The amount of DC bus voltage is monitored by the drive controller. If the DC bus
voltage below a minimal threshold, the drive be governed according to the selected
error response is shut automatically.
reason:
1. Power of, without disabling the drive via the controller enabling.
2. Disturbance in the power supply
Remedy:
Check the logic for activating the drive within the connected control.
Checking the power supply.
The error disappears when DKC01, DKC11 and DKC03 when removing the controller
enable.
F878
The speed control loop monitoring is triggered when following conditions occur
simultaneously:
1. The current nominal value is at the peak current limit
2. The diference between actual speed and setpoint speed is greater than 10% of
the maximum motor speed.
3. actual speed> 1.25 of the maximum speed
4. setpoints and actual acceleration have diferent signs.
reason:
1. Motor cable is connected incorrectly.
2. Power section of the drive controller is defective.
3. Feedback defective.
4. Speed controller parameterization wrong
5. commutation ofset wrong
Remedy:
1. Check the motor cable connection.
2. Replace the drive controller.
3. Replace motor.
4. Check the velocity controller to the application specification
5. Replace motor.