You are on page 1of 1

49 Hz

Grid
Trip

48.75 Hz
UF LS
Stage 1

48.3 Hz
UF LS
Stage 2

48 Hz
UF LS
Stage 3

47.7 Hz
UF LS
Stage 4

df/dt = -2
Hz/sec

0.1 sec

Trip Grid

0.4 sec

Trip Stage 1 Loads

0.1 sec

Trip Stage 1 Loads

0.4 sec

Trip Stage 2 Loads

0.2 sec

Trip Stage 2 Loads

0.4 sec

Trip Stage 3 Loads

0.2 sec

Trip Stage 3 Loads

0.4 sec

Trip Stage 4 Loads

0.2 sec

Trip Stage 4 Loads

0.1 sec

Generator Protection Trip

df/dt = -0.9
Hz/sec

df/dt = -0.28
Hz/sec

df/dt = 0
Hz/sec

df/dt = 0
Hz/sec

47 Hz

You might also like