Professional Documents
Culture Documents
Measuring Earth Resistance
Measuring Earth Resistance
A few fundamentals
1.1
The efficiency of an earthing system is principally determined by its impedance ZE. As can
be seen from figure , the earth impedance
can be expressed as in equation (1):
Z E = RE2 + X E2
(1)
RE = RD + RM + RC
(2)
1.3
UM
(3)
with
XM reactance of the metallic earth electrode
XC reactance of the earthing conductor.
For AC supply current the reactance of the earthing conductor is only significant in the case of
extended horizontal earthing strips or long earth
rods. In all other cases, the difference between
earth impedance and earth resistance is so
small that frequently no distinction is made between these two quantities. The relevant industrial standards also treat earth impedance and
earth resistance as identical.
As earthing measurements are carried out using
an AC supply, it is actually the earth impedance that is measured. If the measurement frequency is greater than 50Hz, a slightly larger
earth impedance is displayed. However, overestimating the earth impedance is not a problem, as it errs on the side of safety.
1.2
Requirements for
earthing measurements
Earthing measurements are necessary whenever compliance with a specified earth resistance or a particular earth impedance is required, as is the case in the following earthing systems:
Protective earth for TT and IT earthing sys-
Standards for
measuring instruments
Avoiding hazards
and measuring errors
The process of measurement and any accompanying procedures (e.g. breaking standard
connections and making non-standard connections) must not pose a safety hazard ([3],
sec.61.1.3). The magnitude of the test voltage or the test current must be limited (see sections 3.1 and 4.1). Before breaking a connection that is required for electric shock prevention,
the entire power installation must be disconnected from the supply and locked out to prevent it being switched on again.
Any measurement that involves breaking connections (e.g. opening the inspection joint of a
lightning protection system) must never be carried out during a storm or whenever a storm
could be expected. Failure to comply could be
hazardous, particularly for the person performing the operation. After the measurement has
been completed, any connections that were
broken must be properly restored.
If the test current is split so that part of it runs
parallel to the earth electrode being measured,
the earth resistance displayed by the meter will
be too small. The person conducting the measurement must therefore be aware of everything
that is connected to the earth electrode under
test [8]. Measurements must only be carried
out by competent persons.
1.6
The specific resistance of soil decreases with increasing temperature and increasing soil moisture levels. Whereas these effects are of minor
consequence for foundation earth electrodes in
buildings with a basement or for long (vertical)
rod electrodes, they have to be taken into account in the case of horizontal surface earth
electrodes.
Measurements made during cold, dry weather
remain unaffected, but measurement data recorded in warm weather or after a rain shower
have to be adjusted upward.
ZE
RD
1.4
XE
1.5
XM XC
RM RC
RE
1.7
Assessing
measurement results
Earth resistance meters are not error free. Measurement errors can occur even if the conditions specified in the relevant standards and instrument instruction manuals are complied
with and even in the absence of interference effects. The magnitude of an instruments operating error is listed on its technical specification
sheet or in its instruction manual. In those methods of measuring earth resistance that draw
current directly from the power source (see
sections2.4 and 4), additional measurement
uncertainty can be caused by random current
and voltage fluctuations in the supply during
the measurement.
Examples of possible operator errors include:
failure to take account of connections detrimental to the measurement process
connecting the instrument leads incorrectly
or selecting the wrong setting on the selector
switch of the instrument
inserting the auxiliary earth electrode or
probe in the wrong location
meter reading errors
failure to implement measures to reduce systematic measurement errors.
Results from first-time measurements should
be compared with the project specifications, results of repeat tests should be compared with
those of earlier measurements. If significant differences are apparent, the possible causes of
the discrepancy should be determined. The influence of weather on the measurement results
and how this can be taken into account is discussed in section1.6.
1.8
Test report
Measuring earth resistance is only one of several tests that have to be performed on earthing
Table
2
2.1
Overview of measurement
methods for RE
Principles
There is a wide degree of variation in the internal circuitry of the measuring instruments used
and the layout and arrangement of the external
measuring circuits. However, a common feature of all the methods is that they determine the
earth impedance by measuring the voltage
across the earthing system for a known test current. Leads that carry the test current outside of
4
5
6
7
Designation based on internal circuitry
Balanced-bridge methods
Current-voltage methods
Distinction based on whether method draws current directly from supplyv)
yes
no
Distinction based on use of probe and/or auxiliary electrodew)
probe and
probe, no
no probe, no
probe and
probe, no
no probe, no
probe
auxiliary
auxiliary
auxiliary
auxiliary
auxiliary
auxiliary
electrode
electrode
electrodex), y)
electrode
electrode
electrodex)
(stakeless
method)
Figure
2
3b)z)
3c)
3a)
3b)
3c)
4a)
Detailed description in section
2.2
3.2
3.3
3.4
4.3
Detailed schematic of measurement method
5
6
7
11
v) For current-voltage techniques, this distiction is included in the method name.
w) All methods include this distinction as part of the method name.
x) Measures resistance of conductor loop via earth return path.
y) An earth resistance meter does not need to be inserted into the earthing conductor if a clamp-on resistance meter is
conductor.
z) In the case of balance-bridge methods, figure only applies to the exterior circuit.
PEN or neutral
conductor instead of probe
no probex)
4b)
4c)
4.4
4.5
12
13
L1
L2
L3
PEN
REC
PSAC
UM
UM
ES
REC
RE
RF
I3 = 0
UM
RE =
I
RE
PSAC
U1
ES
ES
ES
U2
REC
I3 = 0
I1
Probe
Auxiliary
Earth
earth
electrode
electrode
a)
RF
RE
RE < Rloop
UM
Rloop =
I
Probe
Functional Earth
earth
electrode
electrode
Functional Earth
earth
electrode
electrode
b)
c)
Current-voltage methods that do not draw current directly from the power supply
RE
Earth
electrode
UM
R2
I2
I1
REC
PSAC
I1
CT
REC
PSAC
L1
L2
L3
PEN
Probe
Auxiliary
earth
electrode
a) with probe and auxiliary electrode; b) with probe, but without an auxiliary electrode;
c) no probe, no auxiliary electrode (measures resistance of conductor loop via earth return path).
I test current; Rloop loop resistance; UM test voltage.
2.2
UM
RE =
I
Earth
resistance
meter
UM
RE =
I
L1
L2
L3
PEN
or N
UM
RE =
I
UM
U0
UM
UM
I
V
V
S
UM
I
A
I
A
V
S
E
UE
RF
Probe
Functional
earth
electrode
a)
RE
Earth
electrode
RF
Functional
earth
electrode
b)
RE
Earth
electrode
RE
RF
Functional
earth
electrode
c)
Earth
electrode
U0 UM
Rloop <
I
RE < Rloop
UE < U0 UM
Current-voltage methods that draw current directly from the power supply
a) with probe; b) using PEN conductor or neutral conductor instead of probe;
c) no probe (measures resistance of conductor loop via earth return path);
U0 conductor-to-earth voltage
2.3
UM
I
(4)
UM
RE =
I
Earth resistance meter
REC
PSAC
I
UM
ES
Earth
electrode
Auxiliary
earth
electrode
Probe
RE
3
3.1
0.2 s 0.2 s
s
RE'
approximately
flat section
RE'2
RE'
2.4
RE'1
Distance
Current-voltage
To protect against electric shocks, the open-circuit test voltage generated by the meter must
not exceed 50V (r.m.s.) and 70V (peak). In
the case of earth resistance meters used on
agricultural sites, these values must be halved.
Alternatively, the short-circuit current must not
exceed 3.5 mA r.m.s. and a peak value of
5 mA (see [5], sec. 4.5). If neither of these
conditions are met, the meter must switch off
automatically.
The meter is powered either by a battery, a
group of primary cells or a hand-driven generator, though the latter method is now rare. The
meter must indicate whether the end-point voltage of the power supply is sufficient to maintain proper instrument function (see [4],
sec.4.3).
When earth resistance is measured by a method that does not involve current being drawn
directly from the supply, the earth resistance RE
is computed as the quotient of the measured
voltage UM that appears across the earth electrode (and across the meter socketsES and S)
and the measured current I (that flows through
socketsE and H). Figure only indicates the
basic principle of the complex circuitry within
3.2
3.2.1 Principle
As shown in figure , the earth electrode under test, an auxiliary earth electrode and the
probe are connected to the earth resistance meter. The test current I flows through the earth
electrode, the soil and the auxiliary earth electrode. The voltage UM that appears across the
earth resistance RE also appears across the meter socketsES and S. The earth resistance is
displayed as the value of UM divided by I.
3.2.4 Probe2)
As the internal resistance of the voltage measurement path is very large, the resistance of the
probe and therefore the size of the probe is of
minor importance. The preferred location of the
probe is on the straight line between the earth
electrode and the auxiliary earth electrode at a
position where it has minimum interaction with
the spheres of influence of the two electrodes
(see diagram in figure).
If one were to carry out a series of measurements with different distances between the
earth electrode and the probe the results would
form a curve whose ends are relatively steep
while the intermediate section of the curve is
flatter. If the distance between the earth electrode and the auxiliary electrode is large enough,
the curve will have an approximately horizontal
central section in which the measured resistance to earth is essentially independent of
electrode separation.
This central section must be determined by at
least three measurements. The midpoint of the
central section is not midway between the earth
electrode and the auxiliary earth electrode, but
lies closer to the auxiliary earth electrode as the
spatial extent of the spheres of influence associated with the two earth electrodes differ. In
general, the optimum separation between the
earth electrode and the probe is about two
thirds of the distance between the earth electrode and the auxiliary earth electrode3).
3.3
3.3.1 Principle
L1
L2
L3
PEN
PEN
L1
L2
L3
PEN
PEN
MEB
MEB
PE N
REC
REC
PSAC
PSAC
I
UM
A
ES
3.4
RF
RE
Functional
earth
electrode
ES
EC
EC
UM
PE N
UM
RE =
I
Earth
Probe
electrode
Rloop < RE
RF
RE
Functional
earth
electrode
UM
Rloop =
I
Earth
electrode
3.4.1 Principle
3.5
L1
L2
L3
PEN
L1
L2
L3
PEN
L1
L2
L3
PEN
PEN
MEB
ES
ES
IV
I = IE1 + Icpl
IE1 < Icpl
RM < RE1
I = IE1 + Icpl
IE1 < 0
Icpl < I
RM RE1
CMC COM
for
VIC Rloop
UM
Icpl
Icpl
EC
E2
E2
RF
RE
Functional
earth
electrode
Earth
electrode
Rcpl
RE1
RE1
RE2
IE1
IE2
IE12 = 0
IE2 = 0
a) Small distance and therefore small coupling resistance Rcpl between the earth electrode under
test E1 and a second earth electrode E2 that is connected to the PEN conductor. b) Metallic
connection to a second earth electrode that is itself connected to the PEN conductor.
Icpl current causing measurement error; RE1 earth resistance being measured; RM earth resistance displayed on meter.
3.6
S H
Earthed conductor
e. g. counterpoise
E ES
S H
UM
RE1 =
IE1
Other earth
electrodes
IP
I
IE
CMC
Lattice-type EC
pylon
SCT
EC
RE
Test
object
a)
RE < Rloop
RE2
Cases involving a TN system in which the method shown in fig. is not suitable
PE N
EC
IV
Auxiliary
Other Probe earth
electrode
earth
electrodes
IP
IE
IE1
IE2
IE3
IE4
RE1
RE2
RE3
RE4
Test object
(pyton stubs)
Auxiliary
Probe earth
electrode
b)
L1
L2
L3
N
L1
L2
L3
PEN
RCD
4
4.1
UM
RE =
I
UM
RE =
I
PE
PE
MEB
MEB
Earth
resistance
meter
Earth
resistance
meter
L
UM
UM
I
V
A
E
I
V
EC
EC
RF
Functional
earth
a) electrode
Probe
RE
RF
RE
Earth
electrode
Functional
earth
b) electrode
Probe
Earth
electrode
Current-voltage methods that draw current directly from the power supply and
that use a probe
a) Installation with TN system; b) Installation with TT system
EC earthing conductor; RCD residual current device; I test current; MEB Main earthing busbar;
RF resistance of functional earth; RE earth resistance being measured; UM test voltage
1
1
1
1
1
+
+
+
RE1 RE2 RE3 RE4
(5)
UM
RE =
I
Measuring equipment
L1
L2
L3
N
L1
L2
L3
PEN
RCD
UM
RE =
I
PE
MEB
PE
MEB
Earth
resistance
meter
Earth
resistance
meter
L
EC
UM
UM
I
V
I
V
A
E
A
E
EC
RF
Functional
earth
a) electrode
RE
Earth
electrode
RF
Functional
earth
b) electrode
RE
Earth
electrode
12 Current-voltage methods that draw current directly from the power supply and
that use the PEN or neutral conductor instead of a probe
7) The jaws of the split-core transformer are dimensioned for large rectangular-section conductors
such as the legs of high-voltage pylons.
L1
L2
L3
PEN
U0 UM
Rloop <
I
RE < Rloop
UE < U0 UM
L1
L2
L3
N
U0 UM
Rloop <
I
RE < Rloop
PE
N PE
UE < U0 UM
MEB
Earth
resistance
meter
RCD
Earth
resistance
meter
MEB
L
UM
UM
U0
U0
EC
UM
UM
I
V
A
E
A
E
EC
RF
UE
UE
RE
Functional
earth
a) electrode
RF
Earth
electrode
RE
Functional
earth
b) electrode
Earth
electrode
13 Current-voltage methods that draw current directly from the power supply and
that do not use a probe
a) Installation with TN system; b) Installation with TT system
Rloop loop resistance; U0 conductor-to-earth voltage; UE voltage across tested earth electrode
L1
L2
L3
N
UM
RE =
I
L1
L2
L3
N
UM
RE =
I
UE = UM
RCD
N
MEB
Earth
resistance
meter
L
UM
V I
E
UM
V I
E
A
E
I IP
IP
IE
CMC
EC
Functional Probe
earth
electrode
EC
RE
Earth
electrode
MEB
IE
CMC
RF
PE
Earth
resistance
meter
RF
Other
earth
electrodes
Functional Probe
earth
electrode
RE
Earth
electrode
Other
earth
electrodes
14 Selective earth resistance measurement methods that draw current directly from
the power supply and that use a probe and a clamp-on ammeter
4.2
4.3
This method is the most accurate of the techniques that draw current directly from the supply provided that the probe can be inserted into the soil at a suitable location. A schematic of
the measurement set-up is shown in figure .
The probe has to be located so that it is outside
the sphere of influence of the earth electrode.
The voltage UM between the socketsE and S
generates the test current I in the earth electrode.
4.4
This measuring techniques can be used whenever it is not possible to insert a probe into the
ground at the right location. In this method (see
figure12 ) the probe is replaced by connecting
socket S of the meter to the PEN or PE conductor in a TN system or to the neutral conductor in a TT system. Caution! The neutral
conductor must be treated as if it is live, even
though it is earthed.
The value displayed by the meter includes the
resistance to earth of the functional earth electrode. This will overestimate the resistance of
the earth electrode and thus yield a value that
errs on the side of safety.
The voltages generated by operating currents
and by fault currents in the functional earth or
in the PEN conductor or neutral conductor of
the power supply system can result in erroneous measurement results. The accuracy of
this technique is therefore lower than that
10
4.5
4.6
References
[1] IEC 60364-4-41:205 Erection of power installations with nominal voltages up to 1000 V Part
4-41: Protection for safety Protection against
electric shock.
[2] Hering, E.: Schutzerder des TT-Systems (engl.:
Protective earthing in the TT system). Elektropraktiker, Berlin 59 (2005) 5, p.370-373.
[3] IEC 60364-6:2006-02 Low-voltage electrical installations Part 6: Verification.
[4] IEC 61557-1:2007 Equipment for testing, measuring or monitoring of protective measures
Part 1: General requirements.
[5] IEC 61557-5:2007 Equipment for testing, measuring or monitoring of protective measures
Part 5: Resistance to earth.
[6] IEC 61557-6:2007 Equipment for testing, measuring or monitoring of protective measures
Part 6: Effectiveness of residual current devices
(RCD) in TT, TN and IT systems.
[7] IEC 61557-10:2000 Equipment for testing,
measuring or monitoring of protective measures
Part 10: Combined measuring equipment for
testing, measuring or monitoring of protective
measures.
[8] Hering, E.: Probleme mit einem der Erdungsmeverfahren beim TN-System (engl.: Problems
with an earth resistance measurement technique
in a TN system). Elektropraktiker, Berlin 53
(1999) 9, p.820-822.
[9] Hering, E.: Durchgangsprfungen an Erdungsanlagen [Continuity testing in earthing systems].
Elektropraktiker, Berlin 59 (2005) 11, p.888891 und in diesem Sonderdruck.
[10]DIN EN 62305-3 (VDE 0185-305-3):2006-10:
Protection against lightning Part 3: Physical damage to structures and life hazard.
The method selective earth resistance measurement8) is used if, for the purposes of the
measurement, the earth electrode under test
cannot or should not be disconnected from other earth electrodes to which it is wired in parallel. It is based on the method using a probe discussed in section4.3, but in this variant (see
figure14 ) a special earth resistance meter
(Chauvin Arnoux C.A.6115N or C.A.6456)
and an additional current measuring clamp
CMC are required. The current measuring
clamp is connected to a multipole socket on the
meter and the clamp jaws are placed around
the earthing conductor EC connected to the
earth electrode under test.
If the meter is connected in this way and if the
rotary selector switch set appropriately, IP, the
portion of the measuring current I flowing via
the other parallel earth electrodes, has no effect
on measurement result so that the branch current IE recorded by the current measuring clamp
CMC is solely responsible for determining the
resistance to earth RE displayed by the meter.
8) On its own, the expression selective earth measurement is ambiguous, as other earth resistance
measurement techniques are also selective, e. g.
those presented in sections 3.4, 3.5 and 3.6.
Continuity testing
in earthing systems
E. Hering, Dresden (Germany)
Continuity tests are carried out to verify that conductors, in this case metal
conductors, are unbroken. This article describes the extent to which continuity
testing in earthing systems is required and possible and also discusses the test
equipment that can be used. In terms of continuity there is no significant difference between the initial test and repeat tests, despite the fact that they are
treated separately in the relevant standards.
1
1.1
1.2
Continuity testing on ring earth electrodes is advisable for the following reasons:
a) Earth resistance measurements, which are
required by the applicable standards but are
not dealt with in this article, are unable to detect any break in the ring. While any discontinuity will not lead to an increase in the resistance to earth, it can have a significant detrimental effect on the efficiency of the
voltage protection, as the surge currents are
forced to flow via another path.
b) Repeated continuity testing on older ring
earth electrodes can, if carried out in the form
of resistance measurements, identify reductions in the conductor cross-section (as a result of corrosion) by registering an increased
resistance.
In order for continuity testing to be possible, a
buried ring earth electrode must have at least
1.3
Hazard avoidance
The process of measurement and any accompanying procedures (e.g. breaking standard
connections and making non-standard connections) must not pose a safety hazard. If the
earth electrode also functions as the protective
earthing of a TT or IT earthing system as detailed in [1], its connection to the MEB may only
be broken if the electrical installation has been
disconnected from the power source or power
generator.
Tests that involve breaking connections (e.g.
opening the inspection joint of a lightning protection system) must never be carried out during a storm or whenever a storm could expected. Failure to comply could be hazardous,
particularly for the person doing the testing.
For safety reasons, the use of voltages greater
than 25V should be avoided. Small voltages
are anyway advisable for continuity testing (see
[6], sec.612.2). The testing and measuring
equipment used must comply with the specifications in the relevant standard (see ref.[7]).
Resistance measurements are typically carried
out using equipment that conforms with the
specifications in reference [8]. However, earth
resistance meters that meet the requirements in
reference [9] can also be used.
3
3.1
Test methods
Principles
11
PS
PS
PLC
a)
PLC CAM2
TC
TC
CAM
CAM
b)
G
3
CT
a)
CT
b)
c)
PS
I2
2
CA2
CA1
G
I1
I
PS
I2 I3 = I4 I1
I3
CA4
CA3
3
I4 4
c)
3.2
3
b)
CT
2
CA2
G
PS
a)
mV VM
Continuity testing circuits that measure the current in a conductor that has
another conductor connected to it in
parallel
12
1
CA1
3.3
If the ring earth electrode has at least four connection points, a break in ring continuity can be
identified by sequentially measuring the resistance between two neighbouring connection
points. The small resistances of the conductors
that run between the point of connection of the
meter leads and the ring have to be subtracted
from the resistance displayed on the ohmmeter.
Although the soil and, in the case of a foundation earth electrode, also the concrete are connected in parallel to the metal conductor, they
have no significant effect on the measurement
result because their resistivity is very much
greater than that of steel.
If the ring is uninterrupted, the resistance measured is that of a parallel circuit comprising the
1) The semicircular jaws of the clamp contain two
transformers. The purpose of one is to induce a
voltage in the conductor, the other measures the
resulting current. The clamp is closed when the
jaws have been placed around the conductor. The
display on the clamp meter displays a resistance
value computed by dividing the value of the induced voltage by the current flowing in the conductor.
Ro = RP
(3 R ) = 3 R
(4 R ) 4
P
(4)
(43)R
Rc = 3
m
OM
Discontinuity
section of the earth ring enclosed by the measuring leads and the series circuit that makes
up the remaining part of the ring. If the earth
ring electrode is broken at some point between
the measuring leads (see figure ), the resistance measured is that of the remaining part of
the ring. If the measurement is made on one
part of the ring, the resistance of that part alone
is measured.
Example calculation 1
The ring earth electrode has four connection
points. Those parts of the ring located between
the connection points have the resistances
R1R4. If the ring is unbroken, the resistance
RO (O is used here to symbolize the intact
earth ring electrode) measured across the two
connection points that enclose the part of the
ring with the resistance R1 is given by:
1
RE =
(1)
1
1
1
1
+
+
+
RE1 RE2 RE3 RE4
However, if the part of the ring with the resistance R1 is broken, the resistance RC measured
across those same connection points (C is
used here to symbolize a ring with a continuity
break) will now be given by equation(2).
RC = R2 + R3 + R4
(2)
Example calculation 2
Situation as in example calculation 1 but each
of the four sections of the ring has the same resistance RP.
RP = R1 = R2 = R3 = R4
(5)
RC = 3 RP
o=
4Ro
(6)
References
[1] IEC 60364-4-41:2005 Erection of power installations with nominal voltages up to 1000 V Part
4-41: Protection for safety Protection against
electric shock.
[2] DIN VDE 0100-540 (VDE 0100-540):2007-06
Low-voltage electrical installations Part5-54:
Selection and erection of electrical equipment
Earthing arrangements, protective conductors and
protective bonding conductors.
[3] Prestandard DIN V VDE V 0100-534 (VDE V
0100-534):1999-04 Electrical installations of
buildings Part 5-34: Selection and erection of
equipment Devices for protection against overvoltages.
[4] EN 62305-3:2006 Protection against lightning
Part 3: Physical damage to structures and life hazard (IEC 62305-3:2006).
[5] DIN 18014:2007-09 Foundation earth electrodes.
[6] IEC 60364-6:2006-02 Low-voltage electrical installations Part 6: Verification.
[7] EN 61557-1:2007 Equipment for testing, measuring or monitoring of protective measures Part
1: General requirements (equivalent to IEC
61557-1).
[8] EN 61557-4:2007 Equipment for testing, measuring or monitoring of protective measures Part
4: Resistance of earth connection and equipotential bonding (equivalent to IEC 61557-4).
[9] EN 61557-5:2007 Equipment for testing, measuring or monitoring of protective measures Part
5: Resistance to earth (equivalent to IEC 615575).
Test report
(3)
13