Grid

Grid Voltage
3 SC Power
3 SC Current
X/R Ratio

400
10000
14.43
0

kV
MVAsc
kA

Step Up transformer
Primary Voltage
Secondary Voltage
Apparaent power
Primary FLA
Secondary FLA
%Z
Max. 3 Symm. Fault on 400 kV
Max. 3 Symm. Fault on 11 kV

400
11
125
180
6561
13
1.44
52.49

kV
kV
MVA
A
A
%
kA
kA

Step Down transformer


Primary Voltage
Secondary Voltage
Apparaent power
Primary FLA
Secondary FLA
%Z
Max. 3 Symm. Fault on 11 kV
Max. 3 Symm. Fault on 6 kV

11
6
18
945
1732
9
10.50
19.25

kV
kV
MVA
A
A
%
kA
kA

Generator Load
Nominal Voltage
Apparaent power
Real Power
PF
FLA
xd"
3 Phase Symm. Fault

11
125.00
100.00
0.80
6560.80
20.00
32.80

kV
MVA
MW
A
%
kA

Aux
Loss
Total
Export
Loss
Total

Grid
Grid Voltage
3 SC Power
3 SC Current
X/R Ratio

400
10000
14.43

kV
MVAsc
kA

Step Up transformer
Primary Voltage
Secondary Voltage
Apparaent power
Primary FLA
Secondary FLA
%Z
Max. 3 Symm. Fault on 400 kV
Max. 3 Symm. Fault on 11 kV

400
11
125
180
6561
12.5
1.44
52.49

kV
kV
MVA
A
A
%
kA
kA

Step Down transformer


Primary Voltage
Secondary Voltage
Apparaent power
Primary FLA
Secondary FLA
%Z
Max. 3 Symm. Fault on 11 kV
Max. 3 Symm. Fault on 6 kV

11
6
18
945
1732
9
10.50
19.25

kV
kV
MVA
A
A
%
kA
kA

11
125.00
100
0.8
6561
20
32.8

kV
MVA
MW

Generator
Nominal Voltage
Apparaent power
Real Power
PF
FLA
xd"
3 Phase Symm. Fault

15.00%
5.00%

100.00%
5.00%

18.75
0.94
19.69
125.00
6.25
131.25

A
%
kA

400 kV Bus
3 Symm. Fault

16.9

kA

11 kV Bus
3 Symm. Fault

93.8

kA

19.2

kA

6 kV Bus
3 Symm. Fault

MV Margin

1.1

kV
11
400

kA
32.8
0.90

kV
400
11
Final

kA
14.4
525
52.49

kV
11
6
Final

kA
93.8
172
19.25

Grid
Grid Voltage
3 SC Power
3 SC Current
X/R Ratio

400
40000
57.74
0

kV
MVAsc
kA

Step Up transformer
Primary Voltage
Secondary Voltage
Apparaent power
Primary FLA
Secondary FLA
%Z
Max. 3 Symm. Fault on 400 kV
Max. 3 Symm. Fault on 11 kV

400
11
125
180
6561
13
1.44
52.49

kV
kV
MVA
A
A
%
kA
kA

Step Down transformer


Primary Voltage
Secondary Voltage
Apparaent power
Primary FLA
Secondary FLA
%Z
Max. 3 Symm. Fault on 11 kV
Max. 3 Symm. Fault on 0.4 kV

11
0.4
9
472
12990
7.5
5.25
144.34

kV
kV
MVA
A
A
%
kA
kA

Generator Load
Nominal Voltage
Apparaent power
Real Power
PF
FLA
xd"
3 Phase Symm. Fault

11
58.82
50.00
0.85
3087.43
20.00
15.44

kV
MVA
MW
A
%
kA

Aux
Loss
Total
Export
Loss
Total

Grid
Grid Voltage
3 SC Power
3 SC Current
X/R Ratio

400
40000
57.74

kV
MVAsc
kA

Step Up transformer
Primary Voltage
Secondary Voltage
Apparaent power
Primary FLA
Secondary FLA
%Z
Max. 3 Symm. Fault on 400 kV
Max. 3 Symm. Fault on 11 kV

400
11
125
180
6561
12.5
1.44
52.49

kV
kV
MVA
A
A
%
kA
kA

Step Down transformer


Primary Voltage
Secondary Voltage
Apparaent power
Primary FLA
Secondary FLA
%Z
Max. 3 Symm. Fault on 11 kV
Max. 3 Symm. Fault on 0.4 kV

11
0.4
9
472
12990
9
5.25
144.34

kV
kV
MVA
A
A
%
kA
kA

11
58.82
50
0.85
3087
20
15.4

kV
MVA
MW

Generator
Nominal Voltage
Apparaent power
Real Power
PF
FLA
xd"
3 Phase Symm. Fault

15.00%
5.00%

100.00%
5.00%

8.82
0.44
9.26
58.82
2.94
61.76

A
%
kA

400 kV Bus
3 Symm. Fault

64.0

kA

11 kV Bus
3 Symm. Fault

74.7

kA

0.4 kV Bus
3 Symm. Fault

144.3

kA

MV Margin

1.1

kV
11
400

kA
15.4
0.42

kV
400
11
Final

kA
57.7
2099
52.49

kV
11
0.4
Final

kA
74.7
2055
144.34