You are on page 1of 16

UNIT 1

LAVT
CT 2
Name Plate Details:
Core 1: 2500/5 A

Burden: -

CL: PS

I SF / ALF : -

Core 2: 2500/5 A

Burden: -

CL: PS

I SF / ALF : -

For

Core 1: Vk: 400V; Max. RS: 2.0 ; Iex<30 mA at Vk/2

For

Core 2: Vk: 400V; Max. RS: 2.0 ; Iex<30 mA at Vk/2

Freq: 50Hz; Ins. Level : 12/36/95 kV; STC: 40 kA for 1 sec.; Ins. Cl: B
Confirmed To: IS 2705/1992
Knee Point Voltage Test:
R PH:
CT SL. NO.: CT12109179
Applied Voltage to
secondary in Volts
20
40
60
80
100
120
140
160
180
200
220

Y PH:

Measured Current in mA
Core 1
Core 2
9.0
9.0
12.9
12.8
15.6
15.5
18.3
17.6
20.8
20.7

CT SL. NO.: CT12109176


Applied Voltage to
secondary in Volts
20
40
60
80
100
120
140
160
180
200
220

Measured Current in mA
Core 1
Core 2
8.9
7.8
13.0
11.2
15.3
13.5
18.2
16.1
20.1
18.0

B PH:
CT SL. NO.: CT12109175
Applied Voltage to
secondary in Volts
20
40
60
80
100
120
140
160
180
200
220

CT 3

Measured Current in mA
Core 1
Core 2
8.5
8.9
11.8
12.7
14.3
15.1
19.0
18.2
20.0
20.4

Name Plate Details:


Core 1: 2500/5 A

Burden: -

CL: PS

I SF / ALF : -

Core 2: 2500/5 A

Burden: -

CL: PS

I SF / ALF : -

For

Core 1: Vk: 400V; Max. RS: 2.0 ; Iex<30 mA at Vk/2

For

Core 2: Vk: 400V; Max. RS: 2.0 ; Iex<30 mA at Vk/2

Freq: 50Hz; Ins. Level : 12/36/95 kV; STC: 40 kA for 1 sec.; Ins. Cl: B
Confirmed To: IS 2705/1992
Knee Point Voltage Test:
R PH:
CT SL. NO.: CT12109169
Applied Voltage to
secondary in Volts
20
40
60
80
100
120
140
160
180
200
220

Y PH:
CT SL. NO.: CT12109171

Measured Current in mA
Core 1
Core 2
6.5
8.5
10.6
13.0
13.5
16.4
15.7
19.7
17.7
23.1

Applied Voltage to
secondary in Volts
20
40
60
80
100
120
140
160
180
200
220

Measured Current in mA
Core 1
Core 2
10.1
8.2
13.6
12.9
16.7
15.2
20.0
18.2
22.6
22.9

B PH:
CT SL. NO.: CT12109174
Applied Voltage to
secondary in Volts
20
40
60
80
100
120
140
160
180
200
220

UNIT 1 NGT
CT 1
Name Plate Details:

Measured Current in mA
Core 1
Core 2
9.6
10.9
13.5
15.3
17.1
18.5
21.0
22.1
24.9
24.2

Core 1: 2500/5 A

Burden: -

CL: PS

I SF / ALF : -

Core 2: 2500/5 A

Burden: -

CL: PS

I SF / ALF : -

For

Core 1: Vk: 400V; Max. RS: 2.0 ; Iex<30 mA at Vk/2

For

Core 2: Vk: 400V; Max. RS: 2.0 ; Iex<30 mA at Vk/2

Freq: 50Hz; Ins. Level : 12/36/95 kV; STC: 40 kA for 1 sec.; Ins. Cl: B
Confirmed To: IS 2705/1992
Knee Point Voltage Test:

R PH:
CT SL. NO.: CT12109185
Applied Voltage to
secondary in Volts
20
40
60
80
100
120
140
160
180
200
220

Measured Current in mA
Core 1
Core 2
6.2
10.2
9.8
14.5
12.9
17.4
15.5
20.4
18.2
23.6

Y PH:
CT SL. NO.: CT12109186
Applied Voltage to
secondary in Volts

Measured Current in mA

Core 1
6.7
10.5
14.2
17.6
21.2

20
40
60
80
100
120
140
160
180
200
220

Core 2
11.4
15.1
17.1
18.5
20.7

B PH:
CT SL. NO.: CT12109184
Applied Voltage to
secondary in Volts
20
40
60
80
100
120
140
160
180
200
220

Measured Current in mA
Core 1
Core 2
8.5
9.5
11.6
13.2
13.3
15.1
15.0
17.0
16.6
18.3

CT 2
Name Plate Details:
Core 1: 2500/5 A

Burden: -

CL: PS

I SF / ALF : -

Core 2: 2500/5 A

Burden: -

CL: PS

I SF / ALF : -

For

Core 1: Vk: 400V; Max. RS: 2.0 ; Iex<30 mA at Vk/2

For

Core 2: Vk: 400V; Max. RS: 2.0 ; Iex<30 mA at Vk/2

Freq: 50Hz; Ins. Level : 12/36/95 kV; STC: 40 kA for 1 sec.; Ins. Cl: B
Confirmed To: IS 2705/1992
Knee Point Voltage Test:

R PH:

CT SL. NO.: CT12109180


Applied Voltage to
secondary in Volts
20
40
60
80
100
120
140
160
180
200
220

Measured Current in mA
Core 1
Core 2
9.7
9.3
14.0
13.6
16.9
15.1
19.9
17.7
23.7
20.2

Y PH:
CT SL. NO.: CT12109188
Applied Voltage to
secondary in Volts
20

Measured Current in mA
Core 1
Core 2
12.5
9.2

40
60
80
100
120
140
160
180
200
220

16.6
19.1
22.0
24.1

12.9
15.6
18.7
21.5

B PH:
CT SL. NO.: CT12109190
Applied Voltage to
secondary in Volts
20
40
60
80
100
120
140
160
180
200
220

Measured Current in mA
Core 1
Core 2
9.3
9.7
13.8
12.9
15.9
15.3
18.2
17.4
20.4
18.4

UNIT 2
LAVT
CT 2
Name Plate Details:
Core 1: 2500/5 A

Burden: -

CL: PS

I SF / ALF : -

Core 2: 2500/5 A

Burden: -

CL: PS

I SF / ALF : -

For

Core 1: Vk: 400V; Max. RS: 2.0 ; Iex<30 mA at Vk/2

For

Core 2: Vk: 400V; Max. RS: 2.0 ; Iex<30 mA at Vk/2

Freq: 50Hz; Ins. Level : 12/36/95 kV; STC: 40 kA for 1 sec.; Ins. Cl: B
Confirmed To: IS 2705/1992
Knee Point Voltage Test:
R PH:
CT SL. NO.: CT12109170
Applied Voltage to
secondary in Volts
20
40
60
80
100
120
140
160
180
200
220

Measured Current in mA
Core 1
Core 2
9.7
9.5
14.0
13.5
17.4
16.8
21.4
19.5
25.2
21.8
23.1
26.1

Y PH:
CT SL. NO.: CT12109178
Applied Voltage to
secondary in Volts
20
40
60
80

Measured Current in mA
Core 1
Core 2
10.1
10.0
14.2
14.5
17.1
17.9
19.5
20.9

100
120
140
160
180
200
220

21.6
23.8
26.4

24.4
28.2

B PH:
CT SL. NO.: CT12109172
Applied Voltage to
secondary in Volts
20
40
60
80
100
120
140
160
180
200
220

Measured Current in mA
Core 1
Core 2
9.7
10.4
13.8
14.6
17.7
18.3
21.2
21.3
25.0
23.2
25.7
27.9

CT 3
Name Plate Details:
Core 1: 2500/5 A

Burden: -

CL: PS

I SF / ALF : -

Core 2: 2500/5 A

Burden: -

CL: PS

I SF / ALF : -

For

Core 1: Vk: 400V; Max. RS: 2.0 ; Iex<30 mA at Vk/2

For

Core 2: Vk: 400V; Max. RS: 2.0 ; Iex<30 mA at Vk/2

Freq: 50Hz; Ins. Level : 12/36/95 kV; STC: 40 kA for 1 sec.; Ins. Cl: B
Confirmed To: IS 2705/1992
Knee Point Voltage Test:
R PH:
CT SL. NO.: CT12109173
Applied Voltage to
secondary in Volts
20
40
60
80
100
120
140
160
180
200
220

Measured Current in mA
Core 1
Core 2
11.8
10.6
17.2
14.8
21.9
18.1
26.4
21.2
24.7
28.0

Y PH:
CT SL. NO.: CT12109177
Applied Voltage to
secondary in Volts
20
40
60
80
100
120

Measured Current in mA
Core 1
Core 2
10.4
9.1
14.7
13.1
17.8
16.1
20.8
17.7
23.2
18.4
26.6
21.4

140
160
180
200
220

23.3
25.8

B PH:
CT SL. NO.: CT12109168
Applied Voltage to
secondary in Volts
20
40
60
80
100
120
140
160
180
200
220

Measured Current in mA
Core 1
Core 2
10.6
10.1
14.6
13.9
17.1
16.1
19.6
18.5
22.2
20.6
25.3
23.1
25.8

UNIT 2 NGT
CT 1
Name Plate Details:
Core 1: 2500/5 A

Burden: -

CL: PS

I SF / ALF : -

Core 2: 2500/5 A

Burden: -

CL: PS

I SF / ALF : -

For

Core 1: Vk: 400V; Max. RS: 2.0 ; Iex<30 mA at Vk/2

For

Core 2: Vk: 400V; Max. RS: 2.0 ; Iex<30 mA at Vk/2

Freq: 50Hz; Ins. Level : 12/36/95 kV; STC: 40 kA for 1 sec.; Ins. Cl: B
Confirmed To: IS 2705/1992

Knee Point Voltage Test:

R PH:
CT SL. NO.: CT12109189
Applied Voltage to
secondary in Volts
20
40
60
80
100
120
140
160
180
200
220

Measured Current in mA
Core 1
Core 2
10.0
9.0
14.1
12.3
17.0
15.3
20.4
17.2
23.2
19.7
21.9
24.2
26.7

Y PH:
CT SL. NO.: CT12109191
Applied Voltage to
secondary in Volts
20
40
60
80
100
120
140
160
180

Measured Current in mA
Core 1
Core 2
7.7
9.9
12.1
13.9
16.2
17.2
20.3
19.3
24.6
22.2
24.6

200
220
B PH:
CT SL. NO.: CT12109183
Applied Voltage to
secondary in Volts
20
40
60
80
100
120
140
160
180
200
220

Measured Current in mA
Core 1
Core 2
9.9
9.6
13.9
13.9
17.2
17.2
19.3
20.6
22.2
24.1
24.6

CT 2
Name Plate Details:
Core 1: 2500/5 A

Burden: -

CL: PS

I SF / ALF : -

Core 2: 2500/5 A

Burden: -

CL: PS

I SF / ALF : -

For

Core 1: Vk: 400V; Max. RS: 2.0 ; Iex<30 mA at Vk/2

For

Core 2: Vk: 400V; Max. RS: 2.0 ; Iex<30 mA at Vk/2

Freq: 50Hz; Ins. Level : 12/36/95 kV; STC: 40 kA for 1 sec.; Ins. Cl: B
Confirmed To: IS 2705/1992
Knee Point Voltage Test:

R PH:

CT SL. NO.: CT12109182


Applied Voltage to
secondary in Volts
20
40
60
80
100
120
140
160
180
200
220

Measured Current in mA
Core 1
Core 2
6.8
11.3
10.4
15.2
13.7
18.1
16.7
21.0
19.9
23.0
23.4
25.2
27.6
27.7

Y PH:
CT SL. NO.: CT12109181
Applied Voltage to
secondary in Volts
20
40
60
80
100
120
140
160
180
200
220

Measured Current in mA
Core 1
Core 2
9.7
9.3
13.7
13.0
17.1
16.2
20.8
18.4
24.2
20.7
27.1
22.7
26.0
27.2

B PH:
CT SL. NO.: CT12109187
Applied Voltage to
secondary in Volts
20
40
60
80
100
120
140
160
180
200
220

Measured Current in mA
Core 1
Core 2
10.3
10.3
14.5
14.4
17.8
17.2
20.6
20.0
24.3
22.2
28.4
25.4
28.5

You might also like