Professional Documents
Culture Documents
for discussion. It is the hope of the authors that require consideration. With the ad- properly evaluating and applying motors,
that relay engineers will find the data vent of new insulation systems, of new and affording adequate relay protection.
useful in describing the advantages of new materials, and of the use of computers Since other designs may have widely
devices or applications of present devices which contribute to refinements in design, different characteristics, these data cannot
for motor protection. components other than the insulation be used in specifying a protection system
Motor users have employed, until re- system will become increasingly limiting. for any particular design other than this
cently, the stator insulation of an induction The addition of data along the lines of one. Nevertheless, this should be a
motor to define its limits of operation. this paper is therefore essential in the valuable tool in evaluating present practices.
Authorized licensed use limited to: ULAKBIM UASL ISTANBUL TEKNIK UNIV. Downloaded on March 27,2020 at 13:20:44 UTC from IEEE Xplore. Restrictions apply.
I%ZT=per-cent impedance of the tertiary tion of both. Larger kva capacity may be Other symbols used are
circuit of the autotransformer just as economieal as higher impedance. %IZOH-N=zero-sequence impedance of an
%IZH = (%IZH-L+ %7GIZH-T- %IZL-T)/2 Without any increase in impedance the re- autotransformer from the HV circuit
(1)
quired size of the tertiary winding to limit to neutral including the delta tertiary
the steady-state short-circuit current to winding
%IZL = %IZH-L -%CIZH (2) 25 times normal would be %IZOL- N = zero-sequence impedance of an
autotransformer from the LV circuit
%IZT = %CIZH-T %CIZH (3) 44 to neutral including the delta tertiary
1,658 X-= 2,918 kva winding
where 25 %IZOH- L//N = zero-sequence impedance of
%IZH- L = per-cent impedance from the HV an autotransformer from the HV
circuit to the LV circuit of the auto- Tertiary Winding Without External circuit to the LV circuit and the
transformer Terminals tertiary winding in parallel
%IZH- T = per-cent impedance from the HV %IZOL- H//N = zero-sequence impedance of
circuit to the tertiary circuit of the an autotransformer from the LV
Economy can sometimes be realized circuit to the HV circuit and the
autotransformer by omitting the terminals of the tertiary
7GIZL- T = per-cent impedance from the LV tertiary winding in parallel
circuit to the tertiary circuit of the winding in applications where the tertiary %IZOH = zero-sequence impedance of the
autotransformer does not supply any load. Then the HV circuit in an autotransformer
possibility of a 3-phase fault is removed %IZOL = zero-sequence impedance of the
As an example assume a 10,000-kva LV circuit in an autotransformer
and the tertiary winding need only be %IZoN = zero-sequence impedance of the
autotransformer, 115,000 to 69,000 volts, large enough to carry zero-sequence un- neutral circuit including the delta
with minimum-size tertiary winding with balanced currents and zero-sequence cur- tertiary winding in an autotrans-
taps in the high voltage at 120,750 and rents caused by line-to-neutral faults. To former
109,250 volts having an impedance of n= rated current based on same kva as
attain this economy safely requires the the impedances
3.68% at the 115,000- to 69,000-volt con- calculation of possible zero-sequence cur- I,= positive-sequence current expressed in
nection. The impedance at 109,250 to rents. per unit of I,
69,000 volts is assumed to be 3.12%. The A well-grounded system, that is, one 12=negative sequence current expressed in
HV system is assumed to have 1% im- having low zero-sequence impedance, per unit of In
pedance and the LV system 3% imped- o= zero sequence current expressed in per
will relieve to some extent the zero- unit of I,,
ance. The HV to tertiary-voltage cir- sequence current load on the tertiary of
cuit impedance, %IZH-T, is 15.89% and the autotransformer. For this reason it Subscripts H, L, and N following a
the LV to tertiary-voltage circuit imped- is necessary to know the maximum zero- current symbol indicate HV circuit, LV
ance is 11.5%. All impedances refer sequence impedance characteristics of the circuit, and tertiary-neutral circuit cur-
to a base of 10,000 kva. Starting with HV and LV systems that are to be rents, respectively.
these data the solution of tertiary short- connected to the autotransformer as well In calculating possible zero-sequence
circuit current is as follows: as the maximum short-circuit kva capa- fault currents in systems that do not have
%IZH (%IZH-L+ %IZH-T - %IZL-T)/2
= bilities of these systems if an exact cal- resistance grounding it is customary to
culation of the necessary size of the ter- assume that all impedances are reactances
= (3.12+ 15.89-11.5)/2 - 3.755% so that reactance equations are used for
tiary winding is to be made.
%IZL= 3.12-3.755 = -0.635% Of course, the impedances of the auto- impedances.
transformer are also necessary. Available Zero-sequence current will flow in the
%ICIZT = 15.89 -3.755=12.135% impedances at minimum cost depend on tertiary winding when there is a line-to-
Substituting these in Fig. I gives a the autotransformer rating. In general, neutral fault on either the HV or the LV
total impedance of 13.715%. the positive-sequence impedance at rated system. Simultaneous line - to - neutral
voltage connection will be the co-ratio faults on both systems could be more
10,000 X 100 = severe, particularly if the two faults were
72,900 = kva equivalent cur- times the available positive-sequence im-
13.7 15 pedances of 2-winding transformers of
rent that would flow in the
tertiary winding the same voltage class. The co-ratio, r, 21 IH 21IL
is given by the equation
The equivalent size of the series winding
is high voltage-low voltage
I= (4)
high voltage
120,750- 69,000
109,250 4
%IZHL = r X %oIZR (5)
Authorized licensed use limited to: ULAKBIM UASL ISTANBUL TEKNIK UNIV. Downloaded on March 27,2020 at 13:20:44 UTC from IEEE Xplore. Restrictions apply.
11 = 12 = IO (6)
With full voltage maintained these cur-
rents are
Table 1. Zero-Sequence Impedance Tests and the Equation for Calculating Impedance
Value from Each Test
Connection Equivalent Amperes* Equation for Converting Test Results
Test Figs. Circuit Figs. to Circulate into Per-Cent Zero-Sequence Impedance
Authorized licensed use limited to: ULAKBIM UASL ISTANBUL TEKNIK UNIV. Downloaded on March 27,2020 at 13:20:44 UTC from IEEE Xplore. Restrictions apply.
Fig. 10. These values of impedances in-
serted in equivalent circuits per Fig. 3 and
Fig. 5 will facilitate the calculation of
short-circuit currents for single line-to-
ground faults.
If it is desired to calculate fault currents
for the severe condition of simultaneous
(A) (A) line-to-ground faults on both the HV
and the LV systems with the same phase
x H faulted on both systems, the equiva-
lent circuit would be per Fig. 11. This
figure is a combination of Figs. 3 and 5.
Example
Assume a 50,000-kva autotransformer,
N N 138 kv to 69 kv, with taps at 144.9 kv
(B) (B) and 131.1 kv, having 4% impedance.
The HV system has 2,000-mva (megavolt-
Fig. 6. Connection for test of %Mioa-N (A) Fig. 7. Connection for test of %IZOL-N (A) amperes) short-circuit capacity, with
and equivalent circuit (B) and equivalent circuit (B)
XoIX,=3. The LV system has 500-mva
short-circuit capacity with Xo/X1 = 2.
H2 H2 A minimum-size tertiary winding is in-
cluded with terminals not brought out.
69
Co-ratio at 138 kv, r= 3= 0.5
138
N N
Because impedance changes are the square
(B) (B)
of the co-ratio,
Fig. 8. Connection for test of %IZOH-L//N Fig. 9. Connection for test of %IZoL-H//N %IZH -=4X =00) 3.6%
/0.474
0
2
(A) and equivalent circuit (B) (A) and equivalent circuit (B)
%oIZoR = 0.8 X 3.6 = 2.88%
Authorized licensed use limited to: ULAKBIM UASL ISTANBUL TEKNIK UNIV. Downloaded on March 27,2020 at 13:20:44 UTC from IEEE Xplore. Restrictions apply.
Table 1!. Fault Conditons
Times Rated
Current of
Kva of 10,130-Kva
Neutral Zero- Tertiary
Fault II, 12, and lo ION Sequence Current Winding
HV line to neutral
. ................. 12.46In ..... 4. 665In. 233,250 ..... ..... 23
LV line to neutral .9 .2OIn .... 4.77 In ..... 238,500 ..... 23.5
HV line to neutral with LV
disconnected.. 10.94In.. .... 4.04In ...... 245-,200 .... . 24
Simultaneous HV and LV line-
to-neutral faults .14.4 In ..... 66.65 In .... . 332,500 .... . 33
Authorized licensed use limited to: ULAKBIM UASL ISTANBUL TEKNIK UNIV. Downloaded on March 27,2020 at 13:20:44 UTC from IEEE Xplore. Restrictions apply.