Company:AMKORTECHNOLOGYPHILIPPINES,INC.

P3/P4
ProjectTitle:WastewaterTreatmentPlantandUpgradingofNeutralizationSystem

COMPUTATIONOFAIRCONSUMPTION

Table1.TotalAirConsumptionofAllFloPumps.
Pump
AirConsumption(SCFM)
1. LimeDosingPump
0.8
2. CoagulantDosingPump
0.8
3. FloccculantDosingPump
0.8
4. SlurryPump
8.0
5. ClarifierSludgePump
40.0
6. SludgePump
45.0
TOTAL
95.4

Table2.TotalAirConsumptionforNeutralizationTanks

Tank
AirConsumption(SCFM)
1. NeutralizationTank1
22.46
2. NeutralizationTank2
22.46
TOTAL
44.92

TankVolume:5600gallons=748.611cu.ft
DesignBasis:30SCFM/1000cu.ft

TotalAirRequirement=(30SCFM/1000cu.Ft)x748.6111cu.ft
=22.46scfm