You are on page 1of 6

21, rue d'Artois, F-75008 Paris Session 2000

http://www.cigre.org 12/33-02 © CIGRÉ

DETECTION OF TRANSFORMER WINDING DISPLACEMENT


BY THE FREQUENCY RESPONSE OF STRAY LOSSES (FRSL)

L. BOLDUC * P. PICHER G. PARÉ R.J. DEMERS J. BÉLANGER


HYDRO-QUÉBEC HYDRO-QUÉBEC HYDRO-QUÉBEC HYDRO-QUÉBEC HYDRO-QUÉBEC
IREQ IREQ IREQ TRANSÉNERGIE TRANSÉNERGIE
CANADA CANADA CANADA CANADA CANADA

1. INTRODUCTION This paper reviews the principles underlying the FRSL


method and the experience acquired by Hydro-Québec’s
maintenance crews in using it.
Increased competition makes it imperative that electric
utilities maximize the useful life of their existing
systems in order to defer replacement costs. Power 2. OVERVIEW OF THE FRSL METHOD
system planners require advanced techniques to assess
the risks and benefits associated with these actions.
2.1 Test circuit
The methods used to detect transformer winding
As shown in Figure 1, the test circuit required for the
displacement help assess the transformer’s condition and
FRSL measurement is the same as for the impedance
its capacity to operate without costly equipment failures.
measurement and consists in supplying low voltage to
Several methods are used to detect winding distortion
one winding of the transformer and in short-circuiting
including impedance variation measurement [1], low-
another one.
voltage impulse testing (LVI) [2], frequency response
analysis (FRA) [3], and frequency response of stray
Unlike the conventional impedance measurement
losses (FRSL) [4].
method, the FRSL method is applied on a range of
frequencies from 20 to 600 Hz, including industrial
The method used for the diagnosis of winding
frequency. This frequency range is given as a reference
displacement based on the frequency response of stray
only and can be adjusted based on the capacities of the
losses was developed at IREQ in the late 70’s. Over the
source and/or wattmeter used.
last 20 years, the method was used for the diagnosis of
winding displacement on some 40 of Hydro-Québec’s
power transformers. For the past three years, the
method has been part of the ISO procedure used for
short-circuit withstand tests at IREQ’s high-power
laboratory.
1000 VA
20-600 Hz FRSL
The method, which can be easily applied in a high-
voltage substation environment, confirms the condition volts
of the transformer windings either for purposes of amperes
watts
commissioning, after being exposed to a short-circuit, or
as part of the monitoring of the equipment’s aging.
Figure 1 : Test circuit for the FRSL measurement.
Recently, the FRSL measuring equipment was upgraded
in order to automate the testing procedure.

* 1800 boul. Lionel-Boulet, Varennes (Québec), J3X 1S1, bolduc.leonard@ireq.ca, tel.: 450-652-8287
2.2 Measured parameters This flux produces eddy currents in the conductors
which grow as the cross section that they present to the
The rms current (Irms), rms voltage (Erms) and active flux lines is greater and the frequency is higher. Losses
power (P) are measured for each frequency in order to also occur where the flux lines penetrate into the core
plot the equivalent resistance and impedance curves as a perpendicularly to the laminations. The same situation
function of frequency. The FRSL method covers the applies in the tank, which is not laminated and made of
diagnosis based on the conventional impedance magnetic material. If one of the windings is displaced,
variation measurement since this parameter is measured the configuration of the flux lines is changed and the
for each frequency, including industrial frequency. stray losses are modified, resulting in a modification of
the equivalent resistance as a function of frequency.
Equations (1) and (2) show the calculation of equivalent Section 4 shows a typical curve representing the
resistance and impedance. equivalent resistance as a function of frequency.

P 3.3 Inductance measurement


R= 2 (1)
I rms
The source should provide a sinusoidal voltage with
minimal harmonic distortion. Under sine-wave
E rms conditions, formula (3) can be used to calculate the
Z= (2)
I rms inductance based on the impedance and the equivalent
resistance.

3. CONCEPTUAL BASIS FOR THE METHOD


Z 2 − R2 (3)
L=
2πf
3.1 Impedance measurement

The impedance measurement is done with the low- The value of the inductance, which must remain
voltage winding short-circuited such that the current is constant or with a slight decrease in frequency, is a good
limited by the transformer’s leakage reactance. The indication of whether the current test is proceeding
reluctance seen by the leakage flux is largely determined correctly.
by the leakage channel located between the inside of the
inner winding, the outside of the outer winding, and the 3.4 FRSL method versus impedance measurement
top and bottom yokes. When a winding becomes
distorted, the reluctance of the magnetic path is The diagnosis of both methods is based on the flow of
modified, which leads to a change in the impedance leakage flux through the windings, but the FRSL method
measurement. has the advantage of being sensitive to variations in
eddy current losses in the windings. The method is
3.2 Equivalent resistance measurement capable of detecting the disappearance of the insulation,
which causes several parallel conductors to be short-
Given the thickness of the actual winding, part of the circuited in one area of the winding, with the result that
leakage flux crosses the conductors along the windings the conductor is made larger and consequently the eddy
and at the ends, as shown in Figure 2. current losses are increased. This kind of fault cannot
be identified by impedance measurement since the
leakage channel remains virtually unchanged.
Top yoke
Inner winding Outer winding
Tests involving controlled displacement of the windings
revealed that the FRSL method is more sensitive than
the impedance variation measurement for detecting axial
displacement in the winding assembly. Neither method,
Wound leg

leakage flux

however, is capable of detecting minor axial


displacement. The detection threshold requires that the
winding displacement be of the same magnitude as the
space between the windings.

Other results from a series of short-circuit tests have


Short-circuit Bottom yoke Power supply
demonstrated the sensitivity of the FRSL method for
detecting winding displacement [5].
Figure 2 : Leakage flux in transformer windings.
3.5 Interpretation of the results circuited together. Using the three resulting curves, it is
then possible to calculate the resistance associated with
The FRSL diagnosis is not based on the absolute value each leg’s windings.
of the resistance as a function of frequency but rather on
a comparison of curves. The comparison can be It is also possible to proceed with successive excitation
established with a similar transformer or with a previous between each end of the wye-connected winding and the
test performed on the same transformer. neutral point. The results obtained with this circuit
configuration are slightly higher. The difference is
In the case of a three-phase transformer, the results can understandable since the leakage flux is then forced out
be interpreted based on a comparison between the three of the core, completing its circuit either through the tank
phases of the transformer. There is usually a slight or other structures and, in so doing, crossing the top of
difference between the central leg’s windings and the the windings where it produces additional eddy current
end legs windings, and sometimes also between the end losses.
legs windings. These differences in the stray losses can
be attributed to the effect of the proximity of the tank, 3.7 Measurement accuracy
which is not the same on all three phases. Not all of the
additional losses occur in the tank, but the deformation 3.7.1 Active power measurement
of the leakage flux created by the tank generates higher
eddy current losses in the conductors or other structures. Wattmeter manufacturers specify the limits of error for
In such cases, a comparison with a similar transformer active power versus frequency and power factor. It is
or with a previous test performed on the same unit will recommended to use a wattmeter with the highest
be the best way of detecting displacement in the accuracy at a low power factor (cosΦ=0.01) over the
windings. entire desired frequency range.

Once field experience has been acquired and a database Voltage must be measured at the transformer’s
containing tests results has been created, an terminals. If the current is measured with a shunt
interpretation guide of the FRSL results can be produced located inside the wattmeter, the time required by the
in order to simplify the diagnosis of transformer winding voltage signal to propagate in the measurement cable
displacement. (about 3 ns/m) must be taken into account, since this can
add an error to the active power measurement, thus
3.6 Three-phase transformers tests creating a delay in the voltage signal in relation to the
current signal. This phenomenon is even more
It is preferable to use a three-phase source to test three- important for a high signal frequency and a low power
phase transformers in order to reproduce the leakage factor.
flux created in the windings during normal transformer
operation. However, if only a single-phase source is For instance, for a 600-Hz test using a 10-m
available, it is possible to perform three tests using a measurement cable, an error of about 1.1% is added
connection depending on the winding configuration, as given a power factor of 1%, while the error for 5 kHz is
in the case of the impedance measurement. In each about 9.4%. To counter this phenomenon and ensure
case, the flow of the leakage flux must be analyzed optimal repeatability of results, it is preferable to use
based on the windings configuration so that the cables that are as short as possible when measuring the
correlation can be established with the resulting losses voltage at the transformer terminals. To obtain
and the best diagnosis obtained. comparative test results, ideally the same cables should
be used, or at least ones that are of the same length.
For instance, for a three-phase three-legged transformer
with a wye-connected winding on the high-voltage side The quality of the short-circuit cable is important when
and a delta-connected winding on the low-voltage side, assessing the equivalent resistance as seen from the
it is preferable to perform the measurement from the primary side. Equation (4) shows the contribution of the
high-voltage side since the equivalent resistance is then short-circuit cable resistance to the total equivalent
higher and easier to measure. resistance seen from the primary side :

It is usually impossible to open the delta winding to Rtot = R primary + n 2 ( Rsec ondary + Rshort −circuit ) , (4)
allow each phase to be measured separately when
measurements are being done on a faulty transformer in
a high-voltage substation. In such a case, in order to where n is the turn ratio between the primary and
reproduce a flow of leakage flux between two phases, a secondary.
single-phase excitation can be successively applied
between two terminals of the wye-connected winding
with the three terminals of the delta winding short-
It should be noted that the size of the conductor must be isolate the resistance due to the eddy current losses, a
chosen based on the secondary current, which is n times good approximation consists in subtracting from the
greater than the primary current. value measured for the different frequencies the value of
the direct-current resistance obtained by extrapolation.
The short-circuit cables must therefore be very good Thus, once the temperature of the winding at the time of
conductors of the same length for each phase in the case the test is known, the results can be adjusted as required
of a three-phase test, with very low resistance in relation in order to compare them with a test conducted at a
to the resistance of each winding. different temperature.

Prior to each test, the current transformers must be


4. CASE STUDIES
short-circuited, as they can adversely affect the
impedance measurement if they are left open-circuited.
4.1 33.33 MVA, 121 kV/12.85 kV, Y∆ transformer
3.7.2 Effect of temperature
Poor contact in the no-load tap changer has degenerated,
The value of a conductor’s resistance varies as a with the creation of carbon, into a short-circuit at the
function of temperature in accordance with the voltage-regulating winding terminals. Tripping
following equations : occurred through the gas relay. Figure 3 shows the
distortion of the phase B primary winding with radial
R = R0 [1 + α ⋅ ∆T ] , ( 5) displacement of some winding components.

ρ0 l ( 6)
with ∆T = T − T0 and R0 = ,
S

where R0 is the resistance of the winding at temperature


T0 , α the thermal coefficient of the conductor
-1
(0.00393°C for copper), T0 the reference temperature
(usually 20°C), ρ0 the resistivity of the conductor at
-8
temperature T0 (for copper 1.72⋅10 Ω⋅m at 20°C),
and l and S the length and cross section of the
conductor, respectively.

In the case of eddy currents induced in the conductors,


the resistance corresponding to the stray losses
decreases with temperature as in (7) :
Figure 3 : Winding deformation resulting from a short-circuit.
Rstray 0 (7)
Rstray = Even if the displacement and failures are very evident,
(1 + α ⋅ ∆T ) the standard measurements do not reveal any fault :

In fact, additional losses are basically caused by the • the transformer ratio is maintained ;
voltages induced by the leakage flux which appears • the direct-current resistance is not modified ;
inside the conductors. These voltages lead to induced • the excitation current is not affected ;
currents with an amplitude limited by the resistivity of • the impedance measurements do not reveal anything
the material. The induced voltages depend only on the in relation to the other phases, whereas the variation
load current, which generates the leakage flux. If, remains under 1%.
following an increase in temperature, the material’s
Figure 4 indicates that the stray losses are translated by a
resistivity increases, the induced currents and,
resistance on phase B of about 15% higher than on
consequently, the losses, decrease. This is the opposite
phases A and C. The figure shows the resistance
of what occurs in the case of resistive losses which have
representing the stray losses and the direct-current
not been caused by induced voltages but rather by the
resistance.
current whose amplitude is set by the actual load. In
fact, in such a case, if the temperature increases, the
current remains the same and the losses increase.

The total resistance thus comprises the effect of the


resistive losses and the eddy current losses. In order to
12
the different frequencies in relation to the direct-current
losses :
10

kf α (9)
∆P (%) = × 100
8 Rdc
B
resistance (ohms)

6 In the case of the damaged transformer shown in


C
Figure 3, the additional losses reach 47% at 60 Hz.
4
Equation (9) can also be used to validate the quality of
the transposition inside a winding since the circulating
R stray
2 currents flowing between parallel strands cause an
increase in industrial-frequency losses in relation to
R dc
0
direct-current losses. The measurement is usually
0 100 200 300 400 capable of detecting any other fault or design flaw which
frequency (Hz) has an effect on stray losses.
Figure 4 : Variation of the resistance as a function of frequency
showing an increase in phase B resistance. 4.2 40 MVA, 121 kV/12.85 kV, Y∆ transformer

If, as indicated in Figure 5, the resistance values are This transformer was withdrawn from service since it
transferred to a logarithmic scale, a simple empirical produced gas which, when analyzed, indicated a hot spot
relationship is determined between the resistance involving paper. Laboratory tests revealed :
representing the stray losses and the frequency :
• the transformer ratio is adequate ;
Rstray = kf α (8) • the excitation current is normal ;
• an impedance measurement on all three-phases does
not reveal any significant variation.
In this instance, the coefficient α is 1.5. This empirical
model is also observed and published in reference [6]. However, the FRSL test shows a difference in eddy
current losses of 40% between phases.
An analysis of the FRSL test results reveals that the
equivalent resistance representing stray losses usually After the tests were completed, the windings were
increases as the frequency rises at a power ranging from removed. No deformation was observed. However,
1.4 to 1.8. This value is lower than the value of 2 Figure 6 shows a large burn on the varnish at one
proposed in the literature, as stated in reference [7]. location of the phase A secondary winding where 8 of
the 13 parallel strands forming the conductor are short-
10 circuited.

5
resistance (ohms)

B C
A
Figure 6 : Major burn on the varnish detected by FRSL.

This type of fault most likely is due to a flaw in the


1 varnish or from metal dust which short-circuited two
parallel strands. Afterwards, when the eddy currents
were generated between these two conductors, the spot
became increasingly hotter until it resulted in a
0,5
50 100 200 500 degradation of the varnish, thus increasing the hot spot
frequency (Hz) and the losses.
Figure 5 : Variation of the resistance representing the stray losses as a 5. CONCLUSION
function of frequency.

Equation (9), which uses the expression indicated in (8), Field experience shows that the FRSL method is an
provides a way of determining the additional losses at effective preventive and maintenance tool that is
compatible with the environment of a high-voltage 9. In order to obtain repeatability in the results, it is
substation. The method is obviously not a unique tool preferable to always use the same cables or cables of the
which replaces all other methods. However, when used same length and a wattmeter with good accuracy at a
jointly with other methods, it can lead to a more low power factor.
accurate diagnosis of the actual condition of transformer
windings.
6. ACKNOWLEDGMENTS
The following points summarize the method :
The authors gratefully acknowledge Jacques Aubin for
1. The FRSL method mainly consists in measuring his support in the development of the FRSL method,
stray losses over a certain range of frequencies, Claude Rajotte for his support and contribution to the
including the industrial frequency. The method covers method’s fine-tuning and application, and Claude
the diagnosis based on the conventional measurement of Jasmin and his team for automating the test procedure.
impedance variation, since this parameter is also
measured. 7. REFERENCES
2. The curve of the resistance representing stray losses
in the windings as a function of frequency is close to kf α [1] M.F. Lachman, Y.N. Shafir, Influence of Single-
where α is usually a value ranging from 1.4 to 1.8. Phase Excitation and Magnetizing Reactance on
Transformer Leakage Reactance Measurement
3. The transformer inductance is virtually not affected (IEEE Transactions on Power Delivery, Vol. 12,
by the variation in frequency, in the frequency range No. 4, Oct 1997, pp. 1538-1546).
used. [2] E.J. Rogers, L.E. Humbard, D.A. Gillies,
Instrumentation Techniques for Low Voltage
4. Regarding the detection of axial displacement of the
Impulse Testing of Power Transformers (IEEE
entire winding, tests have shown that the measurement
Transactions on Power Apparatus and Systems,
of variation of the stray losses is more accurate than
Vol. PAS-91, No. 3, May/June 1972, pp. 1281-
impedance variation measurement. The detection
1293).
threshold for both methods requires that the winding
displacement be the same as the spacing between [3] E.P. Dick, C.C. Erven, Transformer Diagnostic
windings. Testing by Frequency Response Analysis (IEEE
Transactions on Power Apparatus and Systems,
5. The measurement of stray losses has led to the Vol. PAS-97, No. 6, Nov/Dec 1978, pp. 2144-
detection of a short-circuit between parallel strands in a 2153).
winding. It also allows the verification of the quality of
the transposition on a winding made up of several [4] L. Bolduc, J. Aubin, Detection of Transformer
parallel strands. In general, the measurement is capable Winding Displacement by the FRSL Diagnosis
of detecting any fault or design flaw which has an effect Method (Rapport ACE RP 77-47, Mars 1981).
on stray losses. [5] N. Giao Trinh, J. Aubin, L. Bolduc, Evaluation
of the Dielectric and Short-Circuit Capabilities of
6. The FRSL diagnosis is not based on the absolute Naturally Aged Power Transformers (IEEE
value of the resistance as a function of frequency but Transactions on Power Apparatus and Systems,
rather on a comparison of curves. The comparison can Vol. PAS-103, No. 1, Jan 1984, pp. 109-120).
be established with a similar transformer or with a
previous test performed on the same transformer. In the [6] G. Olivier, C. Paun, Échauffement des
case of a three-phase transformer, the results can also be transformateurs en régime non sinusoïdal (Revue
interpreted based on a comparison between the three Internationale de Génie Électrique, Volume 1,
phases of the transformer. No. 2, 1998, pp. 203-224).
[7] IEEE Std. 519-1992, IEEE Recommended
7. For three-phase transformers, it is preferable to
Practices and Requirements for Harmonic
perform the test using a three-phase source so that the
Control in Electrical Power Systems, April 1993.
leakage flux under normal operating conditions can be
reproduced. If this is not possible, three successive tests
can be carried out with a single-phase source.

8. The presence of the tank causes an increase in stray


losses mainly in the windings. This increase is not
uniform over the three phases of a three-phase
transformer, but the two end phases usually show a
similar increase.

You might also like