You are on page 1of 168

Capacitors

Dominik Pieniazek, P.E. VI Engineering, LLC


Nicholas A. Losito Jr. Castle Power Solutions, LLC

Outline
Day 1
Basic Power Calculations
Capacitor Fundamentals
Capacitor Ratings
Capacitor Application
Capacitor
p
Protection
Day 2
Harmonics
Capacitor Bank Design Considerations

Shunt Capacitors
Medium Voltage
pp
Substation Applications
Power Factor Correction

Basic Power Calculations

Basic Power Calculations


C
Common
Q
Questions:
ti
What are VARs?
Wh do
Why
d we care about
b t VARs?
VAR ?

Basic Power Calculations


Most plant loads (motors, transformers, etc) are INDUCTIVE
and require a magnetic field to operate. The magnetic field is
necessary, but produces NO USEFUL WORK. The utility
must supply the power to produce the magnetic field and the
power to produce USEFUL work.
The ACTIVE component produces the USEFUL work, the
REACTIVE component produces the magnetic field.

VAR

Basic Power Calculations


An analogy
gy that
most can understand.

VA

Mug
Capacity
i off equipment
i
(i.e. xfmr, cable, swgr, etc)
ee
Beer
Stuff that you want
Foam (Head)
St ff which
Stuff
hi h prevents
t
you from maximizing the
amount of beer that you get

Basic Power Calculations

V: Reference
f
voltage
l
IR: Resistive load
IL: Inductive load
IC: Capacitive load

Basic Power Calculations

Vref
Ires

Power = Re(V I*)

Basic Power Calculations

Vref
Ilag

Power = Re(V I*)


Note that due to phase shift (30 degrees) only 86.66% of current is applied to calculate work.

Basic Power Calculations

Vref
Ilead

Power = Re(V I*)


Regardless whether leading or lagging, power calculation yields similar results

Basic Power Calculations

Vref
I90

Power = Re(V I*)


In the case where current leads or lags the voltage by 90 degrees, P = 0

Basic Power Calculations


Power Factor [ PF ] = Cos

=P/S

A)
V
k
S(

P (W)
Power Triangle
g
The relationship between S, P, and Q. This figure represents a lagging power
factor. If Q is negative, leading power factor.

Q (kVAR)

Basic Power Calculations


So how do we know if our
current is lagging or leading
the voltage, and what can we
do to correct it?
Consider this example,
example

Basic Power Calculations


Incomingg service is at
99.5% capacity
5500 kW
3400 kVAR
6466 kVA

2000 kW
1000 kVAR

1000 kW
800 kVAR

2500 kW
1600 kVAR

Basic Power Calculations


Power Factor [ PF ] = Cos
=gP / S
0.85 lag
A)
V
k
S(

31.8 deg
P (W)
5500
kW
Power Triangle
g
Even though our facility require only 5500 kW to perform Real Work, our
incoming service must be sized for 6466 kVA.

Q
(kVAR)
3400
kVAR

We have a 6500 kVA mug


that is holding 5500 kW
and 3400 kVAR.

VA

VAR

Basic Power Calculations

With the existing configuration


the facilityy cannot add anyy loads
without upgrading the incoming
service.

Basic Power Calculations


Incomingg service is at
85% capacity
5500 kW
0 kVAR
5500 kVA

3400 kVAR

2000 kW
1000 kVAR

1000 kW
800 kVAR

2500 kW
1600 kVAR

Basic Power Calculations


Power Factor [ PF ] = Cos
= Py / S
1.0 unity
A)
V
k
S(

0 deg
P (W)
5500
kW
Power Triangle
g
The cap bank is providing 3400 kVAR, so our service is now providing only
5500 kVA (reduction from 6466 kVA.

Q
(kVAR)
0 kVAR

Basic Power Calculations


COS [
] = 0.67
COS [
] = 0.95
Q2 = Q1 + Qc

VA
k
00
1,5

Q1 = 1,118 kVAR

VA
1,053 k

Q2 = 330 kVAR
Q

1 000 kW
1,000
Required Apparent Power
Before and After
Adding a Power Capacitor Bank

Qc = 788 kVAR

An example of how to calculate the size of a cap bank based on a target power factor

Basic Power Calculations

But wait, theres more.

Basic Power Calculations


Odds are that the utilityy is
charging you for penalties
for a low power factor.

5500 kW
3400 kVAR
6466 kVA

5500
= 0.85
6466
Typically, penalties are
applied for power factor less
than 0.95%.
2000 kW
1000 kVAR

1000 kW
800 kVAR

2500 kW
1600 kVAR

Basic Power Calculations


There are also voltage
g
considerations.
5500 kW
3400 kVAR
6466 kVA
Volt Drop = 5.8%

Assuming typical values:


Source impedance =
9% at 6500 kVA
The expected voltage drop at
the main bus will be close to
6%!

2000 kW
1000 kVAR

1000 kW
800 kVAR

2500 kW
1600 kVAR

Basic Power Calculations


Capacitor bank reduces the
voltage drop at main bus
by 5%!
5500 kW
0 kVAR
5500 kVA
Volt Drop = 1.0%
3400 kVAR

2000 kW
1000 kVAR

1000 kW
800 kVAR

2500 kW
1600 kVAR

Basic Power Calculations


Note that the capacitor bank
can also raise the bus voltage
g
above the nominal value.
5500 kW
-1600 kVAR
5728 kVA
Volt Drop = -1.5%
5000 kVAR

2000 kW
1000 kVAR

1000 kW
800 kVAR

2500 kW
1600 kVAR

Basic Power Calculations


The voltage continues to rise
if the capacitor
p
bank remains
connected and the load is
reduced.

3000 kW
-3200 kVAR
4386 kVA
Volt Drop = -3.6%

5000 kVAR

Out of service

2000 kW
1000 kVAR

1000 kW
800 kVAR

0 kW
0 kVAR

Capacitor Fundamentals

Capacitor Fundamentals

C = eo A / d for a parallel plate capacitor,


where eo is the permittivity of the insulating material (dielectric)
between plates.

Capacitor Fundamentals

We recall that we can add series capacitances to


obtain an equivalent capacitance.

1 / Ceq = 1 / C1 + 1 / C2

Capacitor Fundamentals

Similarly, we can add parallel capacitances to


obtain an equivalent capacitance.

Ceq = C1 + C2

Capacitor Fundamentals
but we typically do not have much use for capacitance values.
So we convert capacitance to impedance:

1
1
XC

C 2fC

Capacitor Fundamentals
Z R jX c
Z R jX c
Z XC
2

V
Z
S

V
S
XC

Capacitor Fundamentals
2

V [kV ]
S [kV
kVAR]
*1000
000
Z []
Example:
The capacitance of a capacitor is 6.22 F and the
nameplate voltage is 8000 V. Calculate the power rating.

XC

1
426.7[]
6
2(3.14)(60)(6.22 x10 )
(8) 2
S
1,000 150[kVAR]
426.7

Capacitor Fundamentals

Capacitor Fundamentals

Capacitor Fundamentals

Capacitor Fundamentals

Capacitor Fundamentals

Capacitor Fundamentals
Note that IEEE Std 18
requires the discharge
resistor to reduce the
terminal voltage to 50 V in
th time
the
ti frame
f
as specified
ifi d
in the table below.

Discharge resistor

Capacitor Ratings

Capacitor Ratings
Medium-voltage
Medium
voltage capacitors are available in many different styles.
styles
The main points of differentiation are listed below:
Voltage rating
kVAR rating
Single
g bushingg or dual bushingg
Internally fused, externally fused, or fuseless

Capacitor Ratings
IEEE 81 defines the ratings for capacitors
Voltage, rms (terminal to terminal)
Terminal-to-case (or ground) insulation class
Reactive power
Number of phases
p
Frequency

Capacitor Ratings
IEEE 18 provides capacitor tolerances
The capacitance shall not vary more than -0% to +10% of
nominal value based on rated kVAR, voltage, and frequency
measured at 25 deg C.
This means that a new 150 kVAR unit can range
g anywhere
y
from
150 kVAR to 165 kVAR.

Capacitor Ratings
IEEE 18 states the capacitor is intended to operate at or below
rated voltage. Capacitors shall be capable of continuous
operation given that none of the following limitations are
exceeded:
110% of rated rms voltage (temporary overvoltage parameters
will be discussed later))
120% of peak voltage, including harmonics but excluding
transients
135% of nominal rms current based on rated kVAR and rated
voltage
135% of rated kVAR

Capacitor Ratings

* Impulse tests shall be applied between terminals and case, with the terminals connected together. For capacitors
having bushings with two different BIL ratings, this test shall be based on the bushing with the lower
BIL. The nameplate shall show both BIL ratings, e.g. 150/95 kV BIL.
** Not applicable to indoor ratings

Capacitor Application

Capacitor Application
Power factor correction capacitor banks are typically installed in
the following ways :
Pole top
Metal-Enclosed / Pad-Mount
Ope
Open rack
ac
Terminal end at equipment

Capacitor Application

P l Top
Pole
T Installation
I t ll ti

Capacitor Application

Transient inrush reactors

P l Top
Pole
T Installation
I t ll ti

Capacitor Application

Pad Mounted Installation


Pad-Mounted

Capacitor Application

Metal-Enclosed
Metal
Enclosed Substation Installation

Capacitor Application

Three-phase iron core


harmonic filter reactor
Metal-Enclosed
Metal
Enclosed Substation Installation

Capacitor Application

Open Rack, Medium-Voltage Substation Installation

Capacitor Application

Open Rack, High-Voltage Substation Installation

Capacitor Application

Installation in Equipment

Capacitor Application
Power factor correction capacitor banks can be configured in the
following ways :
Delta
Wye - Solidly Grounded
Wye
y - Ungrounded
g
A common misconception is that the capacitor bank should be
connected Delta since it is being applied to a delta or high
highimpedance grounded system. This is NOT true.

Capacitor Application
The driving factor which determine the configuration for the
given application is COST.
Voltage considerations
IEEE 1036 suggests that only banks rated 2400 V and below
should be Delta connected.
connected This is mainly because standard
voltage ratings for wye connected banks may not be available.
Cost of phase-to-phase vs phase-to-neutral rated capacitors at
higher voltages tends to point installations towards wye
connected banks for larger bank installations.

Capacitor Application
Delta
Lower voltages (<= 2400 V)
Standard capacitors are typically not available at 1380 V
Distribution systems (pole top)
Units are configured with a single series group of capacitors
with capacitors rated phase-to-phase.
phase to phase Therefore
Therefore, unbalance
detection is not required.

Capacitor Application
Wye Solidly Grounded
Initial cost of the bank may be lower since the neutral does not
have to be insulated from ground.
ground
Capacitor switch recovery voltages are reduced
High inrush currents may occur in the station ground system
The
Th grounded-wye
d d
arrangement provides
id a low-impedance
l
i
d
fault
f l
path which may require revision to the existing system ground
pprotection scheme. Typically
yp
y not applied
pp
to ungrounded
g
systems.
y
When applied to resistance-grounded systems, difficulty in
coordination between capacitor fuses and upstream ground
protection relays (consider coordination of 40 A fuse with a 400 A
grounded system).
Typical for smaller installations (since auxiliary equipment is not
required)
i d)

Capacitor Application
The most common capacitor bank configurations for
larger substation applications are Wye-Ungrounded

Three of the most common unbalance protection schemes are shown.


Discussion of the protection schemes will be presented later.

Capacitor Protection
Fusing
Fuseless
Internally
I t
ll Fused
F d
Externally Fused

Capacitor Protection

B k Protection
Bank
P t ti Summary
S

Capacitor Protection
Fuseless Capacitors
Constr cted of small capacitor elements which
Constructed
hich are arranged in
series and parallel. The elements are constructed of aluminum
foil with a dielectric of electrical grade polypropylene. This
design provides a safe failure mode. In the event that the
dielectric fails, the energy in the resulting small arc punctures
many layers of the thin film and foil within the element. The
arc causes the film layer to receded allowing many layers of the
aluminum foil electrodes to touch and weld together forming an
electrically stable electrical joint.
joint This results in an entire
series section being shorted.

Capacitor Protection
Example of Fuseless Installation

Capacitor Protection
Internally Fused Capacitors
Constr cted such
Constructed
s ch that each element
is protected with a series
connected current limiting fuse.
The design is such that isolated
fusing prevents potential damage
to the adjacent elements and
fuses. The current limiting mode
chops the fault current to prevent
the energy stored in the parallel
connected elements from being
discharged into the faulted
element.

Capacitor Protection

Group Fusing

Individual
d v du Fusing
us g

Capacitor Protection
Group Fusing Considerations for Selecting Fuse
(typical for distribution pole mounted racks)

Continuous Current
Transient Current
Fault Current
Tankk Rupture Curve
C
C di i
Coordination
Voltage on Good Capacitors

Capacitor Protection
Continuous Current
For wye-solidly grounded systems: Fuse > = 135% of rated
capacitor current (includes overvoltage, capacitor tolerances,
and harmonics).
For wye-ungrounded
y
g
systems:
y
Fuse > = 125% of rated
capacitor current (includes overvoltage, capacitor tolerances,
and harmonics).
Care should be taken when using NEMA Type T and K tin links which are rated
y 1.50.
150%. In this case, the divide the fuse ratingg by

Capacitor Protection
Transient Current
Capacitor switching (specifically back-to-back switching)
Lightning surges
Back-to-back is typically
yp
y not a factor for ppole mounted capacitors
p
banks.
High frequency lightning surges:
Use NEMA T tin links for ampere ratings up to 25 A.
Use NEMA K tin links for ampere ratings above 25 A.

Capacitor Protection
Fault Current
Ensure that the fuse can interrupt the available fault current
Tank Rupture Coordination
Ensure that the fuse maximum clearingg TCC curve for the fuse
link is plotted below the capacitor tank rupture curve. In cases of
high fault currents, the tank rupture curve should be compensated
for asymmetry.
asymmetry
Voltage on Good Capacitors
For an ungrounded
d d system, a fault
f l on one phase
h
results
l in
i a 1.73
times overvoltage on the un-faulted phases. Ensure that the fault
p
failure.
is cleared before the second capacitor

Capacitor Protection
Problems with Fusing of Small Ungrounded Banks
Consider a 12.47 kV, 1500 kVAR cap bank made of three (3)
500 kVAR single-phase
i l h
units.
i
1500[kVAR]
69.44[ A] 69.44 1.5 104[ A] 100[ A]Fuse
3 12.47[kV ]

If a capacitor fails, we will expect approximately 3x line current.


pp
y 500 seconds to clear this
It will take a 100 A fuse approximately
fault (3 x 69.44 A = 208.32 A). The capacitor case will rupture
long before the fuse clears the fault.
The solution is using smaller units (explanation to follow).

Capacitor Protection
Individual Fusing Considerations for Selecting Fuse
(typical for substation capacitor banks)

Continuous Current
Transient Current
Fault Current
Tank Rupture Curve Coordination
Voltage on Good Capacitors
Energy Discharge into Faulted Unit
Outrush Current
Coordination with Unbalance Detection System

Capacitor Protection
Continuous Current
Fuse > = 135% of rated capacitor current (includes overvoltage,
capacitor tolerances, and harmonics)
Care should be taken when using NEMA Type T and K tin links which are rated
150% In this case,
150%.
case the divide the fuse rating by 1.50.
1 50

Capacitor Protection
Transient Current
Lightning surges
Capacitor switching (specifically back-to-back switching)
High
g magnitude,
g
, high
g frequency
q
y lightning
g
g surges
g are typically
yp
y not
a concern for substation installations.
Back-to-back
Back
to back switching is typically controlled with pre-insertion
pre insertion
closing resistors or current limiting reactors.
By the
h nature off installation,
i
ll i the
h parallel
ll l fuses
f
will
ill share
h the
h
transient current and will not be a factor.

Capacitor Protection
Fault Current
Ensure that the fuse can interrupt the available fault current.
In substation banks with multiple series groups, fault current will
not flow through
g a failed capacitor
p
unit unless other units
experience a simultaneous failure. For this reason expulsion
fuses are commonly used rather than current limiting fuses
Tank Rupture Coordination
Ensure that the fuse maximum clearing TCC curve for the fuse
li k is
link
i plotted
l d below
b l the
h capacitor
i tankk rupture curve. In cases off
high fault currents, the tank rupture curve should be compensated
y
y
for asymmetry.

Capacitor Protection
Example of a Definite
Tank Rupture Curve.
The time
Th
i between
b
the
h
rupture curve and the
fuse maximum clear
curve is the
coordination margin.

Capacitor Protection
Example of a 10% and 50%
Rupture Curve for a 100 kVAR
Capacitor.
Probability
y based tank rupture
p
curves are developed when there
is too much variance in rupture
test data.
Based on the 10% and 50%
curves, one can extrapolate the
curves for
f any probability.
b bili

Capacitor Protection
Voltage on Good Capacitors
When a short-circuit on one unit occurs, an overvoltage results on
the un-faulted phases. Ensure that the fault is cleared before the
second capacitor failure. A table summarizes this voltage rise on
the un-faulted units

Per Unit Voltage on Un-failed Capacitors

Capacitor Protection
Energy Discharge Into a Failed Unit
When a capacitor failure occurs, the stored energy in the parallel
connected capacitors can discharge thro
through
gh the failed capacitor
and its fuse. The total calculated parallel stored energy should
not exceed the energy capability (Joule rating) of the capacitor
and fuse. If the energy capabilities are exceeded, a failure of the
fuse and/or rupture of the capacitor tank can result.
Typical rating of film capacitors is 15,000 Joules (4650 kVAR in
parallel) and 10,000 Joules (3100 kVAR in parallel) for paperfilm capacitors.
capacitors Expulsion fuses are typically rated 30
30,000
000
Joules. Current limiting fuses are required if ratings are exceeded.
(1 Joule = 1 W x sec
sec, use 00.2
2 cycle clearing time for calculation)

Capacitor Protection
Outrush Current
When a capacitor failure occurs, the parallel connected capacitors
can discharge high frequency current into the failed capacitor.
The fuses of the un-failed capacitors should be able to withstand
the high
g frequency
q
y discharge
g currents. These calculations and
measurements are complex and are determined by the
manufacturer.
Coordination with Unbalance Detection Scheme
The individual fuse must clear the fault before the unbalance
protection
i scheme
h
trips
i the
h entire
i capacitor
i bank.
b k

Capacitor Protection
Fusing Recommendations by McGraw Edison

Capacitor Protection
Recall Problem with Fusing of Small Ungrounded Banks
12.47 kV, 1500 kVAR cap bank made of three (3) 500 kVAR units
1500[kVAR]
69.44[ A] 69.44 1.5 104[ A] 100[ A]Fuse
3 12.47[kV ]

It will take a 100 A fuse approximately 500 seconds to clear this


fault (3 x 69.44 A = 208.32 A). The capacitor case will rupture
long before the fuse clears the fault.
The solution is using smaller units with individual fusing.
Consider five ((5)) 100 kVAR capacitors
p
pper phase,
p
, each with a
25 A fuse. The clear time for a 25 A fuse @ 208.32 A is below
the published capacitor rupture curve.

Capacitor Protection
Why is the Current 3 x Nominal Line Current for a Phase-toNeutral Fault on a Wye-Ungrounded Capacitor Bank?
B

A
N

A
N

VNG
Since V = I*Z, where Z is
constant
t t (assuming
(
i f = 60 hz)
h )
If voltage across capacitor is
increased by 1.732, the current
also increases byy factor of 1.732

IA = 3.0
3 0 p.u.

Capacitor Protection

Minimum Conductor Size


It was noted that capacitors are rated 135% of rating. This
requires the conductor to be sized 135% of the nominal capacitor
rating.
rating

Capacitor Protection
Unbalance Protection
As single-phase units in a multiple unit/phase installation fail and
are removed from service,
service the remaining units are experience an
overvoltage condition. IEEE Standard 1036 provides
overvoltage limitations.
Duration

Max Voltage
(x rated RMS)

6 cycles

2.20

15 ccycles
cles

2 00
2.00

1s

1.70

15 sec

1.40

1 min

1.30

An unbalance protection scheme must by implemented to prevent


g units.
the failure of the overvoltaged

Capacitor Protection

Capacitor Protection

Neutral Voltage Unbalance with Unbalance Compensation

Capacitor Protection

VA

VNG

Normal Conditions
VN = VG
VAN = VBN = VCN

VG VN
VC

VB

Capacitor Protection
Ungrounded or Impedance
Grounded System

VA

VNG

Normal Conditions
VN = VG
VAN = VBN = VCN = 1.0
.0 p.u.

VG VN
VC

VB

Capacitor Protection

VNG
Phase to Neutral Fault
VNG = VLN
VAN = VBN = VLL = 1.732 p.u.

Capacitor Protection

VA

VNG
VG
One Can Removed
VNG = 0.2 p.u.
VCN = 1.2
1 2 p.u.
pu

VC

VN
VB

Capacitor Protection
Ungrounded or Impedance
Grounded System

VA

VNG

Normal Conditions
VN = VG
VAN = VBN = VCN = 1.0
.0 p.u.

VG VN
VC

VB

Capacitor Protection
Ungrounded or Impedance
Grounded System

VA
Gnd
VNG

Ground Fault
VNG = VLN
VAG = VBG = VLL = 1.732
1 732 p.u.
pu

VN
VGC
VC =V
Ground Fault at Cap Bank or
A
Anywhere
h on the
h S
System

VB

Capacitor Protection

Wye-Ungrounded:
Voltage Between
Capacitor Bank Neutral
and Ground vs. Percentage
of Capacitor Units
Removed from Series
Group

Capacitor Protection

Wye-Ungrounded:
Voltage on Remaining
Capacitor Units in Series
Group vs. Percentage of
Capacitor Units Removed
from Series Group

Capacitor Protection

Wye-Grounded:
Neutral Current vs
Percentage of
Capacitor Units
Removed from Series
Group

Capacitor Protection

Wye-Grounded or Delta:
Voltage on Remaining
Units in Series Group vs.
Percentage of Capacitor
Units Removed from
Series Group

Capacitor Protection

Double Wye-Ungrounded,
Neutrals Tied Together:
Neutral Current vs.
Percentage of Capacitor
Units Removed from
Series Group

Capacitor Protection

Double Wye-Ungrounded,
Neutrals Tied Together:
Voltage on Remaining
Capacitor Units in Series
vs. Percentage of
Capacitor Units Removed
from Series Group

Capacitor Protection
A phase

B phase

C phase
P: Number of
units in group
(P=6)

S: Number of
series groups
(S=4)

Reference Figure for Calculations to Follow

Capacitor Protection
# of Series Groups

Grounded Y or Delta

Ungrounded Y

Split Ungrounded Y
(equal sections)

10

10

10

10

10

10

10

10

10

10

11

10

10

11

10

10

10

11

11

11

10

11

11

12 and over

11

11

11

Minimum recommended number of units in parallel per series


Group to limit voltage on remaining units to 110% with one unit out

Capacitor Protection

Many more configurations and


calculations shown in IEEE C37.99

Day 2

Capacitor Fundamentals
Further discussion on capacitor voltage ratings:
On a ungrounded or impedance grounded system, a ground fault
on one phase will cause the other two phases will be elevated by
1 732
1.732.
Does this mean that capacitors must be rated phase-to-phase?
Certainly nothing wrong with this, but cost will be significantly
higher.
g

Capacitor Fundamentals
Recall:

V2
S
XC

This means that a 150 kVAR,


kVAR 12470 V unit applied at 7200 V
will provide only 50 kVAR.
S NEW
S NEW

7200[V ]2

150[kVAR]
2
12470[V ]
50[kVAR]

Capacitor Fundamentals
Using 12470 V capacitors on a 12470 V Ungrounded or
Resistance-Grounded System
y
will require
q
3x more cans.
It should be noted that the 12470 V cans will also be larger than
the 7200 V cans.
cans
Results in a much larger and more costly installation.
This solution would be required if a ground fault could be
maintained for extended pperiods of time.

Capacitor Fundamentals
Perhaps a 150 kVAR or 200 kVAR, 7620 V or 7960 V units
applied at 7200 V would be a better solution.
7200[V ]
150[kVAR ]
2
7620[V ]
134[kVAR ]

S NEW
S NEW

S NEW
OR

OR
2

7200[V ]
150[kVAR ]
2
7960[V ]
123[kVAR ]

S NEW
S NEW

S NEW

7200[V ]2

200[kVAR ]
2
7620[V ]
178[kVAR ]

S NEW
S NEW

7200[V ]2

[kVAR]
2
7960[V ]
163[kVAR ]

Note that the 7620 V unit provides an additional 6%


The 7960 V unit provides an additional 11%

Capacitor Fundamentals
Explusion Fuses:
Provides a means of disconnecting a failed capacitor from the circuit by melting a
tin-lead low current link. The shorted capacitor unit causes a large increase in the
current through the fuse. The current is limited only by the power system
reactance and the other capacitor units in series with the failed capacitor unit. The
pressure is generated by the hot arc making contact with the fiber lining of the
fuse tube. The link is cooled and stretched as it is forced out the tube. The fuse
continues to conduct until a natural current zero occurs. The current zero is
causedd bby th
the power system
t fault
f lt currentt crossing
i zero. If other
th capacitors
it are
connected in parallel with the failed unit, all the stored energy in these capacitors
will be absorbed in either the fuse operation or the failed capacitor unit. Most of
gy is absorbed in the failed capacitor.
p
the energy

Capacitor Fundamentals
Current Limiting Fuses:
Uses a long uniform cross section element. This configuration makes the fuse a
current chopping fuse. The fuse develops a back voltage per inch of element
across the entire length of the element. When this voltage exceeds the available
voltage across the fuse, the fuse forces the arc to extinguish. The result is that a
trapped voltage may and probably will remain on the other capacitors in the
series group. The fuse by its design avoids absorbing all of the available energy
on the series group. This fuse is used for capacitor banks with a large number of
parallel
ll l capacitors.
it
It can be
b usedd on applications
li ti
with
ith essentially
ti ll infinite
i fi it parallel
ll l
stored energy, as long as sufficient back voltage can be developed to force the
current to extinguish. This is the fuse we apply to series, large shunt, and DC
banks.
Because of the high back voltage that is developed, this fuse must be used with
several capacitors in parallel to limit the voltage build up or a flashover may
occur elsewhere in the capacitor rack.
rack

Capacitor Fundamentals
Current Limiting Fuses vs Expulsion Fuses:

Expulsion Fuse

C
Current
Limiting
Li i i Fuse
F

Capacitor Fundamentals
Current Limiting Fuses vs Expulsion Fuses:
Expulsion Fuses
Operate mechanically and provide a visual indication
Require additional space for operation
Typically applied for outdoor application due to ionized gas release.
Combination
C
bi ti expulsion
l i with
ith currentt limiting
li iti characteristic
h
t i ti fuses
f
can be
b usedd in
i
indoor metal-enclosed equipment.
p
Less expensive

Capacitor Fundamentals

Capacitor Fundamentals
Current Limiting Fuses
Do not emit ionized gases during operation.
operation Ionized gases are undesirable
because they can cause bushing and insulator flashovers that result in additional
damage. Do not require ventilation.
Fast current-limiting operation
High interrupting capacity, noiseless operation
Can be specified for indoor and outdoor applications .
No pressure build-up, therefore, no vents or special reinforced compartments are
required.
i d
More expensive

Capacitor Fundamentals
Note no pigtail and blown fuse indication

Capacitor Fundamentals
Current Limiting with Expulsion

Capacitor Fundamentals
What about arresters? How and where should they be
applied?
Depending on application, environment, exposure to
switching etc,
switching,
etc arresters may be necessary.
necessary
We recall that when a travelling wave meets a high
impedance, the wave can double in size. For this reason,
arresters (if used) should be installed as close to the capacitor
bank as ppossible. Installation of arresters at the breaker
feeding the capacitor bank will not do much for protection of
the capacitor bank.

Capacitor Protection
A basic three (3) arrester method is shown below. This is
typical for solidly grounded systems and wye
wye-grounded
grounded
capacitor banks.

Capacitor Protection
Depending on type of installation, system parameters and
level of protection required, a six(6) arrestor method may be
applied.

Capacitor Protection
For an ungrounded system or a high-impedance grounded
system, a four (4) arrestor grounding method might be
considered an wye ungrounded bank.

VLL

Ground Fault
VNG = VLN
VAG = VBG = VLL = 1.732 p.u.

VLL

Phase to Neutral Fault


VNG = VLN
VAN = VBN = VLL = 1.732 p.u.

ArrPH

If faults can be maintained,

ArrN
ArrPH must be rated VLL
ArrN must be rated VLN
The effective arrester MCOV
is VLL + VLN

Capacitor Protection
Note that if a basic three (3) arrester method is applied to an ungrounded bank, the arresters
must be rated high enough to sustain a temporary overvoltage condition during a phase-toground fault on the system. This may not provide an adequate level of protection for the
capacitors.
Phase to Neutral Fault
VNG = VLN
VAN = VBN = VLL = 1.732
1 732 p.u.

Arresters do not provide protection


across the capacitor bushings. Note
that the BIL applies to bushing-tocase insulation.
i l ti

VLL

If faults can be maintained, Arresters


must be rated VLL

VLL

Ground Fault
VNG = VLN
VAG = VBG = VLL = 1.732
1 732 p.u.

Capacitor Protection
Good Presentations on Capacitor Arrester Applications
Guidelines
G
id li
ffor S
Selection
l ti off S
Surge A
Arresters
t ffor Sh
Shuntt
Capacitor Banks ABB Technical Information
Surge Arrester Application of MV-Capacitor Banks to
Mitigate Problems of Switching Restrike CIRED 19th
International Conference on Electricity Distribution,
Distribution Vienna,
Vienna
21-24 May 2007.
Both
B
th off these
th
papers also
l address
dd
phase-to-phase
h
t h
arrester
t
connections.

Harmonics

Harmonics
Recall that the impedance of a capacitor is inversely
proportional to the system frequency.
frequency

1
1
XC

C 2fC
Harmonics flow to the point of lowest impedance. The higher
the harmonic,
harmonic the lower the impedance of the capacitor.
capacitor
As capacitors absorb harmonics, the capacitor heats up and
th life
the
lif expectancy
t
is
i reduced.
d d The
Th voltage
lt
harmonics
h
i stress
t
the capacitor dielectric and reduce the life expectancy of the
capacitor.

Harmonics

Harmonics
Where do harmonics come from?
Power Electronics (drives, rectifiers, computer power
supplies, etc)
Arcingg Devices ((welders,, arc furnaces,, florescent lights,
g , etc))
Iron Saturating Devices (transformers)
Rotating Machines (Generators)
Parallel Resonance (between cap bank and power
equipment)
IEEE Std 519 provides recommended limits of harmonic
distortion at the point-of-common-coupling (PCC) with the
y
utility.

Harmonics

Harmonics

Harmonics
Resonance
When a number of harmonic current sources are injecting currents
into the supply and the frequency of one of the harmonics coincides
with the resonant frequency of the supply transformer and
Power Factor Correction capacitor combination, the system
resonates and a large circulating harmonic current is excited
between these components
components. The result of this is that a large
current at this harmonic flows in the supply transformer, this
resulting in a large harmonic voltage distortion being imposed upon
the load voltage.

Harmonics
A studyy should be pperformed to determine levels of harmonics on a
system to determine if any filters are necessary when installing a
capacitor bank.
Care should be taken to determine if the filtered capacitor bank will
introduce any resonance problems. If resonance problems exist, the
fil design
filter
d i must be
b adjusted.
dj
d

Harmonics

An example of a 13
13.8
8 kV harmonic filter

Capacitor Bank Design Considerations

Design Considerations
So how do we size a capacitor bank?
Determine
D
t
i your primary
i
goall
Voltage support
Lower utility bill (avoid penalties)
Increase capacity of system
It can be all three, or any combination of the above.
Note that correcting to unity power factor at maximum load is
costly
tl andd may nott be
b necessary.

Design Considerations
For a 20 MVA load at 0.88
0 88 power factor (17.6
(17 6 MW,
MW 9.5
9 5 MVAR)
To achieve 95% power factor, a 3.72 MVAR bank is required
To achieve 98% power factor, a 5.93 MVAR bank is required
To achieve unity power factor, a 9.50 MVAR bank is required

Design Considerations
Determine if current limiting reactors or tuning reactors are
required.
Harmonics and resonance may dictate tuning reactors
Back to back switching may require current limiting reactors
Back-to-back
(unless another method is used to mitigate the switching surges,
i.e. pre-insertion closing resistors/reactors, zero-crossing
breakers etc)
breakers,

Design Considerations
Determine the proper voltage.
Capacitors are very susceptible to voltage transients and
harmonics. Increasing the rated voltage increases the protective
margin on the insulation.
The voltage at the capacitor terminals will be higher than bus
voltage
lt
if reactors
t are utilized.
tili d It is
i important
i
t t to
t accountt for
f this
thi
voltage difference.
Determine the voltage swing of the system. Will the capacitors
remain on-line while the facility is lightly loaded.

Design Considerations
We listed some reasons for specifying higher than bus nominal
rating of capacitors. However, care must be taken to ensure that
the kVAR rating is properly adjusted as a result.
Three (6) 150 kVAR, 7960 V wye-connected capacitors provide a
nominal 901 kVAR when connected to a 13.8 kV bus.
Three (6) 150 kVAR, 8320 V wye-connected capacitors provide a
nominal 825 kVAR when connected to a 13.8
13 8 kV bus

Design Considerations
Determine optimal size and number of stages.
Depending
D
di on swing
i in
i plant
l t load,
l d a single
i l bank
b k sized
i d for
f full
f ll
plant capacity may not be the answer.
IEEE 1036 recommends limiting the voltage change to 2-3%. The
delta voltage can be estimated by:
V

MVAR
100%
MVASC

Switch of a capacitor applies high stresses to the insulation.


insulation
Limiting the number of stages and limiting the frequency of
switching will increase the life. Ideally, a capacitor is switched
on and left on.

Design Considerations
Determine best location for the installation
installation. The most effective
placement for power factor correction capacitor banks is at the
load. However, this is not always practical or cost effective.
Typically, a capacitor bank is installed on each bus of a main-tiemain switchgear.
If capacitors are installed at the motor pecker head (running
capacitors) ensure that the capacitor VAR rating does not exceed
capacitors),
90% of the motor no-load VAR. Otherwise, it is possible to
damage the motor by overexcitation.

Design Considerations
Use caution when sizing motor running capacitors.
Logic would suggest that installation of a power factor
correction capacitor at the motor terminals sized to provide
y ppower factor makes sense.
unity
THIS IS NOT THE CASE. Do not exceed 90% of the
motor no-load
no load kVAR demand.
demand Exceeding this value can
result in damage to the motor insulation as a result of
overexcitation.

Design Considerations
As an example for a 4000 V, 4000 hp motor:
100% load current = 495 A @ 89.7% pf
100% load kVAR = 1516 kVAR
No load current = 117 A @ 6.3 % pf
No load kVAR = 809 kVAR
Max size of running capacitor is 0.90
0 90 x 809 kVAR = 728 kVAR

Design Considerations
M: Motor Magnetizing Curve
C1: Capacitor size at 100% motor mag current
C2: Capacitor sized > 100% motor mag current
C4: Capacitor sized < 100% motor mag current

If the capacitive reactance of the capacitor is less less than that of the motor reactance (this occurs
when to large of a capacitor is chosen). This combination of reactance will result in a resonant
frequency below 60 hertz
hertz. Therefore,
Therefore as the motor slows in speed,
speed the frequency of the motor
terminal voltage will decrease from a value of near 60 hertz toward zero. When the motor's terminal
voltage frequency passes through the resonant frequency setup between the capacitor reactance and
the motor reactance, the terminal voltage will become very high, only limited by the properties of the
iron Depending on the inertia of the motor,
iron.
motor this resonance (or high voltage) may be present for a
considerable period of time.

Design Considerations
Determine the most optimal type of installation.
installation
Will the capacitor bank be installed within a fenced substation?
Metal-enclosed, pad mount, or open rack may be good choices
Will the capacitor bank be installed in a process area?
Metal-enclosed or pad mount may be good choices
Will the capacitor bank be pole mounted on a distribution line?

Bank Failures

Design Considerations
Consider the impact to personnel safety adjacent equipment when
deciding between a metal-enclosed and open-rack system.
Porcelain can resemble shrapnel when a capacitor bushing fails.

Design Considerations
Determine the most optimal configuration.
Higher reliability costs more.
y g
(1)
( ) 800 kVAR pper pphase
2400 kVAR,, 13800 V,, wye-grounded
bank will be a smaller footprint and cost less than
2400 kVAR,
kVAR 13800 V
V, wye-ungrounded
wye ungrounded (8) 100 kVAR per
phase bank.
However, the
H
h reliability
li bili off the
h wye-ungrounded
d d bbank
k iis
significantly higher

Design Considerations
Determine the switching equipment
When breakers are used for switching capacitors (single bank
or back-to-back switching), the breakers must be rated for
p
switching.
g
capacitor
IEEE C37.99 provides the equations for calculating the inrush
current and frequency.
frequency

Design Considerations

Design Considerations
Consider a single 4800 kVAR wye-ungrounded bank switched
(with nominal inductance from equipment):
3253A pk @ 600 Hz, the product is 0.20 x 107
Switching a second similar bank on the same bus without
current limiting reactor:
24,058 A pk @ 7.66 kHz, the product is 18.4 x 107
B adding
By
ddi a 100 mH
H current limiting
li i i reactor, the
h inrush
i
h is:
i
p
is 1.7 x 107
7254 A ppk @ 2.31 kHz,, the product

Design Considerations

Design Considerations

Design Considerations
Energization of a single capacitor bank.

Design Considerations

B k b k switching
Back-to-back
i hi off the
h same unit.
i

Design Considerations

E
Example
l off breaker
b k with
i h pre-insertion
i
i resistor.
i

Design Considerations

Another application.

Design Considerations

A Pre-Insertion Manufactures Perspective.


p

Design Considerations
Another concern is voltage amplification as a result of switching a
second capacitor bank.

Design Considerations

Design Considerations
Consider other accessories:
Disconnect switch
Grounding switch
Kirk-keyy interlock
Ventilation requirements
Control power

Design Considerations

Design Considerations

Design Considerations
Be aware that larger medium voltage motors may include
surge
g ppacks.
The surge pack will decrease the crest voltage and rate of
rise of the impending surge.
surge High rates of rise damage end
turns while high crest voltage damage winding to core
insulation.
Typically the capacitance of the is small enough that it can
g
but this should be verified.
be neglected,

Design Considerations

Typical Surge Pack Application

Design Considerations
Do not confuse Harmonic Filter Banks with Power Factor
Correction Banks.
Banks
The voltage ratings of harmonic filter banks are substantially
higher because they are connected on the back end of a tuning
reactor where the voltage is substantially higher. As a result of
thee higher
g e voltage,
vo ge, thee installed
s ed kVAR
V
ccan be anywhere
yw e e from
o
25% to 40% higher than nominal design.
The capacitor cans must be capable of this output.
output

Grounding of Wye Banks


If multiple wye-grounded banks are in close proximity, use
ppeninsula ggrounding
g or single-point
g p
ggrounding.
g
Single-Point Grounding
The neutrals of all banks of a given voltage are connected
together with insulated cable/bus and tied to the ground
grid only at one point. This prevents high-frequency
currents (due
(d to back-to-back
b k b k switching)
i hi ) from
f
flowing
fl i into
i
the ground grid.

Grounding of Wye Banks


Peninsula Grounding
One or more isolated gground ggrid conductors are carried
underneath the capacitor rack of each phase and tied to the
station ground grid at one point at the edge of the capacitor
area All capacitor bank neutral connections are made to
area.
this isolated peninsula ground grid conductor.

Grounding of Wye Banks

Grounding of Wye Banks

References
IEEE Std. 18
IEEE C37.99
NEMA CP-1
IEEE Std 1036
IEEE
IEEE Std 399 (Brown Book)

You might also like