SEQUENCE CONTROL
(SEQUENCE TABLE)

PT. Yokogawa Indonesia


Wisma Aldiron Dirgantara 2nd floor, suite 202-209
Jl. Jend. Gatot Subroto Kav.72 Jakarta 12780
Phone : 021-799 0102, Fax : 021-799 0070

TYPES OF SEQUENCE CONTROL BLOCKS

The following function blocks are catagorized as sequence


control blocks:
1.Sequence Table Blocks
2.Logic Chart Block
3.Sequential Function Chart Block
4.Switch Instrument Blocks
5.Sequence Element Blocks
6.Valve Monitoring Block

PT YOKOGAWA INDONESIA
Training Center Technical Support Group

TYPES OF SEQUENCE CONTROL BLOCKS (1/2)

Sequence Table Blocks


This function blocks realizes sequence control by operating other function blocks and/or
process or software I/O.
There are two basic type of Sequence Table blocks:
Sequence Table Block ST16
Rule Extension Block ST16E
On top of the basic types above, there are also other types such as
Sequence Table Block M_ST16
(Number of condition signals: 32 to 64, number of action signals: 32 to 64 / Total 96)
Rule Extension Block M_ST16
Sequence Table Block L_ST16
(Number of condition signals: 64, number of action signals: 64 / Total 128)
Rule Extension Block L_ST16
The conditions & operations are arranged in the table format & specifies which operation
is performed by the combination of conditions.

PT YOKOGAWA INDONESIA
Training Center Technical Support Group

SEQUENCE TABLE BLOCK (ST16, ST16E)


Sequence Table block (ST16, ST16E) is a decision table type function block that describes
the relationship between input signal and output signal in a Y/N (Yes/No) fashion.

The ST16 block has a sequence control function that handles a total of 64 I/O signals and 32
rules. The I/O signals can also be redistributed in the 8-signal unit.
The rule extension block (ST16E) is used for extending the rules of ST16 block. It connects
to an ST16 block and only allows connection to a step-type ST16 block. Hence, it cannot be
used/activated independently.

PT YOKOGAWA INDONESIA
Training Center Technical Support Group

SEQUENCE TABLE BLOCK (ST16, ST16E)


I/O connection is set by describing
connection information & data in the
input connection information setting
area, condition setting area, output
connection information setting area &
operation specification setting area of
the sequence table.

PT YOKOGAWA INDONESIA
Training Center Technical Support Group

SEQUENCE TABLE BLOCK (ST16, ST16E)


When the phase step sequence table is used, the number of processes (number of steps)
may be insuficient depending on the process that is being performed.
Solution: use the rule expansion format sequence table block (ST16E) to expand the
number of rules.

PT YOKOGAWA INDONESIA
Training Center Technical Support Group

SEQUENCE TABLE BLOCK (ST16, ST16E)


Complete Sequence Table
Configuration
Condition Signal

Enter the element symbol in the Tag Name Data


Item column (eg. FC002.ALRM) and condition
specification in the Data column (eg. HI).

Action Signal

Enter the element symbol in the Tag Name Data


Item column (eg. %AN0010.PV) and action
specification in the Data column (eg. H).

Rule Number

Up to 32 rules per block may be used. The


output is based on each rule condition and
condition testing result.

Condition Rule

Use Y/N pattern (in combination) to condition


rule. If the testing result of condition signal
corresponds with the Y/N pattern, the condition
is then said satisfied.

Action Rule

Use Y/N pattern (in combination) to action rule.


If the the testing result of condition signal is
satisfied, action rule will be manipulated
according to the Y/N pattern.

PT YOKOGAWA INDONESIA
Training Center Technical Support Group

SEQUENCE TABLE BLOCK (ST16, ST16E)


Complete Sequence Table
Configuration
Step Label

Step labels are used for phase indication when


performing step sequence control in the
Sequence Table. The labels are character strings
that combine two or less alphanumeric
characters (A to Z, 0 to 9).

Next Step Label

THEN
Execute the next step label when the
corresponding rule condition status is true or
satisfied & after the manipulated output is
completed.
ELSE
Execute the next step label when the
corresponding rule status is false.

Tag Name.Data Item

Describe the connection information of the


condition and action signal (eg. FC001.MODE,
FC001.PSW, TIMER001.OP, etc).

Data

Describe the specification of condition and action


signal (eg. AUT, HI, L, H, STOP, RUN, etc).

PT YOKOGAWA INDONESIA
Training Center Technical Support Group

SEQUENCE TABLE BLOCK (ST16, ST16E)


Complete Sequence Table
Configuration
Comment

Comments are defined by user to describe the meaning


of symbols & contents of status manipulation of
condition & action rules.

Processing Timing

There ara two processing timings:


Start/Execution Timing
It refers to the timing at which control algorithms are
executed when receiving input signals. Select one of the
following type
- Periodic Execution (T)
- One-Shot Processing (O)
- Startup at Initial Cold Start/Restart of FCS (I)
- Restricted Initial Execution (B)
Output Timing
It indicates the condition or behaviour of action signals
in conjunction with the condition rule status change
(applicable with T & O type of Start Timing only).
Select either
- Output Only When Condition Change (C) or
- Output Each Time Conditions Are Satisfied (E)

Scan Period

Sequence table with periodic execution type (T) is


activated at defined scan period.
There are three types of scan periods:
- Basic Scan (1 second fixed)
- Medium Speed Scan ( 200 & 500 milliseconds)
50, 100, 250 milliseconds are also applicable.
- High Speed Scan (200 & 500 milliseconds)
50, 100, 250 milliseconds are also applicable.

PT YOKOGAWA INDONESIA
Training Center Technical Support Group

SEQUENCE TABLE BLOCK (ST16, ST16E)


Start / Execution Timing

Periodic Execution (T)


The periodic execution means that the sequence control block is repeatedly executed in a
preset cycle.

One-Shot Execution (O)


When execution timing of a function block is defined as one-shot type, the block is executed
only when it is invoked by other function block. A one-shot function block can invoke another
one-shot function block. However, such succession is limited to seven blocks. Invocation can
only be initiated from the same FCS.
Invocation signal
ACT.ON

Invoking function
block

ACT.OFF
Sequence process execution
Executing

One-shot type
function block

Idle
One-Shot Processing Conceptual Diagram

PT YOKOGAWA INDONESIA
Training Center Technical Support Group

SEQUENCE TABLE BLOCK (ST16, ST16E)


Start / Execution Timing

Initial Execution/Restart Execution (I)


In this execution type, the sequence block executes its process when the FCS performs a cold
start or a restart.

Restricted Initial Execution (B)


In restricted initial execution, the sequence control block executes only when the FCS
performs a cold start, not include restart.

PT YOKOGAWA INDONESIA
Training Center Technical Support Group

SEQUENCE TABLE BLOCK (ST16, ST16E)


Output Timing

Output Only When Conditions Are Changed (C)


The sequence table blocks output an operation/action signal only at the timing when the
judged conditions are changed from false to true. This is applicable only with periodic
execution (T) or one-shot start (O) start timing.
Condition detection
(a change from false to true state)
True
Condition rule
change

False
Action change/interuption is
possible eventhough the
conditions rule are satisfied
True

Action rule
change

False
Output Only When Conditions Are Changed Conceptual Figure

Note:
Note
However, if non-latched output is specified for the action signal, the operation changes when the
condition is switched from true to false.
PT YOKOGAWA INDONESIA
Training Center Technical Support Group

SEQUENCE TABLE BLOCK (ST16, ST16E)


Output Timing

Output Each Time Conditions Are Satisfied (E)


The sequence table blocks output its operation/action signal every scan period as long as the
judged conditions are satisfied.
Condition detection
(false or true state)
True
Condition rule
change

False
Action change/interuption is
not possible as long as the
condition remains satisfied.
True

Action rule
change

False
Output Each Time Conditions Are Satisfied Conceptual Figure

PT YOKOGAWA INDONESIA
Training Center Technical Support Group

SEQUENCE TABLE BLOCK (ST16, ST16E)


Execution & Output Timing Combination

PT YOKOGAWA INDONESIA
Training Center Technical Support Group

SEQUENCE TABLE BLOCK (ST16, ST16E)


Sequence Description Example (AND Gate)

The basic logical AND gate can be configured in a Sequence Table


as follow:

In the example above, only when all conditions signals are


satisfied the action/output operation may be performed.
PT YOKOGAWA INDONESIA
Training Center Technical Support Group

SEQUENCE TABLE BLOCK (ST16, ST16E)


Sequence Description Example (OR Gate)

The basic logical OR gate can be configured in a Sequence Table


as follow:

In the example above, when any of conditions signals is satisfied


the action/output operation may be performed.
PT YOKOGAWA INDONESIA
Training Center Technical Support Group

SEQUENCE TABLE BLOCK (ST16, ST16E)


Operation Of Non-Step Sequence
In a non step sequence table, all 32 rules are subject to condition testing and the
output operation is performed according to the conditions.
As for condition testing, a condition is
satisfied when all conditions (Y/N) for the
same rule number are true. Rule column
that is blank is considered true
unconditionally.
Operations/actions are executed according
to the operation contents of Y/N patterned
for the rule number whose conditions are
satisfied.
When the conditions of multiple rules are
satisfied simultaneously with respect to
the same action signal, if request for both
Y/N are detected as the resultant
operations, the request for Y takes
precedence and the operation for N will
not be executed.

PT YOKOGAWA INDONESIA
Training Center Technical Support Group

SEQUENCE TABLE BLOCK (ST16, ST16E)


Operation Of Non-Step Sequence (Example)
Here is an example of the sequence that normally
monitors operation to prevent the buffer tank in the
processing piping system from overflow. The sequence
table below monitors the conditions in rule numbers 01
to 04 simultaneously. If any condition becomes true,
the action/operation in the same rule will be executed.
The monitoring continues after the execution.

LAHH100.PV
LAH100.PV
LAL100.PV
LALL100.PV

PT YOKOGAWA INDONESIA
Training Center Technical Support Group

SEQUENCE TABLE BLOCK (ST16, ST16E)


Operation Of Step Sequence
In a step sequence table, the process control sequence of a phase-step process is divided into the
smallest phase units (steps) on the condition monitoring and operation, then these steps are
executed one by one.
Only step label 00 and the rule corresponding to the
Only the step currently
being executed is subject
to condition testing.
Only the actions for the
rules whose conditions
are satisfied in the step
currently being executed,
are in operation.

current step number are subject to condition testing &


operation.
Step label 00 is executed during each period & it may
only be used at the head of a sequence table group. So
it cannot be used as a next step label.
The next execution step label must be described in
THEN/ELSE part in order to advance the next step. If
both are left blank the same step is executed each time
& will not advance.
The next step specified in THEN part is the step to
advance when the condition test result is satisfied (true
state).
The next step specified in ELSE part is the step to
advance when the condition test result is unsatisfied
(false state). It will proceeds to the next step without
executing the action/operation rules.
If there are multiple requests for step transition in the
same step, the step advances to the next step label
with the smallest rule number.
The next step execution is done during the next scan
period.

PT YOKOGAWA INDONESIA
Training Center Technical Support Group

SEQUENCE TABLE BLOCK (ST16, ST16E)


Operation Of Step Sequence (Example)
Sequence Specification
1. Push the start button
Valve A opens to fill the tank with water.
2. When the tank is full
Switch A becomes ON.
Valve A is closed.
3. Push the start button again (with the tank full of water)
Valve B opens to drain the tank.
4. When the tank level becomes low
Switch B becomes ON
Valve B is closed

Water injection
processing
(Step label A1)

Water drain
processing
(Step label A2)

PT YOKOGAWA INDONESIA
Training Center Technical Support Group

SEQUENCE TABLE BLOCK (ST16, ST16E)


Operation Of Step Sequence (Example)

Water injection
processing
(Step label A1)

Water drain
processing
(Step label A2)

In the above sequence table, rules number 01 & 02 are step A1. Rules
number 03 & up are step A2. Rules number o5 and beyond do not have any
Y/N pattern for the condition rule or action rule or move-destination step
label, so they are not subject to condition testing nor action execution.
Step A1 monitors the conditions for rules number 01 & 02 simultaneously.
Whichever the condition is satisfied will be executed. Executing the action of
rule 01 does not advance the step since there is no designation in the movedestination step label. After executing the action, A1 resumes monitoring
rules number 01& 02 again. When rule number 02 conditions become true,
the action of rule 02 is executed & the step advances to A2 as stated in the
move-destination step label.

PT YOKOGAWA INDONESIA
Training Center Technical Support Group

SEQUENCE TABLE BLOCK (ST16, ST16E)


Number Of Condition & Action Signal
By default, sequence table ST16 has 32 condition signals and 32 action/operation signals. However,
this allocation of condition & action signal can be changed on 8-signal unit basis.

PT YOKOGAWA INDONESIA
Training Center Technical Support Group

SEQUENCE TABLE BLOCK (ST16, ST16E)


Number Of Condition & Action Signal
Table : Combination of Condition & Action Signal Counts
Number Of Condition Signal

Number Of Action Signal

56

16

48

24

40

32 (default)

32 (default)

40

24

48

16

56

PT YOKOGAWA INDONESIA
Training Center Technical Support Group

SEQUENCE TABLE BLOCK (ST16, ST16E)


Rule Extension
The number of rules in one sequence table is fixed at 32 & cannot be modified. However, if the
number of rules in a sequence table is not enough to describe one phase unit, it can be extended in
the 32-rule unit by connecting to another sequence table. The number of rules can be extended for a
step-type sequence table.

Type the tag number of the extended


sequence table in the NEXT box of
the first/extending sequence table.

PT YOKOGAWA INDONESIA
Training Center Technical Support Group

SEQUENCE TABLE BLOCK (ST16, ST16E)


Condition Signal Description (Function Blocks and I/O Data)
Function blocks that can be processed in a sequence table are shown below.

Switch Instrument Block

Valve Monitoring Block (VLVM)

Timer Block (TM)

Regulatory Control Blocks

Software Counter Block (CTS)

Calculation Blocks

Pulse Train Input Counter Block (CTP)

Faceplate Blocks

Code Input Block (CI)

SFC Blocks

Code Output Block (CO)

Unit Instrument Blocks

Relational Expression Block (RL)

Sequence Table Blocks

Resource Scheduler Block (RS)

Logic Chart Block

I/O data that can be processed in a sequence table are shown below.

Processing I/O (Digital Input/Output)


Software I/O (Internal Switch, Annunciator, Global Switch)
Communication I/O

PT YOKOGAWA INDONESIA
Training Center Technical Support Group

SEQUENCE TABLE BLOCK (ST16, ST16E)


Condition Signal Description (Switch Instrument & Enhanced Switch Instrument Blocks) 1/2

PT YOKOGAWA INDONESIA
Training Center Technical Support Group

SEQUENCE TABLE BLOCK (ST16, ST16E)


Condition Signal Description (Switch Instrument & Enhanced Switch Instrument Blocks) 2/2

PT YOKOGAWA INDONESIA
Training Center Technical Support Group

SEQUENCE TABLE BLOCK (ST16, ST16E)


Condition Signal Description (Timer Block [TM])

PT YOKOGAWA INDONESIA
Training Center Technical Support Group

SEQUENCE TABLE BLOCK (ST16, ST16E)


Condition Signal Description (Software Counter Block [CTS])

PT YOKOGAWA INDONESIA
Training Center Technical Support Group

SEQUENCE TABLE BLOCK (ST16, ST16E)


Condition Signal Description (Pulse Train Input [CTP])

PT YOKOGAWA INDONESIA
Training Center Technical Support Group

SEQUENCE TABLE BLOCK (ST16, ST16E)


Condition Signal Description (Code Input Block [CI])

Condition Signal Description (Code Output Block [CO])

PT YOKOGAWA INDONESIA
Training Center Technical Support Group

SEQUENCE TABLE BLOCK (ST16, ST16E)


Condition Signal Description (Relational Expression Block [RL])

PT YOKOGAWA INDONESIA
Training Center Technical Support Group

SEQUENCE TABLE BLOCK (ST16, ST16E)


Condition Signal Description (Resource Scheduler Block [RS])

PT YOKOGAWA INDONESIA
Training Center Technical Support Group

SEQUENCE TABLE BLOCK (ST16, ST16E)


Condition Signal Description (Valve Monitoring Block [VLVM])

PT YOKOGAWA INDONESIA
Training Center Technical Support Group

SEQUENCE TABLE BLOCK (ST16, ST16E)


Condition Signal Description (Regulatory Control Block) 1/4

PT YOKOGAWA INDONESIA
Training Center Technical Support Group

SEQUENCE TABLE BLOCK (ST16, ST16E)


Condition Signal Description (Regulatory Control Block) 2/4

PT YOKOGAWA INDONESIA
Training Center Technical Support Group

SEQUENCE TABLE BLOCK (ST16, ST16E)


Condition Signal Description (Regulatory Control Block) 3/4

PT YOKOGAWA INDONESIA
Training Center Technical Support Group

SEQUENCE TABLE BLOCK (ST16, ST16E)


Condition Signal Description (Regulatory Control Block) 4/4

PT YOKOGAWA INDONESIA
Training Center Technical Support Group

SEQUENCE TABLE BLOCK (ST16, ST16E)


Condition Signal Description (Calculation Block) 1/4

PT YOKOGAWA INDONESIA
Training Center Technical Support Group

SEQUENCE TABLE BLOCK (ST16, ST16E)


Condition Signal Description (Calculation Block) 2/4

PT YOKOGAWA INDONESIA
Training Center Technical Support Group

SEQUENCE TABLE BLOCK (ST16, ST16E)


Condition Signal Description (Calculation Block) 3/4

PT YOKOGAWA INDONESIA
Training Center Technical Support Group

SEQUENCE TABLE BLOCK (ST16, ST16E)


Condition Signal Description (Calculation Block) 4/4
The table lists the calculation
blocks that can be referenced
in the condition signal as oneshot operation.
The format is:
TAGNAME.ACT.ON

PT YOKOGAWA INDONESIA
Training Center Technical Support Group

SEQUENCE TABLE BLOCK (ST16, ST16E)


Condition Signal Description (Faceplate Block)

PT YOKOGAWA INDONESIA
Training Center Technical Support Group

SEQUENCE TABLE BLOCK (ST16, ST16E)


Condition Signal Description (Sequential Function Chart Block)
The following lists the data
items of SFC block that can
describe data values in
condition specifications and
their setting ranges:
STEPNO:

1 to 99

SWCR[5]: 0 to 15
SWST[5]: 0,1
SWOP[5]: -15 to 15

PT YOKOGAWA INDONESIA
Training Center Technical Support Group

SEQUENCE TABLE BLOCK (ST16, ST16E)


Condition Signal Description (Unit Supervision Block)

PT YOKOGAWA INDONESIA
Training Center Technical Support Group

SEQUENCE TABLE BLOCK (ST16, ST16E)


Condition Signal Description (Processing I/O Block)

Condition Signal Description (Global Switch)

PT YOKOGAWA INDONESIA
Training Center Technical Support Group

SEQUENCE TABLE BLOCK (ST16, ST16E)


Condition Signal Description (Software / Common Switch)

Condition Signal Description (Communication I/O)

PT YOKOGAWA INDONESIA
Training Center Technical Support Group

SEQUENCE TABLE BLOCK (ST16, ST16E)


Condition Signal Description (Annunciator Message)

PT YOKOGAWA INDONESIA
Training Center Technical Support Group

LABORATORY WORKS
Create a logic sequence from these control narratives:
Case 1
In a cascade loop, if the process variable of the slave controller is HighHigh alarm then the slave controller mode will have to switch to
CASCADE mode and the master controller mode will have to switch to
AUTO mode.
However, the operator is allowed to change the mode of slave controller
to MANUAL or AUTO mode even tough the process variable is still in
High-High alarm state.
Case 2
In a cascade loop, if the process variable of the slave controller is HighHigh alarm then the slave controller mode will have to switch to
CASCADE mode and the master controller mode will have to switch to
AUTO mode.
The control mode of the slave controller cannot be changed until the
alarm vanishes (process variable is in normal state).
PT YOKOGAWA INDONESIA
Training Center Technical Support Group