For carrying Short Circuit Test on Power Transformer Do the following: 

1] Isolate the Power Transformer from service. 


2] Remove HV/LV Jumps and Disconnect Neutral from Earth/Ground. 
3] Short LV Phases by Cu/Al plate which could withstand short circuit current and connect these short
circuited terminals to Neutral 
4] Energise HV side by LV supply (440 3ph Supply) with OLTC tap position on Normal. 
5] Measure Current in Neutral, LV line voltages, HV Volatage and HV Line Currents on various OLTC
Tap position. 

Analysis: 
If Neutral current is near to zero transformer windings are OK 
If Neutral current is higher or equal to Line current between LV Phase one of the winding is Open.

Read
more: http://wiki.answers.com/Q/How_do_you_carry_out_short_circuit_test_on_power_transformers