130R0371 500v0profibus To FC302 Converter
130R0371 500v0profibus To FC302 Converter
Contents
Introduction ........................................................................................................................... 4
How to Install......................................................................................................................... 9
The MCA114 PROFIBUS converter Option ............................................................................ 9
How to Configure the System............................................................................................... 11
Parameter
Mapping List ....................................................................................................... 15
Troubleshooting ................................................................................................................... 58
Step-by-step troubleshooting.......................................................................................... 58
Index.................................................................................................................................... 59
Safety Note
The voltage of the frequency converter is dangerous whenever connected to mains. Incorrect
installation of the motor, frequency converter or fieldbus may cause damage to the equipment,
serious personal injury or death. Consequently, the instructions in this manual, as well as
national and local rules and safety regulations, must be complied with.
Safety Regulations
1. The frequency converter must be disconnected from mains if repair work is to be carried out. Check
that the mains supply has been disconnected and that the necessary time has passed before removing
motor and mains plugs.
2. The [OFF] key on the control panel of the frequency converter does not disconnect the equipment
from mains and is thus not to be used as a safety switch.
3. Correct protective earthing or grounding of the equipment must be established, the user must be
protected against supply voltage, and the motor must be protected against overload in accordance
with applicable national and local regulations.
4. The earth leakage currents are higher than 3.5 mA.
5. Protection against motor overload is not included in the factory setting. If this function is desired,
set par. 1-90 to data value ETR trip or data value ETR warning.
Note: The function is initialised at 1.16 x rated motor current and rated motor frequency. For the
North American market; the ETR functions provide class 20 motor overload protection in accordance
with NEC.
6. Do not remove the plugs for the motor and mains supply while the frequency converter is
connected to mains. Check that the mains supply has been disconnected and that the necessary time
has passed before removing motor and mains plugs.
7. Please note that the frequency converter has more voltage inputs than L1, L2 and L3, when load
sharing (linking of DC intermediate circuit) and external 24 V DC have been installed. Check that all
voltage inputs have been disconnected and that the necessary time has passed before commencing
repair work.
Warning against Unintended Start
1. The motor can be brought to a stop by means of digital commands, bus commands, references or a
local stop, while the frequency converter is connected to mains.
If personal safety considerations make it necessary to ensure that no unintended start occurs, these
stop functions are not sufficient.
2. While parameters are being changed, the motor may start. Consequently, the [OFF] key must
always be activated.
3. A motor that has been stopped may start if faults occur in the electronics of the frequency
converter, or if a temporary overload or a fault in the supply mains or the motor connection ceases.
Warning:
Touching the electrical parts may be fatal - even after the equipment has been disconnected
from mains.
Also make sure that other voltage inputs have been disconnected, such as external 24 V DC, load
sharing (linkage of DC intermediate circuit), as well as the motor connection for kinetic back up.
Please take note of discharge times and further safety guidelines from the section: Safety and
conformity, in the respective Design Guide (MG.33.Ax.yy).
MG.34.N1.02 VLT is a registered Danfoss trademark
Introduction
First time users can obtain the most essential information for quick installation and set-up in these
chapters:
Technical Overview
Constrains
How to Install
For more detailed information including the full range of set-up options and diagnosis tools please
refer to the chapters:
How to Configure the System
Parameter Mapping List
I n t r o d u c t i o n -
Technical Overview
This VLT 5000 to FC 302 converter (MCA114) is a option intended for replacing a VLT 5000 with a
FC 302 Automation Drive, in a PROFIBUS network.
With this PROFIBUS converter option the FC 302 will react as a VLT 5000 on the PROFIBUS network;
it means that it will in most cases not be necessary to change anything in the PLC programming or
configuration.
The FC 302 will identify itselfas a VLT 5000 drive on the PROFIBUS network, and a write command
to e.g. Ramp Up Time in VLT 5000 is automatically linked to the corresponding ramp up time
parameter in FC 302.
N.B.:
Some parameters in the VLT 5000 are not supported in the FC 302 and some FC 302 parameters
can not be accessed via the PROFIBUS converter Option MCA114.
Please refer to the section: Parameter Mapping List for more information.
If ad write request is attempted to a parameter selection not supported, the converter will discard the
value and issue a positive reply.
Only parameters and functions described in this manual are supported.
N.B.:
The replacement drive must match the power-size, or be bigger than the replaced VLT 5000
drive. Also observe that the choice of brake-chopper matches the replaced drive.
N.B.:
Please observe local rules and regulations when replacing drives in existing installations.
I n t r o d u c t i o n -
Constrains
Software versions
Hardware
5000
VLT
Function
FC 302
Terminal
Function
16
17
18
19
27
29
32
33
20
Digital input
Digital input
Digital input
Digital input
Digital input
Digital input
Digital input
Digital input
GND Digital input
X30/2*
X3/3*
18
19
27
29
32
33
20
Digital input
Digital input
Digital input
Digital input
Digital input
Digital input
Digital input
Digital input
GND Digital input
53
54
60
55
53
X30/11*
54
55
42
Analogue/Digital output
42
X30/6*
X30/7*
39
39
4-5
1-3
Relay
Relay
4-6
1-3
Relay
Relay
68
69
61
RS-485-P
RS-485-N
GND RS-485
68
69
61
RS-485-P
RS-485-N
GND RS-485
12
13
24 Volt out
24 Volt out
12
13
24 Volt out
24 Volt out
50
10 Volt out
50
10 Volt out
N.B:
I n t r o d u c t i o n -
Performance
After initialisation most parameters are set to match the factory settings of the VLT 5000
parameters.
To achieve compatible functionality with regards to setup change with running motor, FC 302
setups must be linked. This is done on the FC 302 using par. 0-12.
Hardware
Mechanical adaptation
130B0185
Compact, IP20
395
FC 300-related Literature
Literature no.
MG.33.Ax.yy
MG.33.Bx.yy
I n t r o d u c t i o n -
Abbreviations
AOC
CTW
EMC
I/O
LED
LSB
MAV
MOC
MSB
MRV
N/A
PCD
PCV
PLC
PNU
PPO
PPO1
PPO3
PU
REF
STW
Proper termination of the bus line is essential. A mismatch of impedance may result in reflections on
the line that will corrupt data transmission.
- The PROFIBUS Option Card has a suitable termination, activated by switch 1 located on the
PROFIBUS converter option. The switches must be on to terminate the bus. The factory setting is off.
- Nodes at the physical ends of each segment must be terminated.
N.B.:
Please pay special attention to the pin-numbering vs. colour coding on the PROFIBUS connector
if exchanging the PROFIBUS connector.
On FC 302 the PROFIBUS connectors are colour-coded, but not on the VLT 5000, which could have
lead to swapping of the bus wires.
Correct colour-coding:
62 = RxD/TxD Positive, Red cable
(PROFIBUS B)
63 = RxD/TxD Negative, Green cable
(PROFIBUS A)
Instructions:
Remove the LCD panel from the FC 300.
Remove the frame located beneath and discard.
Push the option into place. Two positions are possible, with cable terminal facing either up or
down. The cable up position is often most suitable when several frequency converters are
installed side by side in a rack, as this position permits shorter cable lengths.
Push the fieldbus option adaptor frame for the FC 300 into place.
Replace the LCD panel.
Attach cable.
Fasten the cable in place using cable holders.
N.B.:
After installing the MCA114 option, be aware of the following parameter settings:
Par. 8-02 Control Word Source = [3] Option A
10
All PROFIBUS stations that are connected to the same bus network must have a unique station
address.
Before a VLT 5000 can be replaced with a FC 302 with MCA114, only the station address needs to be
configured in the FC 302.
The PROFIBUS address of the FC 302 can be selected via:
Hardware switches
Parameter 9-18 Node address
Setting the PROFIBUS Address using the Hardware Switches
Using the hardware switches it is possible to select an address range from 0 to 125 (factory setting
127) according to the table below: ON = 1, OFF = 0
Switch
1
Address
+1
Examples:
1
1
35
1
82
0
2
+2
3
+4
0
1
1
0
0
0
VLT
5000
0
0
0
0
0
1
4
+8
5
6
7
+16 +32 +64
0
1
0
0
0
1
8
-
8
-
FC 302
7
6
5
+64 +32 +16
0
0
1
0
1
0
0
0
1
4
+8
3
+4
2
+2
1
+1
0
0
0
0
0
0
0
1
1
1
1
0
N.B.:
Switch off the power supply before changing the
hardware switches.
11
Node address
Setting the address via parameter 9-18 Node address or the PROFIBUS SSA-command is possible, if
the hardware switches are set to 126 or 127 (factory switch setting). The address change will come
into effect at the next power-up.
Commissioning
After copying the station address from the VLT 5000 to the FC 302, power must be cycled to the FC
302.
The master/PLC should now recognize FC 302, as a VLT 5000, and the NS LED on the MCA114 option
should now be solid green which indicates that communication between master and slave is
established.
If the NS LED flashes, the master/PLC has not recognized the FC 302.
For more information please refer to section: Troubleshooting.
12
LED label
NS
MS
Description
Network Status
Module Status (DP-V1 communication)
LED
Power On
Baud rate
search
Wait
Parameterizing
Wait
Configuration
Data Exchange
Description
Red:
Solid red
Green:
Flashing green
Green:
Flashing green
Green:
Red:
Green:
Red:
Green:
Solid green
Red:
Flashing red
Description
Off
Green:
Green:
Green:
Red:
Steady green
Flashing red
N.B.:
Please note: The LEDs are not compatible with the VLT 5000 PROFIBUS LEDs.
13
The following EMC precautions are recommended in order to achieve interference-free operation of the
PROFIBUS. Additional EMC information is available in the FC 300 series Design Guide.
N.B.:
Relevant national and local regulations, for example regarding protective earth connection,
must be observed.
The PROFIBUS communication cable must be kept away from motor and brake resistor cables to avoid
coupling of high frequency noise from one cable to the other. Normally a distance of 200 mm (8
inches) is sufficient, but maintaining the greatest possible distance between the cables is
recommended, especially where cables run in parallel over long distances. When crossing is
unavoidable, the PROFIBUS cable must cross motor and brake resistor cables at an angle of 90
degrees.
14
VLT
5000 Group 0
Parameter number
Parameter name
Data values
Parameter number
Parameter name
Data values
5000 series
FC 300 series
001
Language Select
[0] English
[1] Deutsch
[2] French
[3] Dansk
[4] Spanish
[5] Italian
001
Language
[0] English
[1] Deutsch
[2] French
[3] Dansk
[4] Spanish
[5] Italian
5000 series
FC 300 series
5000 series
FC 300 series
002
Local/remote control
[0] Remote
[1] Local with External Stop
[2] Local
Parameter number
Parameter name
Data values
003
Local reference
Parameter number
Parameter name
Data values
004
Active Set-up
[0] Factory Setup
[1] Setup 1
[2] Setup 2
[3] Setup 3
[4] Setup 4
[5] Multi Setup
5000 series
Not converted
Not converted
FC 300 series
010
Active Set-up
[0] Factory Setup
[1] Setup 1
[2] Setup 2
[3] Setup 3
[4] Setup 4
[9] Multi Setup
15
Parameter number
Parameter name
Data values
Parameter number
Parameter name
Parameter number
Parameter name
5000 series
FC 300 series
005
Set-up Selection,
Programming
[0] Factory Set-up
[1] Set-up 1
[2] Set-up 2
[3] Set-up 3
[4] Set-up 4
[5] Active Set-up
970
Edit Set-up
5000 series
FC 300 series
5000 series
FC 300 series
006
Setup Copy
0] Factory Set-up
1] Set-up 1
2] Set-up 2
3] Set-up 3
4] Set-up 4
9] Active Set-up
[
[
[
[
[
[
Not converted
007
LCP Copy
Not converted
LCP Copy
5000 series
FC 300 series
5000 series
FC 300 series
Parameter number
Parameter name
008
Display scaling of motor
frequency
Parameter number
Parameter number
Parameter number
Parameter number
Parameter name
Data values
009
010
011
012
Display line
[0] None
[1] Reference %
[2] Reference
[3] Feedback [Unit]
[4] Frequency [Hz]
[5] Frequency x scale
[6] Motor current [A]
[7] Torque [%]
[8] Power [kW]
[9] Power [HP]
[10] Output energy [kWh]
[11] Motor voltage [V]
[12] DC link voltage [V]
[13] Thermal load, motor
[%]
[14] Thermal load, VLT [%]
[15] Running hours [hours]
Not converted
023
020
021
022
Display line 2
[0] None
[1602] Reference %
[1601] Reference
[1652] Feedback [Unit]
[1613] Frequency [Hz]
[1609] Custom readout
[1614] Motor current [A]
[1622] Torque [%]
[1610] Power [kW]
[1611] Power [HP]
[1502] kWh counter [kWh]
[1612] Motor voltage [V]
[1630] DC link voltage [V]
[1618] Thermal load, motor
[%]
[1635] Inverter thermal [%]
[1501] Running hours
[hours]
[16] Digital input
[1660] Digital input
[17] Analogue input 53 [V]
[1662] Analogue input 53
[V]
[18] Analogue input 54 [V]
[1664] Analogue input 54
[V]
[19] Analogue input 60 [mA] [1662] Analogue input 53
[Unit]
[Unit]
16
[mA]
[1651] Pulse reference [Hz]
[1650] Ext. reference [%]
[1603] Status word [hex]
[1633] Brake effect/2 min
[kW]
[1632] Brake effect/sec
[kW]
[1634] Heat sink temp.
5000 series
FC 300 series
[
[
[
[
[
[
Parameter number
Parameter name
013
Local Ctrl./config
Parameter number
Parameter name
Data values
014
Local Stop key
[0] Disable
[1] Enable
041
Off (Stop) key
[0] Disable
[1] Enable
[2] Password
5000 series
FC 300 series
5000 series
FC 300 series
Parameter number
Parameter name
Data values
5000 series
015
Local Jogging
[0] Disable
[1] Enable
Parameter number
Parameter name
Data values
016
Local Reversing
[0] Disable
[1] Enable
Parameter number
Parameter name
Data values
017
Local Reset
[0] Disable
[1] Enable
Parameter number
Parameter name
018
Lock for data change
5000 series
5000 series
Not converted
FC 300 series
Not converted
Not converted
FC 300 series
043
Reset key on LCP
[0] Disable
[1] Enable
[2] Password
FC 300 series
061
Access to Main Menu
17
Data values
Parameter number
Parameter name
Data values
Parameter number
Parameter name
Data values
VLT
0 Not locked
1 Lock
0 Full access
1 LCP: Read only
[ ]
[ ]
[ ]
[ ]
5000 series
FC 300 series
5000 series
FC 300 series
019
004
Power-Up Mode
Operating state at power up
[0] Auto Restart, use saved
[0] Resume
ref.
[1] Forced stop, use saved
[1] Forced stop, use saved
ref.
ref.
[2] Forced stop, set ref = 0.
[2] Forced stop, set ref = 0
027
Warning readout line
[0] Warning in line 1/2
[1] Warning in line 3/4
Not converted
5000 Group 1
Parameter number
Parameter name
Data values
Parameter number
Parameter name
Data values
5000 series
FC 300 series
5000 series
FC 300 series
100
100, 101
Configuration
Configuration
[0] Speed control, open loop Par. 100 = [0] Speed open
loop
Par. 101 = [1] VVC+
[1] Speed control, closed
Par. 100 = [1] Speed
loop
closed loop
Par. 101 = [1] VVC+
[3] Process control, closed
Par. 100 = [3] Process
loop
Par. 101 = [1] VVC+
[4] Torque control, open
Par. 100 = [4] Torque open
loop
loop
Par. 101 = [1] VVC+
[5] Torque control, speed
Par. 100 = [2] Torque close
feedback
loop
Par. 101 = [3] Flux with
motor fb
101
Torque characteristic
[1] High constant torque
18
19
Parameter number
Parameter name
Data range
102
Motor Power
0.18 600 kW
Parameter number
Parameter name
Data range
103
Motor Voltage
200 600 Volt
Parameter number
Parameter name
Data range
104
Motor frequency
20 -1000 Hz
Parameter number
Parameter name
Data range
105
Motor Current
Power Unit dependable
Parameter number
Parameter name
Data range
106
Rated motor speed
100 60000
Parameter number
Parameter name
Data values
107
Automatic motor adaptation
[0] Adaptation off
[1] Adaptation on, Rs and Xs
[2] Adaptation on, RS
Parameter number
Parameter name
Data range
108
Stator resistor
Power Unit dependable
Parameter number
Parameter name
Data range
109
Stator reactance
Power Unit dependable
Parameter number
Parameter name
Data range
110
Motor magnetizing, 0 rpm
0 300 %
Parameter number
Parameter name
111
Min. frequency normal
magnetizing
5000 series
5000 series
5000 series
5000 series
5000 series
5000 series
5000 series
5000 series
5000 series
torque
Par. 1440 VT level = 85%
Par. 104 Over load =
Normal [1]
FC 300 series
120
Motor Power
0.09 3000 kW
FC 300 series
122
Motor Voltage
50 1000 Volt
FC 300 series
123
Motor frequency
20 -1000 Hz
FC 300 series
124
Motor Current
Power Unit dependable
FC 300 series
125
Motor nominal speed
10 60000
FC 300 series
129
Automatic motor adaptation
[0] Off
[1] Enable complete AMA
[2] Enable reduce AMA
FC 300 series
130
Stator resistance (Rs)
0.0140 140.0000
FC 300 series
135
Main reactance
1.0000 10000.0000
FC 300 series
150
Motor magnetizing at 0 rpm
0 300 %
FC 300 series
152
Min Speed Normal
Magnetising [Hz]
20
Data range
0.1 10.0 Hz
Parameter number
Parameter name
113
Load compensation at low
speed
0 300 %
Data range
Parameter number
Parameter name
5000 series
5000 series
0.3 10.0 Hz
FC 300 series
160
Low Speed Load
Compensation
0 300 %
FC 300 series
Data range
114
Load compensation at high
speed
0 300 %
Parameter number
Parameter name
Data range
115
Slip Compensation
-500 - 500%
Parameter number
Parameter name
Data range
116
Slip Compensation Time
constant
0.05 1.00 sec
Parameter number
Parameter name
Data range
117
Resonance dampening
0 - 500%
Parameter number
Parameter name
118
Resonance dampening time
constant
5 50 msec
165
Resonance Dampening Time
Constant
5 50 msec
5000 series
FC 300 series
Data range
5000 series
5000 series
5000 series
5000 series
161
High Speed Load
Compensation
0 300 %
FC 300 series
162
Slip Compensation
-500 - 500%
FC 300 series
163
Slip Compensation Time
constant
0.05 5.00 sec
FC 300 series
164
Resonance Dampening
0 - 500%
FC 300 series
Parameter number
Parameter name
119
High starting torque
Parameter number
Parameter name
Data range
120
Start delay
0.0 10.0 sec
171
Start delay
0.0 10.0 sec
5000 series
FC 300 series
5000 series
Not converted
FC 300 series
21
Parameter number
Parameter name
Data values
121
Start function
[0] DC hold in start delay
time
[1] DC brake in start delay
time
[2] Coasting in start delay
time
[3] Start frequency/voltage
clockwise
[4] Start frequency/voltage
in reference direction
[5] VVC+ clockwise
5000 series
Parameter number
Parameter name
Data values
122
Function at stop
[0] Coasting
[1] DC hold
[2] Motor check
[3] Pre-magnetizing
Parameter number
Parameter name
Data range
123
Min frequency for function
at stop
0.0 10.0 Hz
Parameter number
Parameter name
Data range
124
DC holding current
0 - 100 %
Parameter number
Parameter name
Data range
125
DC braking current
0 - 100 %
Parameter number
Parameter name
Data range
126
DC braking time
0.0 60.0 sec
Parameter number
Parameter name
Data range
127
DC brake cut-in frequency
0.0 (Off) fmax (par. 202)
5000 series
5000 series
5000 series
5000 series
5000 series
172
Start function
[0] DC hold/delay time
1 DC Brake/delay time
[ ]
2 Coast/delay time
[ ]
180
Function at stop
[0] Coast
[1] DC hold
[2] Motor check
[3] Pre-magnetizing
FC 300 series
182
Min Speed for Function at
Stop [Hz]
0.0 20.0 Hz
FC 300 series
200
DC Hold Current
0 - 160 % (motor
depending)
FC 300 series
201
DC brake current
0 160 % P.U depending
FC 300 series
202
DC Braking Time
0.0 60.0 sec
FC 300 series
204
DC Brake Cut In Speed [Hz]
0.0 (Off) fmax (par. 414)
22
5000 series
FC 300 series
Parameter number
Parameter name
Data values
128
Motor thermal protection
[0] No protection
[1] Thermistor warning
[2] Thermistor trip
[3] ETR warning 1
[4] ETR trip 1
[5] ETR warning 2
[6] ETR trip 2
[7] ETR warning 3
[8] ETR trip 3
[9] ETR warning 4
[10] ETR trip 4
Parameter number
Parameter name
Data values
129
External motor fan
[0] No
[1] Yes
Parameter number
Parameter name
Data range
130
Start frequency
0.0 10.0 Hz
175
Start Speed [Hz]
0.0 500 Hz P.U depending
5000 series
FC 300 series
5000 series
FC 300 series
Parameter number
Parameter name
Parameter number
Parameter name
5000 series
5000 series
131
Initial voltage
145
Minimum DC brake time
190
Motor thermal protection
[0] No protection
[1] Thermistor warning
[2] Thermistor trip
[3] ETR warning 1
[4] ETR trip 1
[5] ETR warning 2
[6] ETR trip 2
[7] ETR warning 3
[8] ETR trip 3
[9] ETR warning 4
[10] ETR trip 4
FC 300 series
191
Motor External Fan
[0] No
[1] Yes
FC 300 series
Not converted
Not converted
23
VLT
5000 Group 2
Parameter number
Parameter name
Data values
5000 series
200
Output Frequency
Range/Direction
[0] Only clockwise, 0 132
Hz
[1] Both directions, 0 132
Hz
[2] Only clockwise, 0 1000
Hz
[3] Both directions, 0
1000 Hz
[4] Only counter clockwise,
0 132 Hz
[5] Only counter clockwise,
0 1000 Hz
5000 series
FC 300 series
410
Motor Speed Direction
0 Clockwise
[ ]
2 Both directions
[ ]
0 Clockwise
[ ]
2 Both directions
[ ]
Parameter number
Parameter name
Data range
201
Output frequency low limit
0.0 par. 202 Fmax
Parameter number
Parameter name
Data range
202
Output frequency high limit
0.0 132/1000 Hz
Parameter number
Parameter name
Data values
203
Reference/feedback area
[0] Min Max
[1] - Max - +Max
300
Reference Range
[0] Min Max
[1] - Max - +Max
5000 series
FC 300 series
Parameter number
Parameter name
Data range
Parameter number
Parameter name
Data range
5000 series
5000 series
412
Motor speed Low Limit, Hz
0 par. 414 Fmax [Hz]
FC 300 series
414, 419
Motor speed High Limit, Hz
0 1000 Hz
FC 300 series
204
Minimum reference
-100,000.000 par. 205
Ref max
5000 series
FC 300 series
205
Maximum reference
Par. 204 Refmin
100,000.000
24
Parameter number
Parameter name
Data Values:
5000 series
206
Ramp Type
[0] Linear
[ ]
[ ]
[ ]
4 Sin2 filter
[ ]
Parameter number
Parameter name
Data range
5000 series
207
Ramp up Time 1
0.05 3600.00 sec
FC 300 series
341
Ramp up Time 1
0.01 3600.00 sec
25
5000 series
FC 300 series
Parameter number
Parameter name
Data range
208
Ramp down Time 1
0.05 3600.00 sec
Parameter number
Parameter name
Data range
209
Ramp up Time 2
0.05 3600.00 sec
Parameter number
Parameter name
Data range
210
Ramp down Time 2
0.05 3600.00 sec
Parameter number
Parameter name
Data range
211
Jog ramp time
0.05 3600.00 sec
Parameter number
Parameter name
Data range
212
Quick stop ramp time
0.05 3600.00 sec
Parameter number
Parameter name
Data range
213
Jog Frequency
0.0 par. 202
311
Jog speed [Hz]
0.0 par. 414
5000 series
FC 300 series
Parameter number
Parameter name
Data Values:
5000 series
5000 series
5000 series
5000 series
5000 series
342
Ramp down Time 1
0.01 3600.00 sec
FC 300 series
351
Ramp up Time 2
0.01 3600.00 sec
FC 300 series
352
Ramp down Time 2
0.01 3600.00 sec
FC 300 series
380
Jog ramp time
0.01 3600.00 sec
FC 300 series
381
Quick stop ramp time
0.01 3600.00 sec
FC 300 series
214
304
Reference function
Reference function
[0] Sum
[0] Sum
[1] Relative
See comment below*
[2] External/Preset
[1] External/preset
*= Relative reference is added to the MRV from PROFIBUS.
5000 series
Parameter number
Parameter name
Data range
215
Preset Reference 1
-100.00 100.00 %
Parameter number
Parameter name
Data range
216
Preset Reference 2
-100.00 100.00 %
Parameter number
Parameter name
Data range
217
Preset Reference 3
-100.00 100.00 %
Parameter number
Parameter name
218
Preset Reference 4
5000 series
5000 series
5000 series
FC 300 series
310 index 0
Preset Reference 1..8
-100.00 100.00 %
FC 300 series
310 index 1
Preset Reference 1..8
-100.00 100.00 %
FC 300 series
310 index 2
Preset Reference 1..8
-100.00 100.00 %
FC 300 series
310 index 3
Preset Reference 1..8
26
Data range
-100,00 - 100,00 %
Parameter number
Parameter name
Data range
219
Catch up/slow down value
0.00 100 %
312
Catch up/slow down value
0.00 100 %
Parameter number
Parameter name
Data range
221
416
Torque limit for motor mode Torque limit for motor mode
0.0 Max. torque %
0.0 Max. torque %
5000 series
FC 300 series
Parameter number
Parameter name
Data range
222
Torque limit for generating
mode
0.0 Max. torque %
417
Torque limit for generating
mode
0.0 Max. torque %
Parameter number
Parameter name
Data range
223
450
Warning: Current Low
Warning: Low Current
0.0 par. 224 Current High 0.00 par. 451
5000 series
FC 300 series
Parameter number
Parameter name
Data range
224
Warning: Current High
Power Unit dependable
Parameter number
Parameter name
Data range
225
Warning Low Frequency
0,0 par. 226
Parameter number
Parameter name
Data range
226
Warning High Frequency
par. 225 par. 202
Parameter number
Parameter name
Data range
227
Warning Low Feedback
-100,000.000 par. 228
Parameter number
Parameter name
Data range
228
Warning High Feedback
par. 227 100,000.000
Parameter number
Parameter name
229
Frequency bypass,
bandwidth
0 - 100 %
Data range
5000 series
5000 series
5000 series
5000 series
5000 series
5000 series
5000 series
5000 series
-100,00 - 100,00 %
FC 300 series
FC 300 series
FC 300 series
451
Warning: Current High
Power Unit dependable
FC 300 series
452
Warning: Low Speed
0,0 Par. 453
FC 300 series
453
Warning Speed High
Par. 452 par. 413
FC 300 series
456
Warning: Feedback Low
-999,999.999 par. 457
FC 300 series
457
Warning High Feedback
Par. 456 999,999.999
FC 300 series
Converted to EEprom
27
5000 series
Parameter number
Parameter name
Data range
230
Frequency Bypass 1
0 par. 200
Parameter number
Parameter name
Data range
231
Frequency Bypass 2
0 par. 200
Parameter number
Parameter name
Data range
232
Frequency Bypass 3
0 par. 200
Parameter number
Parameter name
Data range
233
Frequency Bypass 4
0 par. 200
Parameter number
Parameter name
234
Motor phase monitor
Data Values:
VLT
5000 series
5000 series
5000 series
5000 series
0 Enable
1 Disable
[ ]
[ ]
FC 300 series
458
Missing motor phase
function
[2] Trip 1000 ms
[0] Disable
5000 Group 3
Parameter number
Parameter name
Data values
Comments
5000 series
300
Terminal 16, input
FC 300 series
28
5000 series
Parameter number
Parameter name
301
Terminal 17, input
Data values
[0]
Comments
FC 300 series
No function
[1] Reset
[2] Stop inverse
[3] Only start anticlockwise, on
[4] Jog
[14] Jog
[5] Preset reference, on
[15] Preset reference, on
[6] Preset reference, msb
[17] Preset reference bit 1
[7] Freeze reference
[19] Freeze reference
[8] Freeze output
[20] Freeze output
[9] Speed down
[22] Speed down
[10] Choice of setup, msb [24] Setup select bit 1
[11] Slow down
[29] Slow down
[12] Ramp 2
[34] Ramp bit 0
[13] Mains failure inverted Not supported
[23] Pulse reference
[32] Pulse input
[24] Safety interlock
Not supported
[29] Data change lock
Not supported
FC 300 doesnt have a digital input 17, so this is linked to
par. 516 Terminal X30/3 MCB 101
5000 series
Parameter number
Parameter name
Data values
302
Terminal 18, input
[0] No function
[1] Start
[2] Latched start
[3] Only start clockwise, on
Parameter number
Parameter name
Data values
303
Terminal 19, input
[0] No function
[1] Reversing
[2] Start reversing
[3] Only start anticlockwise, on
Parameter number
Parameter name
Data values
304
Terminal 27, input
[0] Coasting stop, inverse
[1] Reset and Coasting
stop, inv.
[2] Quick-stop, inverse
[3] DC-braking, inverse
[4] Stop inverse
5000 series
5000 series
FC 300 series
510
Terminal 18 Digital input
[0] No operation
[8] Start
[9] Latched start
[12] Enable start forward
FC 300 series
511
Terminal 19 Digital input
[0] No operation
[10] Reversing
[11] Start reversing
[13] Enable start reverse
FC 300 series
512
Terminal 27 Digital input
[2] Coast inverse
[3] Coast and reset inv
[4]
29
Parameter number
Parameter name
Data values
Parameter number
Parameter name
Data values
Parameter number
Parameter name
Data values
5000 series
305
Terminal 29, input
[0] No function
[1] Reset
[2] Stop inverse
[3] Only start clockwise, on
[4] Only start anticlockwise, on
[5] Jog
[6] Preset reference, on
[7] Preset reference, lsb
[8] Preset reference, msb
[9] Freeze reference
[10] Freeze output
[11] Speed up
[12] Speed down
[13] Choice of Setup, lsb
[14] Choice of Setup, msb
[15] Catch up
[16] Slow down
[17] Ramp 2
[18] Mains failure inverted
[28] Pulse reference
[29] Data change lock
5000 series
306
Terminal 32, input
[0] No function
[1] Reset
[2] Stop inverse
[3] Only start clockwise, on
[4] Jog
[5] Preset reference, on
[6] Preset reference, lsb
[7] Freeze reference
[8] Freeze output
[9] Speed up
[10] Choice of Setup, lsb
[11] Choice of Setup, msb /
Speed up
[12] Catch up
[13] Ramp 2
[14] Mains failure inverted
[24] Encoder input 2A
[29] Data change lock
5000 series
307
Terminal 33, input
[0] No function
[1] Reset
[2] Stop inverse
FC 300 series
513
Terminal 29 Digital input
[0] No operation
[1] Reset
[6] Stop inverse
[12] Enable start forward
[13] Enable start reverse
[14] Jog
[15] Preset reference, on
[16] Preset reference bit 0
[17] Preset reference bit 1
[19] Freeze reference
[20] Freeze output
[21] Speed up
[22] Slow down
[23] Setup select bit 0
[24] Setup select bit 1
[28] Catch up
[29] Slow down
[34] Ramp bit 0
Not supported
[32] Pulse input
Not supported
FC 300 series
514
Terminal 32 Digital input
[0] No operation
[1] Reset
[6] Stop inverse
[12] Enable start forward
[14] Jog
[15] Preset reference, on
[16] Preset reference bit 0
[19] Freeze reference
[20] Freeze output
[21] Speed up
[23] Setup select bit 0
Not supported
[28] Catch up
[34] Ramp bit 0
Not supported
[0] No operation
Not supported
FC 300 series
515
Terminal 33 Digital input
[0] No operation
[1] Reset
[6] Stop inverse
30
Parameter number
Parameter name
308
Terminal 53, Analogue
Input Voltage
Data values
[0] No Operation
[1]
Reference
[2] Feedback signal
[3]
Torque limit
[4] Thermistor
5000 series
Parameter number
Parameter name
Data range
309
Terminal 53, min. scaling
0 10.0 Volt
Parameter number
Parameter name
Data range
310
Terminal 53, max. scaling
0 10.0 Volt
5000 series
1)
FC 300 series
610
Terminal 53 Low Voltage
-10.00 Par. 611
FC 300 series
611
Terminal 53 High Voltage
Par. 610 - 10.00 Volt
31
Parameter number
Parameter name
Data values
5000 series
311
Terminal 54, Analogue
Input Voltage
Parameter number
Parameter name
Data range
312
Terminal 54, min. scaling
0 10.0 Volt
Parameter number
Parameter name
Data range
313
Terminal 54, max. scaling
0 10.0 Volt
5000 series
5000 series
Parameter number
Parameter name
314
Terminal 60, Analogue
Input current
Data values
[0] No Operation
[1]
Reference
Comments
FC 300 series
Torque limit
FC 300 series
620
Terminal 54 Low Voltage
-10.00 Par. 621
FC 300 series
621
Terminal 54 High Voltage
Par. 620 - 10.00 Volt
FC 300 series
32
5000 series
FC 300 series
Parameter number
Parameter name
Data range
315
Terminal 60, min. scaling
0.0 20.0 mA
Parameter number
Parameter name
Data range
316
Terminal 60, max. scaling
0.0 20.0 mA
Parameter number
Parameter name
Data range
317
Time Out
0 99 sec
600
Live zero Time Out
0 99 s
Parameter number
Parameter name
Data values
318
601
Function after time out
Function after Time Out
[0] Off
[0] Off
[1] Freeze output frequency [1] Freeze Output
Frequency
[2] Stop
[2] Stop
[3] Jog
[3] Jogging
[4] Max Speed, p202
[4] Max Speed
[5] Stop and trip
[5] Stop and trip
5000 series
FC 300 series
Parameter number
319
Parameter number
321
Parameter name
Data values
5000 series
5000 series
5000 series
622
Terminal 54 Low Current
0.00 Par. 623
FC 300 series
623
Terminal 54 High Current
Par. 622 - 20.00 mA
FC 300 series
FC 300 series
33
[9] Alarm
[10] Alarm or Warning
1)
1)
1)
1)
1)
34
32000 p
[42] Ref min Ref max =>
0 20 mA
[43] Ref min Ref max =>
4 20 mA
[44] Ref min Ref max =>
0 - 32000 p
[45] FB min FB max => 0
20 mA
[46] FB min FB max => 4
20 mA
[47] FB min FB max => 0
- 32000 p
[48] 0 I max => 0 20
mA
[49] 0 I max => 4 20
mA
[50] 0 I max => 0
32000 p
[51] 0 T lim => 0 20
mA
[52] 0 T lim => 4 20
mA
[53] 0 T lim => 0 32000
p
[54] 0 T nom => 0 20
mA
[55] 0 T nom => 4 20
mA
[56] 0 T nom => 0
32000 p
[57] 0 P nom => 0 20
mA
[58] 0 P nom => 4 20
mA
[59] 0 P nom => 0
32000 p
[60] 0 SyncRPM => 0
20 mA
[61] 0 SyncRPM => 4
20 mA
[62] 0 SyncRPM => 0
32000 p
[63] RPM at F max => 0
20 mA
[64] RPM at F max => 4
20 mA
[65] RPM at F max => 0
32000 p
freq. 0 32000p
Par. 568 = 32000
Par. 650 = [101] Reference
0 -20 mA
Par. 650 = [131] Reference
4 -20 mA
Par. 566 = [101] Reference
0 32000p
Par. 568 = 32000
Par. 650 = [102] Feedback
0 -20 mA
Par. 650 = [132] Feedback
4 -20 mA
Par. 566 = [102] Feedback
0 32000p
Par. 568 = 32000
Par. 650 = [103] Motor
current 0 -20 mA
Par. 650 = [133] Motor
current 4 -20 mA
Par. 566 = [103] Motor
current 0 - 32000p
Par. 568 = 32000
Par. 650 = [104] Torque
related to limit 0 - 20 mA
Par. 650 = [134] Torque
related to limit 4 - 20 mA
Par. 566 = [104] Torque
related to limit 0 32000p
Par. 568 = 32000
Par. 650 = [105] Torque
related to norm 0 - 20 mA
Par. 650 = [135] Torque
related to norm 4 - 20 mA
Par. 566 = [105] Torque
related to norm 0 32000p
Par. 568 = 32000
Par. 650 = [106] Power
related to norm 0 - 20 mA
Par. 650 = [136] Power
related to norm 4 - 20 mA
Par. 566 = [106] Power
related to norm 0 32000p
Par. 568 = 32000
Not supported
Not supported
Not supported
Par. 650 = [107] Speed
related to norm 0 - 20 mA
Par. 650 = [137] Speed
related to norm 4 - 20 mA
Par. 566 = [107] Speed
related to norm 0 32000p
Par. 568 = 32000
35
Parameter number
Parameter name
Data range
Parameter number
Parameter name
Data range
Parameter number
Parameter number
Parameter name
Data values
5000 series
320
Terminal 42 Output, pulse
scaling
1 32000 Hz
5000 series
FC 300 series
568
Pulse Output Max Freq
#X30/6 (MCB 101)
0 32000 Hz
FC 300 series
322
Terminal 45 Output, pulse
scaling
1 32000 Hz
568
Pulse Output Max Freq
#X30/6 (MCB 101)
0 32000 Hz
5000 series
FC 300 series
323
326
01 Relay
04 Relay
[0] No function
540 Index 0
540 Index 1
Relay 1
Relay 2
Par. 540.0 = [0] No
operation
[1] Control Ready
Par. 540.0 = [1] Control
Ready
[2] Ready signal
Par. 540.0 = [2] Drive ready
[3] Ready - Remote Control
Par. 540.0 = [3] Drive
rdy/rem ctrl
[4] Enabled, no warning
Par. 540.0 = [4] Enable /
no warning
[5] Running
Par. 540.0 = [5] VLT
running
[6] Running, no Warning
Par. 540.0 = [6] Running /
no warning
[7] Running within range,
Par. 540.0 = [7] Run in
no warning
range/no warn
[8] Run at reference, no
Par. 540.0 = [8] Run on
Warning
ref/no warn
[9] Alarm
Par. 540.0 = [9] Alarm
[10] Alarm or Warning
Par. 540.0 = [10] Alarm or
Warning
[11] Torque limit
Par. 540.0 = [11] At torque
limit
[12] Out of current range
Par. 540.0 = [12] Out of
current range
[13] Above I low
Par. 540.0 = [13] Below
current, low
[14] Under I high
Par. 540.0 = [14] Above
current, high
[15] Out of frequency range Par. 540.0 = [15] Out of
speed range
[16] Over f low
Par. 540.0 = [16] Below
speed low
[17] Under f high
Par. 540.0 = [17] Above
speed high
[18] Out of feedback range Par. 540.0 = [18] Out of
feedb. Range
[19] Over feedback low
Par. 540.0 = [16] Below
1)
1)
1)
1)
36
feedback low
Par. 540.0 = [17] Above
feedback high
[21] Thermal warning
Par. 540.0 = [21] Thermal
warning
[22] Ready, no thermal
Par. 540.0 = [12] Ready,no
warning
thermal W
[23] Ready - remote control Par. 540.0 = [23] Remote,
- no thermal warning
ready, no TW
[24] Ready mains voltage Par. 540.0 = [24] Ready,
within range
Voltage OK
[25] Reversing
Par. 540.0 = [25] Reverse
[26] Bus OK
Par. 540.0 = [26] Bus OK
[27] Torque limit and stop Par. 540.0 = [27] Torque
limit & stop
[28] Brake, no brake
Par. 540.0 = [28] Brake, no
warning
brake warning
[29] Brake ready, no fault Par. 540.0 = [29] Brake
ready, no fault
[30] Brake fault
Par. 540.0 = [30] Brake
fault (IGBT)
[31] Relay 123
Par. 540.0 = [31] Relay
123
[32] Mechanical brake
Par. 540.0 = [32] Mech
control
brake ctrl
[33] Control word bit 11/12 Par. 540.0 = [36] Control
word bit 11
Par. 540.1 = [37] Control
word bit 12
[34] Extended mechanical Par. 540.0 = [32] Mech
brake control
brake ctrl
[35] Safety Interlock
Not supported
1) = Note that the function is reversed in FC302 compared to VLT 5000
1)
1)
5000 series
FC 300 series
Parameter number
Parameter name
Data range
324
Relay 01, ON delay
0.00 600.00 sec
Parameter number
Parameter name
Data range
325
Relay 01, OFF delay
0.00 600.00 sec
Parameter number
Parameter name
Data range
327
Pulse reference, max. freq.
100 65000 Hz
Parameter number
Parameter name
Data range
328
Pulse feedback, max. freq.
100 65000 Hz
558
Term. 33 High Frequency
0 110000 Hz
Parameter number
Parameter name
329
570
Encoder feedback pulse/rev. Term 32/33 Pulses per
5000 series
FC 300 series
5000 series
5000 series
5000 series
541 index 0
On Delay, Relay
0.01 600.00 sec
FC 300 series
542 index 0
Off Delay, Relay
0.01 600.00 sec
FC 300 series
551
Term. 29 High Frequency
0 110000 Hz
FC 300 series
37
VLT
Data range
1 4096 pulses
Revolution
1 4096 pulses
5000 series
FC 300 series
Parameter number
Parameter name
330
Freeze ref. /output function
Parameter number
Parameter name
345
Encoder loss timeout
Data range
432
Motor Feedback Loss
Timeout
0.00 60.00 sec
Parameter number
Parameter name
346
Encoder loss function
5000 series
FC 300 series
5000 series
FC 300 series
Data values
Parameter number
Parameter name
Data range
Parameter number
Parameter name
5000 series
Not converted
FC 300 series
430
Motor Feedback Loss
Function
[0] Off
[0] Disable
[1] Freeze output frequency [4] Freeze output frequency
[3] Jog
[3] Jog
[4] Max speed
[5] Max speed
[5] Stop and trip
[11] Stop and trip
[7] Select setup 4
[10] Select setup 4
357
651
Term. 42, Output min. scale Terminal 42 Output Min
Scale
0 100%
0 200%
5000 series
FC 300 series
Data range
358
Term. 42, Output max.
scale
0 500%
652
Terminal 42 Output Max
Scale
0 200%
Parameter number
Parameter name
Data range
359
661
Term. 45, Output min. scale Terminal X30/8 Min. Scale
0 100%
0 200%
5000 series
FC 300 series
Parameter number
Parameter name
Data range
360
Term. 45, Output max.
scale
0 500%
Parameter number
Parameter name
Data range
361
Encoder loss threshold
0 600%
5000 series
5000 series
FC 300 series
662
Terminal X30/8 Max. Scale
0 200%
FC 300 series
431
Motor Feedback Speed Error
1 600 rpm
38
VLT
5000 Group 4
Parameter number
Parameter name
Data values
5000 series
400
Brake function/over voltage
cont.
[0] Off
[1] Resistor brake
[2] Over voltage control
[3] Over voltage control and
stop
5000 series
Parameter number
Parameter name
Data range
401
Brake resistor, ohm
Power unit dependable
Parameter number
Parameter name
Data range
402
Brake power limit, kW
Depends on unit
Parameter number
Parameter name
403
Power monitoring
Data values
[0]
[1]
Parameter number
Parameter name
Data values
404
Brake check
[0] Off
[1] Warning
[2] Trip
Parameter number
Parameter name
Data values
405
Reset
[0] Manual reset
[1] Automatic reset x 1
[2] Automatic reset x 2
[3] Automatic reset x 3
[4] Automatic reset x 4
[5] Automatic reset x 5
[6] Automatic reset x 6
[7] Automatic reset x 7
[8] Automatic reset x 8
[9] Automatic reset x 9
[10] Automatic reset x 10
5000 series
5000 series
Off
Warning
[2] Trip
5000 series
5000 series
FC 300 series
210, 217
Brake Function, Over
voltage con
[0] Off
[1] Resistor brake
Par. 217 = [1] Enable
FC 300 series
3081
Brake resistor, ohm
Power unit dependable
FC 300 series
212
Brake Power Limit (kW)
Depends on unit
FC 300 series
213
Brake Function, Over
voltage con
[0] Off
[1] Warning
[2] Trip
FC 300 series
215
Brake check
[0] Off
[1] Warning
[2] Trip
FC 300 series
14-20
Reset Mode
[0] Off
[1] Automatic reset x 1
[2] Automatic reset x 2
[3] Automatic reset x 3
[4] Automatic reset x 4
[5] Automatic reset x 5
[6] Automatic reset x 6
[7] Automatic reset x 7
[8] Automatic reset x 8
[9] Automatic reset x 9
[10] Automatic reset x 10
39
5000 series
FC 300 series
Parameter number
Parameter name
Data range
406
Automatic restart time
0 10 sec
Parameter number
Parameter name
Data values
407
Mains failure
[0] No function
[1] Controlled ramp down
[2] Controlled ramp down
and trip
[3] Coast
[4] Kinetic back-up
[5] Controlled alarm
suppression
14-10
Mains Failure
[0] No function
[1] Controlled ramp down
[2] Controlled ramp down
and trip
[3] Coast
[4] Kinetic back-up
[5] Kinetic back-up, trip
5000 series
FC 300 series
5000 series
14-21
Automatic Restart Time
0 600 sec
FC 300 series
Parameter number
Parameter name
408
Quick discharge
Parameter number
Parameter name
Data range
409
Trip delay torque
0 60 sec (60=OFF)
Parameter number
Parameter name
Data range
410
Trip delay inverter
0 35 sec
Parameter number
Parameter name
Parameter type
Data range
411
Switching frequency
Unsigned 16 (6)
1.5 14 kHz
14-01
Switching Frequency
Unsigned 8 (5)
< 2.3 => 2.0 kHz [2]
2.3 > 2.7 => 2.5 kHz [3]
2.8 > 3.2 => 3.0 kHz [4]
3.3 > 3.7 => 3.5 kHz [5]
3.8 > 4.5 => 4.0 kHz [6]
4.6 > 5.5 => 5.0 kHz [7]
5.6 > 6.5 => 6.0 kHz [8]
6.6 > 7.5 => 7.0 kHz [9]
7.6 > 9.0 => 8.0 kHz [10]
9.1 > => 10.0 kHz [11]
5000 series
FC 300 series
Parameter number
Parameter name
5000 series
5000 series
5000 series
412
Output frequency
dependent switching
frequency
Not converted
FC 300 series
14-25
Trip delay torque
0 60 sec (60=OFF)
FC 300 series
14-26
Trip Delay at Inverter Fault
0 35 sec
FC 300 series
Not converted
40
Parameter number
Parameter name
Data values
Factory setting
Parameter number
Parameter name
5000 series
FC 300 series
413
Over modulation function
[0] Off
[1] On
[0] Off
14-03
Over modulation function
[0] Off
[1] On
[1] On
5000 series
FC 300 series
5000 series
FC 300 series
414
Minimum feedback
Parameter number
Parameter name
415
Maximum feedback
Parameter number
Parameter name
Data Value
416
Feedback Unit
[0] None
[1] %
[2] PPM
[3] rpm
[4] bar
[5] Cycle/min
[6] Pulse/s
[7] Unit s/s
[8] Unit s/min
[9] Unit s/h
[10] C
[11] Pa
[12] l/s
[13] m3/s
[14] l/min
[15] m3/min
[16] l/h
[17] m3/h
[18] kg/s
[19] kg/min
[20] kg/h
[21] t/min
[22] t/h
[23] m
[24] Nm
[25] m/s
[26] m/min
[27] F
[28] in wg
[29] gal/s
[30] ft3/s
[31] gal/min
5000 series
Not converted
Not converted
FC 300 series
301
Reference/feedback Unit
[0] None
[1] %
[5] PPM
[2] RPM
[71] bar
Not supported
[12] Pulse/s
Not supported
Not supported
Not supported
[60] C
[72] Pa
[20] l/s
[23] m3/s
[21] l/min
[24] m3/min
[22] l/h
[25] m3/h
[30] kg/s
[31] kg/min
[32] kg/h
[33] t/min
[34] t/h
[45] m
[4] Nm
[40] m/s
[41] m/min
[160] F
[172] in wg
[121] gal/s
[125] ft3/s
[122] gal/min
41
32] ft3/min
33] gal/h
34] ft3/h
35] lb/s
36] lb/min
37] lb/h
38] lb ft
39] ft/s
40] ft/min
126] ft3/min
123] gal/h
127] ft3/h
130] lb/s
131] lb/min
132] lb/h
150] lb ft
140] ft/s
141] ft/min
[
[
[
[
[
[
[
[
[
[
[
[
[
[
[
[
[
[
5000 series
FC 300 series
Parameter number
Parameter name
Data range
417
702
Speed PID proportional gain Speed PID proportional gain
0.000 0.150
0.000 1.000
Parameter number
Parameter name
Data range
418
Speed PID integral time
2.00 999.99
Parameter number
Parameter name
419
Speed PID differential time
Data range
0.00 200.00
Parameter number
Parameter name
Data range
420
Speed PID D-gain limit
5.0 50.0
Parameter number
Parameter name
421
Speed PID low-pass filter
Data range
5.0 200.0 ms
Parameter number
Parameter name
Data range
422
U0 voltage at 0 Hz
0.0 par. 103
Parameter number
Parameter name
Data range
423
U1 voltage
0.0 par. 103
Parameter number
Parameter name
Data range
424
F1 frequency
0.0 par. 104
Parameter number
Parameter name
Data range
425
U2 voltage
0.0 par. 103
5000 series
5000 series
5000 series
5000 series
5000 series
5000 series
5000 series
5000 series
FC 300 series
703
Speed PID Integral Time
2.00 20000.00
FC 300 series
704
Speed PID Differentiation
Time
0.00 200.00
FC 300 series
705
Speed PID Diff. Gain Limit
1.0 20.0
FC 300 series
706
Speed PID Lowpass Filter
Time
1.0 100.0
FC 300 series
155 index 0
U0 voltage
0.0 1000.0 V
FC 300 series
155 index 1
U1 voltage
0.0 1000.0 V
FC 300 series
156 index 1
F1 frequency
0.0 1000.0 Hz
FC 300 series
155 index 2
U2 voltage
0.0 1000.0 V
42
5000 series
Parameter number
Parameter name
Data range
426
F2 frequency
0.0 par. 104
Parameter number
Parameter name
Data range
427
U3 voltage
0.0 par. 103
Parameter number
Parameter name
Data range
428
F3 frequency
0.0 par. 104
Parameter number
Parameter name
Data range
429
U4 voltage
0.0 par. 103
Parameter number
Parameter name
Data range
430
F4 frequency
0.0 par. 104
Parameter number
Parameter name
Data range
431
U5 voltage
0.0 par. 103
Parameter number
Parameter name
Data range
432
F5 frequency
0.0 par. 104
Parameter number
Parameter name
433
Torque control, open loop
proportional gain
0 (Off) 500%
Data range
Parameter number
Parameter name
Data range
Parameter number
Parameter name
Data values
5000 series
5000 series
5000 series
5000 series
5000 series
5000 series
5000 series
5000 series
FC 300 series
156 index 2
F2 frequency
0.0 1000.0 Hz
FC 300 series
155 index 2
U3 voltage
0.0 1000.0 V
FC 300 series
156 index 3
F3 frequency
0.0 1000.0 Hz
FC 300 series
155 index 4
U4 voltage
0.0 1000.0 V
FC 300 series
156 index 4
F4 frequency
0.0 1000.0 Hz
FC 300 series
155 index 5
U5 voltage
0.0 1000.0 V
FC 300 series
156 index 5
F5 frequency
0.0 1000.0 Hz
FC 300 series
712
Torque PI Proportional Gain
0 (Off) 500%
FC 300 series
434
Torque control, open loop
integral time
0.002 2.000 sec
713
Torque PI Integration Time
0.002 2.000 sec
5000 series
FC 300 series
5000 series
FC 300 series
437
730
Process PID Normal/Inverse Process PID Normal/
contr
Inverse Control
[0] Normal
[0] Normal
[1] Inverse
[1] Inverse
MG.34.N1.02 VLT is a registered Danfoss trademark
43
Parameter number
Parameter name
Data values
438
Process PID Anti windup
[0] Off
[1] On
731
Process PID Anti Windup
[0] Off
[1] On
Parameter number
Parameter name
Data range
439
732
Process PID start frequency Process PID Start Speed
Fmin fmax
0 6000 rpm
5000 series
FC 300 series
Parameter number
Parameter name
Data range
440
Process PID proportional
gain
0.00 10.00
Parameter number
Parameter name
Data range
441
Process PID integral time
0.01 9999.99
Parameter number
Parameter name
Data range
442
Process PID differentiation
time
0.00 10.00
Parameter number
Parameter name
443
Process PID diff. gain limit
Data range
5.0 50.0
736
Process PID Differentiation
Time
0.00 10.00
5000 series
FC 300 series
5000 series
5000 series
5000 series
5000 series
FC 300 series
733
Process PID proportional
gain
0.00 10.00
FC 300 series
734
Process PID integral time
0.01 10000.00
FC 300 series
735
Process PID Differentiation
Time
0.00 10.00
FC 300 series
Parameter number
Parameter name
444
Process PID lowpass filter
time
Parameter number
Parameter name
Data values
445
Flying start
[0] Off
[1] On
Parameter number
Parameter name
Data values
446
Switching pattern
[0] 60 AVM
[1] SFAVM
1400
Switching Pattern
[0] 60 AVM
[1] SFAVM
5000 series
FC 300 series
5000 series
FC 300 series
Parameter number
Parameter name
5000 series
5000 series
447
Torque compensation
MG.34.N1.02
Not converted
FC 300 series
173
Flying Start
[0] Disable
[1] Enable
FC 300 series
Not converted
44
Parameter number
Parameter name
448
Gear ratio
Not converted
5000 series
FC 300 series
5000 series
FC 300 series
5000 series
FC 300 series
5000 series
FC 300 series
5000 series
FC 300 series
Parameter number
Parameter name
449
Friction loss
Parameter number
Parameter name
Data range
450
14-11
Mains voltage at mains fault Mains Voltage at Mains Fault
180 690 Volt
100 800 Volt
Parameter number
Parameter name
453
707
Gear ratio, speed close loop Speed PID Feedback Gear
Ratio
0.01 100.00
0.0001 32.0000
Data range
Parameter number
Parameter name
454
Dead time compensation
Parameter number
Parameter name
455
Frequency range monitor
Parameter number
Parameter name
457
Phase loss functions
Data values
[0]
[1]
Parameter number
Parameter name
5000 series
Trip
Warning
5000 series
483
Dynamic DC link
compensation
Not converted
Not converted
Not converted
FC 300 series
14-12
Function at Mains
Imbalance
[0] Trip
[1] Warning
[2] Disable
FC 300 series
Not converted
45
VLT
5000 Group 5
5000 series
Parameter number
Parameter name
Data range
500
Address
0 126
Parameter number
Parameter name
Data values
501
Baud rate
[0] 300
[1] 600
[2] 1200
[3] 2400
[4] 4800
[5] 9600
Parameter number
Parameter name
Parameter number
Parameter name
Parameter number
Parameter name
Parameter number
Parameter name
Parameter number
Parameter name
Parameter number
Parameter name
Parameter number
Parameter name
Parameter type
Data values
502
Coasting
503
Quick-stop
504
DC brake
505
Start
506
Reversing
507
Setup select
508
Preset reference select
Unsigned 8 (5)
[0] Digital input
[1] Bus
[2] Logic AND
[3] Logic OR
Parameter number
Parameter name
Data range
509
Bus Jog 1
0.0 par. 202
Parameter number
Parameter name
Data range
510
Bus Jog 2
0.0 par. 202
Parameter number
Parameter name
Data values
512
Telegram Profile
[0] Fieldbus profile
[1] FC profile
5000 series
5000 series
5000 series
5000 series
5000 series
FC 300 series
831
Address
0 126
FC 300 series
832
Baud rate
Not supported
Not supported
Not supported
[0] 2400
[1] 4800
[2] 9600
FC 300 series
850
Coasting
851
Quick-stop
852
DC brake
853
Start
854
Reversing
855
Setup select
856
Preset reference select
Unsigned 8 (5)
[0] Digital input
[1] Bus
[2] Logic AND
[3] Logic OR
FC 300 series
890
Bus Jog 1
0.0 par. 413
FC 300 series
891
Bus Jog 2
0.0 par. 413
FC 300 series
810
Control word Profile
[1] ProfiDrive profile
[0] FC profile
46
Parameter number
Parameter name
5000 series
FC 300 series
5000 series
FC 300 series
513
Bus time interval
Not converted
Parameter number
Parameter name
514
Bus time interval function
Parameter number
Parameter name
515
Reference %
Parameter number
Parameter name
516
Reference Unit
Parameter number
Parameter name
517
Feedback
Parameter number
Parameter name
518
Frequency
16-13
Frequency
5000 series
FC 300 series
5000 series
5000 series
5000 series
5000 series
Parameter number
Parameter name
519
Frequency x scaling
Parameter number
Parameter name
520
Current
Parameter number
Parameter name
521
Torque
Parameter number
Parameter name
522
Power, kW
Parameter number
Parameter name
523
Power, HP
Parameter number
Parameter name
524
Motor voltage
Parameter number
Parameter name
525
DC link voltage
Parameter number
Parameter name
526
Motor temp.
5000 series
5000 series
5000 series
5000 series
5000 series
5000 series
5000 series
Not converted
FC 300 series
16-02
Reference %
FC 300 series
16-01
Reference Unit
FC 300 series
16-52
Feedback Unit
FC 300 series
Not converted
FC 300 series
16-14
Motor current
FC 300 series
16-22
Torque %
FC 300 series
16-10
Power, kW
FC 300 series
16-11
Power, HP
FC 300 series
16-12
Motor voltage
FC 300 series
16-30
DC link voltage
FC 300 series
16-18
Motor temp.
47
5000 series
Parameter number
Parameter name
527
VLT temp.
Parameter number
Parameter name
Data values
528
Digital input
Term. 16 (binary 0000
0001)
Term. 17 (binary 0000
0010)
Term. 18 (binary 0000
0100)
Term. 19 (binary 0000
1000)
Term. 27 (binary 0001
0000)
Term. 32 (binary 0010
0000)
Term. 33 (binary 0100
0000)
5000 series
5000 series
Parameter number
529
Parameter name
Analogue input 53
* = Switch S201 must be OFF
5000 series
Parameter number
530
Parameter name
Analogue input 54
** = Switch S202 must be OFF
5000 series
Parameter number
531
Parameter name
Analogue input 60
*** = Switch S202 must be ON
5000 series
Parameter number
Parameter name
532
Pulse reference
Parameter number
Parameter name
533
External reference %
Parameter number
Parameter name
534
Status word, binary
Parameter number
Parameter name
535
Brake power/2 min
Parameter number
Parameter name
536
Brake power/sec
5000 series
5000 series
5000 series
5000 series
FC 300 series
16-35
VLT temp.
FC 300 series
16-60
Digital input
Term. X30/2 (binary )
Term. X30/3 (binary )
Term. 18 (binary )
Term. 19 (binary )
Term. 27 (binary )
Term. 32 (binary )
Term. 33 (binary )
FC 300 series
16-62
Analogue input 53*
FC 300 series
16-64
Analogue input 54**
FC 300 series
16-64
Analogue input 54***
FC 300 series
16-51
Pulse reference
FC 300 series
16-50
External reference %
FC 300 series
16-03
Status Word
FC 300 series
16-33
Brake Energy /2 min
FC 300 series
16-32
Brake Energy /s
48
5000 series
FC 300 series
Parameter number
Parameter name
537
Heat sink temp
Parameter number
Parameter name
538
Alarm word
Parameter number
Parameter name
539
VLT Control word
Parameter number
Parameter name
540
Warning word
Parameter number
Parameter name
541
Extended status word
14-74
VLT Ext. Status Word
5000 series
FC 300 series
5000 series
FC 300 series
Parameter number
Parameter name
5000 series
5000 series
5000 series
5000 series
553
Display text 1
16-34
Heat sink Temp.
FC 300 series
14-72
VLT Alarm word
FC 300 series
16-00
Control word
FC 300 series
14-73
VLT Warning word
FC 300 series
Not converted
Parameter number
Parameter name
554
Display text 2
Parameter number
Parameter name
557
Motor rpm
16-17
Motor rpm
5000 series
FC 300 series
5000 series
FC 300 series
5000 series
FC 300 series
5000 series
FC 300 series
Parameter number
Parameter name
Parameter number
Parameter name
Parameter number
Parameter name
Parameter number
Parameter name
5000 series
558
Motor rpm x scaling
580
Define parameter
581
Define parameter
582
Define parameter
Not converted
FC 300 series
Not converted
Not converted
Not converted
Not converted
49
VLT
5000 Group 6
5000 series
FC 300 series
Parameter number
Parameter name
600
Operating hours
Parameter number
Parameter name
601
Hours run
Parameter number
Parameter name
602
kWh counter
Parameter number
Parameter name
603
Numbers of power up
Parameter number
Parameter name
604
Numbers of over temp.
Parameter number
Parameter name
605
Numbers of over voltage
15-05
Over voltage
5000 series
FC 300 series
5000 series
FC 300 series
5000 series
FC 300 series
5000 series
FC 300 series
5000 series
FC 300 series
5000 series
FC 300 series
5000 series
FC 300 series
Parameter number
Parameter name
Parameter number
Parameter name
Parameter number
Parameter name
Parameter number
Parameter name
Parameter number
Parameter name
Parameter number
Parameter name
Parameter number
Parameter name
5000 series
5000 series
5000 series
5000 series
5000 series
606
Data log: Digital input
607
Data log: Bus commands
608
Data log: Status word
609
Data log: Reference
610
Data log: Feedback
611
Data log: Motor frequency
612
Data log: Motor voltage
15-00
Operating hours
FC 300 series
15-01
Running Hours
FC 300 series
15-02
kWh counter
FC 300 series
15-03
Power Up's
FC 300 series
15-04
Over Temp's
FC 300 series
Not converted
Not converted
Not converted
Not converted
Not converted
Not converted
Not converted
50
Parameter number
Parameter name
5000 series
FC 300 series
5000 series
FC 300 series
613
Data log: Motor current
Not converted
Parameter number
Parameter name
614
Data log: DC link voltage
Parameter number
Parameter name
615
Fault log: Error code
Parameter number
Parameter name
616
Fault log: Time
Parameter number
Parameter name
617
Fault log: Value
Parameter number
Parameter name
Data value
618
Reset of kWh counter
[0] No reset
[1] Reset
Parameter number
Parameter name
619
Reset of Hours run
Data value
[0] No reset
[1] Reset
Parameter number
Parameter name
Data value
620
Operation mode
[0] Normal operation
[1] Function with
deactivated inverter
[2] Control card test
[3] Initialisation
5000 series
FC 300 series
5000 series
FC 300 series
5000 series
FC 300 series
Parameter number
Parameter name
Parameter number
Parameter name
Parameter number
Parameter name
5000 series
5000 series
5000 series
5000 series
5000 series
5000 series
621
Name plate: VLT type
622
Name plate: Power section
Not converted
FC 300 series
15-30
Fault log: Error code
FC 300 series
15-32
Fault log: Time
FC 300 series
15-31
Fault log: Value
FC 300 series
15-06
Reset kWh Counter
[0] Do not reset
[1] Reset counter
FC 300 series
15-07
Reset Running Hours
Counter
[0] Do not reset
[1] Reset counter
FC 300 series
14-22
Operation Mode
[0] Normal operation
Not supported
Not converted
Not converted
623
Not converted
Name plate: VLT ordering
no.
MG.34.N1.02 VLT is a registered Danfoss trademark
51
Parameter number
Parameter name
Parameter number
Parameter name
Parameter number
Parameter name
Parameter number
Parameter name
Parameter number
Parameter name
Parameter number
Parameter name
Parameter number
Parameter name
Parameter number
Parameter name
5000 series
FC 300 series
5000 series
FC 300 series
5000 series
FC 300 series
5000 series
FC 300 series
5000 series
FC 300 series
5000 series
FC 300 series
5000 series
FC 300 series
5000 series
FC 300 series
624
Name plate: Software
version no.
625
Name plate: LCP ID no
626
Name plate: Data base ID
627
Name plate: Power ID no.
628
Name plate: Application
type
629
Name plate: Application
type no.
630
Name plate: Com. type
Not converted
Not converted
Not converted
Not converted
Not converted
Not converted
Not converted
631
Not converted
Name plate: Com. Type no.
52
VLT
5000 Group 8
Parameter number
Parameter name
Parameter number
Parameter name
5000 series
FC 300 series
5000 series
FC 300 series
5000 series
FC 300 series
800
PROFIBUS DP
801
Baud rate selection
Not converted
Not converted
Parameter number
Parameter name
802
Minimum station delay
Parameter number
Parameter name
Data range
803
Time out after bus error
1 99
803
Control Word Timeout Time
0.1 18000.0
Parameter number
Parameter name
804
804
Response after bus time out Control Word Timeout
Function
[0] Off
[0] Off
[1] Freeze output frequency [1] Freeze output frequency
[2] Stop
[2] Stop
[3] Jogging
[3] Jogging
[4] Max speed
[4] Max speed
[5] Stop and trip
[5] Stop and trip
Par. 802 to RS485
[6] No com. option control
[7] Select set up 4
[10] Select set up 4
5000 series
FC 300 series
Data value
Parameter number
Parameter name
Data value
Parameter number
Parameter name
Parameter number
Parameter name
5000 series
5000 series
Not converted
FC 300 series
FC 300 series
805
Function of control word bit
10
[0] No function
[1] Bit 10 = 1 => CTW
active
[2] Bit 10 = 0 => CTW
active
[3] Bit 10 = 1 => Time out
814
Configurable Control Word
CTW
[0] None
[1] Profile default
5000 series
FC 300 series
5000 series
FC 300 series
806
SAP selection (FMS)
808
ProfiDrives status word
53
Parameter number
Parameter name
Data value
VLT
5000 series
849
Extended diagnose
[0] Disable
[1] Alarm
[2] Alarm and warnings
FC 300 series
807
Diagnosis Trigger
[0] Disable
[1] Trigger on alarm
[2] Trigger on alarm/warn.
5000 Group 9
Parameter number
Parameter name
Parameter number
Parameter name
Parameter number
Parameter name
Parameter number
Parameter name
Parameter number
Parameter name
Parameter number
Parameter name
Parameter number
Parameter name
Parameter number
Parameter name
Parameter number
Parameter name
Parameter number
Parameter name
Parameter number
Parameter name
5000 series
FC 300 series
5000 series
FC 300 series
5000 series
FC 300 series
5000 series
FC 300 series
5000 series
FC 300 series
5000 series
FC 300 series
5000 series
FC 300 series
5000 series
FC 300 series
5000 series
FC 300 series
5000 series
FC 300 series
5000 series
FC 300 series
900
Write PPO type 1
901
Write PPO type 2
902
Write PPO type 3
903
Write PPO type 4
904
PPO type select for DP
907
Read PPO type 1
908
Read PPO type 2
909
Read PPO type 3
910
Read PPO type 4
911
PPO type for FMS read
913
Broadcast index
Not converted
Not converted
Not converted
Not converted
Not converted
Not converted
Not converted
Not converted
Not converted
Not converted
Not converted
54
5000 series
FC 300 series
5000 series
FC 300 series
Parameter number
Parameter name
914
Broadcast off-set
Parameter number
Parameter name
Data value
915
PCD config write
[0] None
[204] Minimum Reference
[205] Maximum Reference
[219] Catch up/slow Down
Value
[207] Ramp 1 Ramp up
Time
[208] Ramp 1 Ramp Down
Time
[209] Ramp 2 Ramp up
Time
[210] Ramp 2 Ramp down
Time
[211] Jog Ramp Time
[212] Quick Stop Ramp
Time
[201] Motor Low Limit [Hz]
Comments
Parameter number
Parameter name
Data value
Not converted
915
PCD Write Configuration
[0] None
[302] Minimum Reference
[203] Maximum Reference
[312] Catch up/slow Down
Value
[341] Ramp 1 Ramp up
Time
[342] Ramp 1 Ramp Down
Time
[351] Ramp 2 Ramp up
Time
[352] Ramp 2 Ramp down
Time
[380] Jog Ramp Time
[381] Quick Stop Ramp
Time
[412] Motor Speed Low
Limit [Hz]
[202] Motor High Limit [Hz] [413] Motor Speed High
Limit [Hz]
[221] Torque Limit Motor
[416] Torque Limit Motor
Mode
Mode
[222] Torque Limit
[417] Torque Limit
Generator Mode
Generator Mode
[509] Bus Jog 1 Speed
[890] Bus Jog 1 Speed
[510] Bus Jog 2 Speed
[891] Bus Jog 2 Speed
VLT 5000 supports more write signals. If a notsupported signal is written then the corresponding signal
will be set to [0] None.
5000 series
916
PCD config read
[0] None
[538] Alarm word
[540] Warning word
[541] Ext. status word
[600] Operating hours
[601] Running hours
[602] kWh Counter
[539] Control word
[516] Reference [Unit]
[515] Reference %
[534] Status word
[522] Power [kW]
[523] Power [HP]
[524] Motor voltage
[518] Motor frequency
FC 300 series
916
PCD read Configuration
[0] None
[1472] VLT Alarm Word
[1473] VLT Warning Word
[1474] VLT Ext. status
Word
[1500] Operating hours
[1501] Running hours
[1502] kWh Counter
[1600] Control word
[1601] Reference [Unit]
[1602] Reference %
[1603] Status word
[1610] Power [kW]
[1611] Power [HP]
[1612] Motor voltage
[1613] Motor frequency
55
5000 series
FC 300 series
Parameter number
Parameter name
917
Spontaneous messages
Parameter number
Parameter name
Data range
918
Station address
0 125
Parameter number
Parameter name
Data value
927
Parameter edit
[0] Disable
[1] Enable
Parameter number
Parameter name
Data value
928
Control authority
[0] Disable
[1] Enable
Parameter number
Parameter name
953
Warning parameter
Parameter number
Parameter name
964
Identification
Parameter number
Parameter name
965
Profile number
965
Profile number
5000 series
FC 300 series
5000 series
FC 300 series
Parameter number
Parameter name
Parameter number
5000 series
5000 series
5000 series
5000 series
5000 series
5000 series
967
Control word (FMS)
968
Not converted
FC 300 series
918
Node Address
0 125
FC 300 series
927
Parameter edit
[0] Disable
[1] Enable
FC 300 series
928
Process Control
[0] Disable
[1] Enable cyclic master
FC 300 series
953
PROFIBUS Warning Word
FC 300 series
964
Device Identification
FC 300 series
Not converted
Not converted
56
Parameter name
Parameter number
Parameter name
Data value
970
Parameter setup selection
[0] Factory setting
[1] Parameter setup 1
[2] Parameter setup 2
[3] Parameter setup 3
[4] Parameter setup 4
[5] Active setup
Parameter number
Parameter name
Parameter type
Data value
971
Save data values
Unsigned 8 (5)
[0] Not active
[1] Save active setup
[2] Save edit setup
[3] Save all setups
971
PROFIBUS Save Data Values
Unsigned 8 (5)
[0] Off
[1] Store all setups
[1] Store all setups
[1] Store all setups
5000 series
FC 300 series
5000 series
FC 300 series
5000 series
FC 300 series
5000 series
FC 300 series
5000 series
FC 300 series
5000 series
FC 300 series
Parameter number
Parameter name
Parameter number
Parameter name
Parameter number
Parameter name
Parameter number
Parameter name
Parameter number
Parameter name
Parameter number
Parameter name
5000 series
5000 series
980
Defined parameters
981
Defined parameters
982
Defined parameters
990
Modified parameters
990
Modified parameters
990
Modified parameters
FC 300 series
970
Edit Set-up
[0] Factory setting
[1] Parameter setup 1
[2] Parameter setup 2
[3] Parameter setup 3
[4] Parameter setup 4
[5] Active setup
FC 300 series
Not converted
Not converted
Not converted
Not converted
Not converted
Not converted
57
Troubleshooting
Step-by-step troubleshooting
After copying the station address from the VLT 5000 to the FC 302, power must be cycled to the FC
302. The master/PLC should now recognize FC 302, as a VLT 5000, and the NS LED on the MCA114
option should now be solid green which indicates that communication between master and slave is
established.
If the NS LED flashes, the master/PLC has not recognized the FC 302.
Check if station address is the same in the FC 302 as the replaced VLT 5000.
Check par. 9-63 Actual Baudrate. If the drive has a connection to the master this
parameter will display the detected baudrate. If not master has been detected the
parameter will display: No baud rate found.
Check par. 9-53 PROFIBUS Warning Word.
Bit
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
0001
0002
0004
0008
0010
0020
0040
0080
0100
0200
0400
0800
1000
2000
4000
8000
Description
58
A
Abbreviations
B
Brake chopper
C
Commissioning
Configuration
Constrains
12
11
6
D
DIP switches
11
E
EMC precautions
14
H
Hardware
I
Installation
L
Linked setups
Literature
LEDs
7
7
13
M
MCA114
Mechanical adaptation
9
7
N
Node address
11
O
Overview (technical)
P
Parameters (mapping list)
Performance
Power size
15
7
5
S
Safety
T
Terminals
Troubleshooting
6
58
W
Warning word
58
59
www.danfoss.com/drives
130R0371
MG34N102
*MG34N102*
Rev. 2008-09-24