedpump is always installed with an individual recirc. system.
When shut, the pressure could build up to as high as 5500 PSIG and the valve can be expected to hold drop-tight against
leakage. Should the valve leak, even the tiniest amount of flashing seat and water mixture would cut the seating surface like
a rough wire and in a short while, the shutoff function of the valve would be lost. (See diagram). Excessive leakage cuts into
the efficiency of the plant, both through direct energy loss and because the boiler cannot be fed the full rated flow. In the
extreme case, a shutdown of an entire power plant may be necessitated because of a single leaking valve.
Thus, the statement of the problem is this: there is a need for a boiler feedwater pump recirculation valve (BFPRV) that
will:
1)
Break down water pressure from ~ 4000 PSI to atmospheric or vacuum pressure:
n
Without cavitation
2)
3)
Modulate automatically and open in case of failure of power to the valve operator.
This application is probably the most severe application of a control valve in the power plant.
w 13
w 14
Stacked disks must be oriented so that the radial flows from their
exhaust ports are not lined up vertically, but alternated. The resulting
annular flow around the plug interrupts the downward annular flow.
A continuous weir around the inner edge of each disc ensures
homogeneous flow from the stack and serves to control total velocity.
Flow from discs below the bottom of the plug interrupts the downward
annular flow and deflects it away from the seating surface (3rd figure).
Seat designs and materials have varied widely over the years. Sterud
considers that most of them have been inadequate and favors a design
that uses a relatively soft 300-series stainless steel seat and a hardened
400-series stainless steel plug. A 3 difference between the machined faces
of the valves conical seat and plug (last figure) produces a line contact
between plug and seat.
This seat design is used with a closing force of about 1000 lb./linear inch of
seat/plug mating. This far exceeds the yield strength of the softer seat material
and is almost 50% higher than the seat load used in most recirculation-valve
designs.
To eliminate the possibility of uneven downward flow around the plug
during very low-flow operation, the actuator is provided with snap-action
relay that closes the valve completely below about 10% of rated flow.
w 15
III.
The main steam system covers the portion of the plant that takes the steam from the boiler, sends it through the
superheaters, and into the high-pressure turbine. The steam exiting the high-pressure turbine is sent through a reheater,
then fed into the low-pressure turbine. Finally, after all potential energy is extracted from the steam, it is dumped into the
condenser to start the whole process over again.
Large generating units were designed generally for base-loaded operation. However, with increased emphasis on planned
cycling operation of fossil-fired boilers, there are new demands on the control of boilers during start-up and low load
operation.
Conventional drum boilers can be operated with wide variation in load, including complete shutdown and re-start, without
sacrificing heat rate or cyclic life. Modes of operation include variable drum pressure, constant throttle pressure and dual
pressure.
With variable drum pressure, the turbine throttle valves are nearly wide open and the throttle pressure varies with drum
pressure. This operation is relatively slow in response to load demand.
With constant drum pressure, the turbine throttle valves are nearly wide open and the throttle pressure varies with drum
pressure. This operation is relatively slow in response to load demand.
With constant drum pressure, the turbine load is changed by modulating the turbine throttle valves. The low load
efficiency is achieved by sequenced turbine control valves and partial ARC throttling at the expense of a large change in
impulse chamber temperature.
Dual pressure operation involves wide variable throttle pressure, with the pressure controlled by wide range superheater
division valves. The drum pressure is controlled at a high pressure above 2000 psi. For this type of control, there is little
change in turbine metal temperatures, or in drum saturation temperature over the load range. Load response will be at least
comparable to that for constant throttle pressure operation.
The dual pressure mode of operation is a system incorporated in some B& W drum boilers. B&W incorporated CCI
DRAG valves in five locations of this system. These valves are:
n BW100FeedwaterRegulator
n BW501SecondarySuperheaterStop
& Bypass Valve
n BW502PrimarySuperheaterBypass
Valve
n BW518MainSteamAttemperator
n BW519ReheatOutletSteam
Attemperator
n BW510TurbineBypass
The superheater division valves (BW500
and BW501) are used below about 70%
load to maintain drum pressure, yet
provide reduced throttle pressure to the
turbine. The BW502 valve permits firing
proportional to steam flow during an
unloaded transient, and limited overfiring at low load. The 502 from
the drum with the steam exiting the
superheater and reheater to hold
temperature at the turbine without the
concern for water into the turbine, which
might result from water attemporation.
The BW100 feedwater regulator is a high
rangeability valve for this service.
w 16
The 500 and 501 valves have been closed to bottle up the boiler
overnight. The boiler pressure will have decayed somewhat, so initial
firing will be to bring drum pressure and temperature up. The 502 valve
is used to bypass the steam to the condenser. When steam temperature
is established, the 501 valve is opened to admit steam through the
superheater and initially through the 510 valve to the condenser. This
if for warming flow. The 510 valve is closed, and turbine throttle valves
are opened to 70%. The turbine is rolled (turbine throttle pressurized at
about 200 to 300 psi. The 501 valve opens to increase the turbine throttle
pressure which is turbine load. With the low flows involved, the steam
attemporation at superheater outlet (518 valve) and reheater outlet (519
valve) controls the turbine temperature without the danger of water into
the turbine at less than 15% load. As load goes above 70%, the BW500
valve is opened to 100% open and the turbine throttle valves control load
of the turbine from there to full load.
It should be obvious that the five valves we provide for this system are
crucial to the successful operation of the system.
The 502 valve starts with low temperature water at drum pressure ( ~
2000 psi and 300F). The flow rapidly changes in temperature as the leg
of water is displaced by 2000 psi saturated steam which is approximately
650F; this is a significant thermal transient. The valve should be over the
plug, gasket seal, with linear disk stack for this service.
The 501 valves starts with high inlet pressure (approximately 2400 psi)
and very low outlet pressure (0 to 100 psi). The valve must control flow to
load the turbine and then control flow as turbine load (pressure) is raised.
This requires a characterized disk stack similar to the BW100 feedwater
regulator valve. The customer would like the system to have an inherent
linear characteristics, i.e., valve stroke linear, with load increase. This
requires that we plot the C v required for each position of the valve for
load required.
The 518 and 519 valve flow conditions are about the same, i.e. ~ 2000 psi
saturated steam ~ 650F inlet and 0 to 300 psi outlet pressure. The trim
can be linear, and under plug flow.
There are other severe service applications which are common to both
drum and once-through units. These are attemperator spray valves, soot
blower control valves (for plants which use steam for soot blowing), and
auxiliary steam valves for steam from main steam to boiler feedpump
turbine.
w 17
w 18
w 19
w 20
w 21
IV.
There are two sets of heater systems in a normal power plant. The lowpressure heaters heat the condensate coming from the condensate pump so it
is near saturation when it gets to the deaereator. The other set, called highpressure heater, heats the feedwater coming from the boiler feedwater pump
so that it is near saturation when it enters the boiler. Both systems work
with same way, with the exception of the heating fluid. In the low-pressure
heaters, exhaust steam from the LP turbine is used, while the high-pressure
heaters use extraction team from the reheat section. See typical schematic,
below.
The level of condensate in the heaters must be controlled for best system
efficiency, so the drain system is fairly elaborate. There are emergency heater
drain valves which bypass the fluid to the condensor. There are heater drain
valves between each other. Each heater is at a lower pressure than the
preceeding heater. The fluid in the first heater is saturated water as the fluid
flows through the drain valve to the next heater, the fluid flashes, the flashed
steam passes over the tubes containing the condensate, and the heat of the
steam is absorbed by the tubes warming the condensate. At the same time
the steam temp is reduced to saturated water. This saturated water is let down
to the next heater and the same process occurs.
w 22
w 23
All boilers require a minimum fluid flow through the furnace wall tubes at
even a minimum firing rate to protect the furnace tubes from overheating.
Protection is provided by circulation of a minimum amount of feedwater
and the use of a startup bypass system.
w 24
Many variations exist when comparing the startup systems provided by each
of the boiler manufacturers. Functionally, they all have a common purpose
as elaborated below. Notice in Figures 1, 2 and 3, the physical differences
illustrated for each of the once-through boiler manufacturers. Combustion
Engineering, Inc., (Figure 3 on Page 52) provides circulation pumps to
recirculate fluid through the furnace pumps and convection walls and, in
this way, protect the tubes from overheating. (Figure 3 on Page 52) Babcock
& Wilcox Company and Foster Wheeler Corporation (Figure 2 on Page 52)
require a minimum pumping rate be established to provide this same protection.
Because of these individual differences, control systems vary on each of
these units insofar as the actual coordination of the valves in each startup
system. However, again analyzing the job that has to be performed, the
functional objectives of all systems are the same, namely:
1)
2)
All systems provide some means of circulating water through the system
for both a cold and hot water cleanup through the use of a polishing
system.
3)
All systems provide for an orderly sequence to startup and initially load
the unit as follows:
a)
b)
c)
When the enthalpy level in the flash tank or separator reaches some
minimum desired level, steam can be admitted to the superheater and
main steam lines for warming purposes.
d)
w 25
e)
2)
3)
Saturated steam from the flash tank or separator to the super heater is
being replaced with steam directly from the evaporating section of the
boiler. This means the enthalpy leaving the furnace section must be
maintained at an enthalpy level approximately that of steam leaving
the flash tank. By properly programming the opening of the inline stop
valves (B&W = 200, FW = Y, CE = BT)and changes in pumping and firing
rate, outlet steam temperatures can be maintained during this transfer
to straight through operation.
Thus during startup and low load operation prior to the turbine load
exceeding the minimum feedwater flow, the control system must utilize
the bypass system valves as an extension of pressure control and
feedwater flow control. During this period, the heat input must be
properly controlled to provide the required steam conditions at the
turbine, recognizing that some heat is being lost through the bypass
system until it is taken out of service.
w 26
w 27
w 28
w 29
1.
2.
3.
The 207 is set to maintain 600 PSI at the inlet to the primary superheater.
4.
The 241 (flash tank level control valve) is open, dumping all flow to the condenser and to the condensate polishing
system. The flash tank will be flooded during this mode to allow the 241 to pass total startup flow.
5.
The 242 valve is kept closed until the flash tank level starts to fall below the flash tank centerline, it will then open
until the flash tank level hits a predetermined high level set point.
6.
Circulation is maintained in this manner until the cation conductivity entering the economizer and at the 207 valve
inlet is below 1 .
w 30
2.
All flash tank drain flow will be transferred from the condenser to the deaereator. The 241 valve is held closed and 230 (deaereator
water pegging control valve) is held open until the deaereator is pegged at its full-load operating pressure (approx. 140 PSI). After
the deaereator is pegged the 230 valve will limit flow to the deaereator to maintain its pressure at set point.
3.
The 241 will control flash-tank level about its normal level after the deaereator is pegged.
4.
When the fluid temperature at the primary superheater inlet exceeds 300 F, the primary superheater outlet pressure setpoint
will be ramped automatically from 600 to 3650 PSI at the primary superheater outlet.
5.
As a temperature leaving the primary superheater increases the 207 operates to maintain a programmed primary superheater
outlet temperature.
6.
At the temperature of 300 F, the 207 valve opens to a minimum position. As the temperature leaving the primary superheater
increases, the 207 operates to maintain a programmed primary superheater outlet temperature.
7.
The 220 (H.P. heater steam control valve) and the 240 (flash tank overpressure control valve) will open to limit the flash
tank pressure at its set point of 500 PSI.
8.
During this period, the secondary superheater will be boiling out to remove all water.
9.
w 31
At a flash tank pressure of 300 PSI, 205 (low pressure superheater nonreturn valve), will open.
2.
The 210 (turbine bypass valve), is opened to pass approximately 2% of full load through the superheater to warm the
main steam lines. The flash tank pressure will continue to increase as firing is continued to its set point of 500 PSI.
3.
At the flash tank pressure of 500 psi, the turbine can be rolled, approximately 2% of full load flow is required to roll the
turbine. The 210 valve should be kept open to pass an additional 2% flow to the condenser.
4.
The firing rate should be adjusted until the gas temperature is approx. 50F above the desired temperature to the
turbine.
5.
After the turbine steam requirements have been met, the 220 (flash tank steam to H.P. heater) valve will be opened
to limit flash tank pressure to 500 psi.
6.
The 241 valve is still maintaining flash tank level, the 230 valve is maintaining deareater pressure (approximately
140 PSI).
7.
When the capacity of the 220 valve is exhausted, the steam entering the turbine should be increased to 1000 PSI. This
will increase the flash tank set point to 1000 PSI.
8.
The 220 and 240 valves are automatically set to hold the flash tank at its set point of 1000 PSI
9.
At a flash tank pressure of 1000 PSI, the turbine can be synchronized and loaded. The unit load is ramped to
approximately 7% load.
w 32
When the load on the turbine reaches approx. 7%, the 201 (pressure reducing valve) will begin to open. This will allow
steam to flow directly to the secondary superheater, rather than to the flash tank.
2.
Pressurization of the secondary superheater occurs as the 201 is opened. (The turbine throttle valves are set to maintain
approximately 7% to 25% load as the secondary superheater is pressurized. When the secondary superheater pressure
exceeds the flash tank pressure, the 205 valve will close.
3.
The 201 valve will continue to be opened at a predetermined rate to allow the turbine load to increase to approx. 25% of full load.
4.
As the 201 opens, the 207 will close to control the primary superheater outlet pressure at its set point.
5.
The flash tank drain flow to the deaereator will decrease as the 201 valve is opened. The deaereator pressure will decay as
the flash tank drains increase. When the deaereator pressure decreases below 25 PSI, the 231 valve will open to hold the
deaereator pressure at 25 PSI with flash tank steam.
6.
The flow to the secondary superheater is through the 201 valve until its capacity is exhausted, which is typically around 25% of
full load. The 200 (high-pressure stop valve) will then be opened to achieve full pressurization of the secondary superheater
7.
As the 200 and 201 valves are opened, the 202 valve will close to hold primary superheater outlet pressure at 3650 PSI.
8.
As the flow to the flash tank decreases, the heaters and deaereator will be pressurized by steam from turbine extraction points.
9.
As the load on the turbine reaches 25% the 202 and 207 valves will close and their opening set point will be
4250 PSI. These valves will now act as relief valves during a unit trip.
10. The 260 valve (flash tank warming line non-return valve; not shown, bypasses the 231 valve) will be
opened to pass a small amount of
steam from the deaereator back to the
flash tank. This is required in order to
keep the flash tank warm in case the
202 or 207 valves open for
overpressure relief.
11. Duringthistimethe241valve
operates to maintain flash tank level.
w 33
w 34
The sliding pressure unit has a few modifications designed to satisfy three basic requirements of operation. These requirements are:
1.
Capability to be reliably started up and shut down to make them available for two-shift operations.
2.
Extended unit load turndown while operating in the once-through mode. To maximize the capability to reduct unit load during
off-peak demand periods without placing the boiler bypass system in service; thus maintaining reasonable heat rates at reduced
loads.
3.
Capability of variable pressure operations the once-through mode to optimize operation of the unit for load cycling. To
extend the range of operation of the unit in the once through mode it is necessary to reduce the boiler minimum feedwater
flow requirements for furnace protection.
Modifications
1.
In constant pressure units, the first pass of the furnace consists of four parallel riser circuits (sidewalls and front and rear
walls). In sliding pressure units this consists of two passes in series; pass 1 is through sidewall risers and pass 2 is through
front and rear wall risers. In addition a bypass valve around pass 1 is installed (263 valve), to limit the flow through
the sidewalls to 125% of original design. This bypass is to limit the additional pressure drop created by the dual pass
arrangement of the lower furnace. A second bypass valve (264 valve) around pass 2 is added to further reduce this pressure
drop; this allows a minimum feedwater flow rate of approximately 10% of full load flow.
2.
For capability of the boiler/turbine temperature matching during startup and for accurate mainstream and hot
reheat control while operating on the bypass system, steam attemperators are added for the secondary superheater and
reheater. The second superheater steam attemperator requires the addition of valves 218 and 205C. The latter is used
to maintain enough
differential pressure
between the flashtank
and the throttle to
support the
attemporation
function. The flash
tank steam is used
for superheat steam
attemperation, since
this function is
required only while on
the bypass system. The
reheat steam attemperation requires
a 219 valve which takes steam from
downstream of the 401 valve, since this reheat
steam attemperation is needed while on the bypass system
and also during once-through operation at lowload generator.
3.
The 202 valve is eliminated from the cycle and the 207 valve is used for all
The key valve(s) for sliding pressure is the 401 valve. This valve is the turbine pressure
control valve. The valve must control load from as low as 10% at 2500 PSI pressure
drop to 100% at approx. 50 PSI pressure drop with a linear installed stroke vs. load
characteristic.
w 35
401 Valve
Disk Stack
w 36
w 37
w 38
W VALVE
Pressure reduction. This valve is usually sized for approximately 25%
boiler flow at 300 psi differential pressure with an equal percentage
characterized disk stack.
P VALVE
Superheater bypass valve. This valve discharges to the flash tank. During
start up the valve is used in series with W valve to control boiler pressure
as temperature is raised. When the unit is on line the P valve is closed
and functions as a pressure relief valve for the boiler. The valve must have
good shutoff. The pressurized seat valve, like the 207 valve in the B&W once
through system (Figure 4A), should be used here. The disk stack can be MS
2000 16 turn type with linear characteristics.
RECIRCULATION VALVES FOR CONDENSATE,
BOOSTER AND MAIN FEEDWATER PUMPS
These valves are the same as on the B&W system.
D VALVE
Flash tank level. This valve is the same as the B&W 241 valve.
E VALVE
Flash tank level (along with D valve). This valve is the same as the B&W
221 valve.
C VALVE
Flash tank to H.P. heater. This valve is the same as the B&W 220 valve.
B VALVE
Flash tank to deaereator. This valve is the same as the B&W 231 valve.
A VALVE
Flash tank to overpressure control valve. This valve is the same as the B&W
240 valve.
w 39
w 40
w 41
W VALVE
Pressure reducing station. This valve is usually sized for approximately
70% boiler flow at 300 psi differential pressure with an equal percentage
characterized disk stack.
P VALVE
Superheater bypass valve. During startup, this valve is used in series with
the W valve to control boiler pressure and level in the separators. The
P valve discharges to the heaters, deaereators, and condenser through the
E, F, and D valves.
RECIRCULATION VALVES FOR CONDENSATE,
BOOSTER AND MAIN FEEDWATER PUMPS
These valves are the same as on the B&W system.
D VALVE
Separator to condenser. This valve is the same as the B&W 241 valve.
E VALVE
Separator to heater. This valve is the same as the B&W 220 valve.
F VALVE
Separator to deaereator. This valve is the same as the B&W 231 valve.
MX VALVE
Auxiliary steam to BFPT (attemperator at low flow). This valve is used to
inject saturated steam into the steam exiting the platen superheater during
system low flow operation.
PR VALVE
Auxiliary steam to BFPT. This valve takes steam from the platen superheater
outlet during system low flow operation.
w 42
w 43
Combustion Engineering,
Once-Through Unit Base Loaded
w 44
BT Valve
w 45
w 46
Combustion Engineering
Supercritical Once-Through Type Unit
Description of CE Once-Through
Unit and a Modification for
Sliding Pressure to 70% Load
BE
BTB
BT
SA
SP
WD
IS
IR
SD
FWB Feedwater control valve. Controls feedwater flow from 5% to 25% unit flow.
w 47
For large supercritical units, 30% turbine bypass is a technical and economic
handicap. Therefore the Combined Circulation design utilizes furnace wall
recirculation rather than a turbine bypass system; a recirculation line takes
the fluid from the furnace wall outlet and discharges it into the inlet of
the furnace wall system. A circulating pump at the inlet of the furnace wall
system maintains the required minimum furnace wall velocities, at lower
loads automatically, by recirculaton superimposed on the once-through flow.
The unit through-load (flow to the turbine), as maintained by the boiler
feedpump, increases in direct proportion to unit load. The recirculated
flow, as maintained by the circulating pump, supplements the throughflow over the lower load range in a manner which protects the furnace
walls by raising the total flow through the walls to a safe level, regardless
of feedwater flow. At approximately 10% load, the pressure drop through
the furnace wall system equals the head produced by the circulation
pump and the stop-check in the recirculation line automatically closes.
The recirculation then ceases to produce recirculation of furnace wall flow
but continues to contribute its positive head to the total unit throughflow, in this manner acting as a booster to the boiler feedpump.
w 48
w 49
The startup shown is for a base loaded unit. The Sulzer valves and actuators are
designed to be operated within the conditions shown.
For instance, the first BT valve is shown to start to open at 18% load. The
pressure drop across this valve at 18% load is 1700 psi. The BT actuators are
sized for that pressure drop. The valve should not (and probably cannot) be
opened at less than 18% load because of the greater pressure drop. The valve,
plus packing friction, is the actuator load. Thus, actuator load is proportional
to system pressure drop.
For lowload operation at less than 30%, the unit may operate with the turbine
throttle valves at 30% and the BT and BTB valves in control between 10% and
30% load. The unit could also operate at less than 10% by transfer from oncethrough to the BE valve and separator startup system.
To reduce load down to the low load is a reverse of the startup. The turbine
throttle valves are used to change the load down to 30%, the BT valves
are brought down to control, and then the BTB valves are as well. The load
reduction via the turbine throttle valves must be done slow enough so as
to minimize thermal stresses on the turbine. There is a fluid temperature
reduction with throttling. Once on the BT valves, the pressure throttling is
across the BT valves and the temperature to the turbine remains constant
because of the superheaters after the BTs. Changing load while on the BT valves
is sliding pressure. This means that varying the load in the 30% to 100% load
range on the turbine throttle valves is slow, but once on the BTs, the load can
vary relatively fast as far as the turbine is concerned.
The Sulzer BE, BTB, and BT valve are extremely heavy-duty valves. They were
designed for the startup and shutdown of the unit as discussed so far. However,
extended time at low load using these valves and actuators was not in the
original scope.
So the question is, What should be done to address extended low load or
sliding pressure operation of the unit?
If sliding pressure (extended service time) is done, the BT valve trim should be
changed from linear to equal-percentage flow characteristic. Also the actuator size
should be increased to enable full pressure range operation on the BT valves.
The equal-percentage characteristic is required so there is a smooth change
in flow as each successive BT valve is opened or closed. Especially important
is when the first BT is opened. At that time the BTB is controlling waterwall
pressure. The BTB trim has about 10 times less plug area than the BT plug area.
When the BT opens, the BTB valve must close to maintain waterwall pressure
as the flow is increased through the BT valve. With the significant difference
in plug size, the equal percentage trim in the BT would allow smooth increase
of flow while minimizing waterwall pressure swing. The equal-percentage trim
requires a larger seat ring bore in the BT valve in order to maintain the
same maximum capacity (Cv). The BT valves combined maximum capacity
must be at least the same as before. The resistances between the pump and
turbine (called parasitic power) must not increase. The forgoing is addressing
extended operation on the BT and BTB valves down to about 10% load on
once-through operation.
The unit could transfer to the startup system for low load down to
approximately 7%. However, transfer from once-through to the startup
system introduces problems of feedwater control and feedwater chemistry. The
frequent cycling of the unit for sliding pressure or for low load operation is best
done on once-through operation.
With BT valves modified with equal-percentage trim, increased seat ring size
for capacity, and larger actuators, the unit can be operated on sliding pressure
to a higher load than 30%. Shown below is a 70% system showing the startup
and once-through ranges of the Sulzer valves:
w 50
The system could be configured with only the BT valves. However the BTB
capacity addition at 100% load is of benefit for minimizing parasitic power.
w 51
The operation of the bypass system can be broken down into two basic areas
of control: the low load and pressure portion of the pumping and firing
controls, and the flash tank sub-loop controls.
The pumping and firing rate controls include the control of the boiler
feedpump, the firing rate and control of critical control valves.
These critical valves for the three major once-through boiler manufacturers
are shown below:
The flash tank subloop controls include the following valves in the three
boiler designs:
w 52
Figures 1 Through 3
Base-Loaded Configurations
Figure 1
Babcox & Wilcox
Once Thru Unit
Figure 2
Foster Wheeler
Once Thru Unit
w 53
Figures 3 Through 4
Base-Loaded Configurations
Figure 3
Combustion Engineering
Once Thru Unit
Figure 2
Riley Stroker
Once Thru Unit
w 54
Figures 4 Through 6
Sliding Pressure Configurations
Figure 4
Babcox & Wilcox
Once-Through Unit
Figure 2
Foster Wheeler
Once-Through Unit
Figure 3
Combustion Engineering
Once-Through Unit
w 55
w 56
Stein Boiler
w 57
Contact us at:
info@ccivalve.com
Visit us online at:
www.ccivalve.com