You are on page 1of 12

ON

ELECTRICAL SYSTEM DESIGN

BY
V.D.VAIDYA
RELIANCE PATALA GANGA PROJECT IN 1981 – PHASE - I

SINGLE LINE DIAGRAM


INDUCTION MOTOR 400 KW HAS TO BE INSTALLED FOR SPECIAL PURPOSE.

MOTOR KW RATING X STARTING FACTOR


STARTING KVA OF MOTOR=
RUNNING P.F. X MOTOR EFFICIENCY
400 X 7.2 = 3478.261 KVA
=
0.9 X 0.92

KVA RATING
AMPERE RATING =
1.732 X VOLTAGE

415 V 6.6 KV

AMPERE RATING 4839.12 AMP 304.27 AMP


Wound rotor induction motor qualities.
Excellent starting torque for high inertia loads.
Low starting current compared to squirrel cage induction motor.
Speed is resistance variable over 50% to 100% full speed.
Higher maintenance of brushes and slip rings compared to squirrel cage motor.
The generator version of the wound rotor machine is known as a doubly-fed
induction generator, a variable speed machine.

You might also like