Neutral Grounding

Sector Energy PTI NC


Theodor Connor

Copyright Siemens AG 2008. All rights reserved.

Topics

Introduction Theoretical background Methods applied for neutral grounding Practical aspects

For internal use only. / Copyright Siemens AG 2008. All rights reserved.

Page 1

01.2008

Th. Connor

PTD SE PTI

Significance of earth faults for network operation

December November October September August July June May April March February January

1 year 8760 hours 31 536 000 seconds

Method of neutral earthing has no influence on behaviour in normal operation


For internal use only. / Copyright Siemens AG 2008. All rights reserved.

Page 2

01.2008

Th. Connor

PTD SE PTI

Kaleidoscope of methods available


Isolated neutral Earth fault compensation Solid earthing NOSPE
High-impedance neutral earthing

KNOSPE

Arc suppression Low-impedance neutral earthing Floating neutral Effective earthing Petersen coil

Resonant earthing

Short-time earthing
For internal use only. / Copyright Siemens AG 2008. All rights reserved.

Page 3

01.2008

Th. Connor

PTD SE PTI

Statistical data of German networks


Voltage level
Line lengths Overhead line Cable Amount of faults per 100 km and year Isolated neutral Earth fault compensation Low-impedance neutral earthing 28 000 km 98 000 km 6 23 % 60 % 8% 111 000 km 60 000 km 89 000 km 11 95 % 2% 4 000 km 6 78 % 22 % 17 000 km 16 km 3 100 %

10 kV

20 kV

110 kV

380 kV

Source: VDEW 1993

For internal use only. / Copyright Siemens AG 2008. All rights reserved.

Page 4

01.2008

Th. Connor

PTD SE PTI

Display methods for system values


UL1 UL1

UL1(t) = L1 sint
t t

Mathematical equations Vector display

Time characteristic

UL1

Positive sequence Negative sequence Zero sequence

Phase-related display

Symmetrical components
For internal use only. / Copyright Siemens AG 2008. All rights reserved.

Page 5

01.2008

Th. Connor

PTD SE PTI

The transient phase of an earth fault

Isolated neutral Discharge Charging oscillation

For internal use only. / Copyright Siemens AG 2008. All rights reserved.

Page 6

01.2008

Th. Connor

PTD SE PTI

Characteristics of transient phase

Frequency Discharge Charging oscillation

500 Hz . . . 100 000 Hz 100 Hz . . . 4 000 Hz

Overvoltage factor

kt =

3 2U

LE max

= 1.2...2.7...3.5

For internal use only. / Copyright Siemens AG 2008. All rights reserved.

Page 7

01.2008

Th. Connor

PTD SE PTI

Permanent earth fault

ICE

Isolated neutral

For internal use only. / Copyright Siemens AG 2008. All rights reserved.

Page 8

01.2008

Th. Connor

PTD SE PTI

Vector diagram for system with isolated neutral

UL1

UL1 = 0

UL2 Normal operation

UL2 Earth fault

For internal use only. / Copyright Siemens AG 2008. All rights reserved.

Page 9

01.2008

Th. Connor

PTD SE PTI

Characteristics of power frequent voltage rise

Coefficient of earthing Earth-fault factor


DIN VDE 0111 IEC 71-1

ULE Max ZE = Ub
3

1 3

... 1

cf =

ULE Max Ub

1 ...

For internal use only. / Copyright Siemens AG 2008. All rights reserved.

Page 10

01.2008

Th. Connor

PTD SE PTI

Network calculation 3-phase short-circuit

IK =

UN 3 Z

For internal use only. / Copyright Siemens AG 2008. All rights reserved.

Page 11

01.2008

Th. Connor

PTD SE PTI

Network calculation Symmetrical components


U1L1

Positive sequence
U1L2 UL1 U2 L1

U1 = 3 (UL1+ a UL2+ a UL3)

U2 L3 UL3 UL2

Negative sequence

U2 =

1 (UL1+ a UL2+ a UL3) 3

U0 L1

Zero sequence

U0 = 3 (UL1 + UL2 + UL3)

For internal use only. / Copyright Siemens AG 2008. All rights reserved.

Page 12

01.2008

Th. Connor

PTD SE PTI

Symmetrical components Example

a2 UT a US UR U1

a2

US UR

a UT

U2

US UR UT
Page 13 01.2008 Th. Connor

U0
PTD SE PTI

For internal use only. / Copyright Siemens AG 2008. All rights reserved.

Symmetrical components Example


a2 UT

a US UR

U1

U2

U0
For internal use only. / Copyright Siemens AG 2008. All rights reserved.

Page 14

01.2008

Th. Connor

PTD SE PTI

Symmetrical components Line to ground fault


I 1 = I R + I S a + I T a2 I 2 = I R + I S a2 + I T a I0 = IR + IS + IT
T IS = 0 S

Boundary requirements at the fault location are fulfilled by series connection of component systems

Positive sequence

R UR = 0

Negative sequence Boundary requirements at the fault location IS = IT = 0 UR = 0 Zero sequence

For internal use only. / Copyright Siemens AG 2008. All rights reserved.

Page 15

01.2008

Th. Connor

PTD SE PTI

Fault current calculation System with isolated neutral

Positive sequence ~

Negative sequence

Zero sequence

IF =

3 UN Z1 + Z2 + Z0

For internal use only. / Copyright Siemens AG 2008. All rights reserved.

Page 16

01.2008

Th. Connor

PTD SE PTI

Isolated neutral

ICE ICE - capacitive earth fault current

ICE = 3 UN C0
Isolated neutral

Transient overvoltages kt 3.0 Voltage rise of the fault-free phases cf 3 ICE = f (Type of lines, voltage level, size of network) Operation under permanent earth fault possible

For internal use only. / Copyright Siemens AG 2008. All rights reserved.

Page 17

01.2008

Th. Connor

PTD SE PTI

Estimation of capacitive earth fault current


Line type Overhead lines 110 kV 20 kV 10 kV Cables Oil cable XLPE cable Lead-sheath cable XLPE cable Lead-sheath cable XLPE cable 110 kV 110 kV 20 kV 20 kV 10 kV 10 kV 13.3 ... 36.1 A/km 7.5 ... 11.4 A/km 2.2 ... 5.3 A/km 1.6 ... 4.4 A/km 1.2 ... 2.7 A/km 1.2 ... 3.3 A/km 0.36 0.06 0.03 A/km A/km A/km Voltage level Capacitive earth fault current ICE

For internal use only. / Copyright Siemens AG 2008. All rights reserved.

Page 18

01.2008

Th. Connor

PTD SE PTI

Intermittent earth fault

-0,5

First earth fault

Recovery

Second earth fault

Ice (t2) = 0
For internal use only. / Copyright Siemens AG 2008. All rights reserved.

Page 19

01.2008

Th. Connor

PTD SE PTI

Intermittent earth fault

First earth fault Recovery Second earth fault

For internal use only. / Copyright Siemens AG 2008. All rights reserved.

Page 20

01.2008

Th. Connor

PTD SE PTI

Ferro resonances
Prerequisite: Circuit with non linear characteristic e.g. saturation on reactance Principle: Driving voltage UN From operational point 1 to point 2 But operational point 2 not stable Current reversal to operational point 3 Types: Nominal frequency, 3rd harmonic Trigger: Switching events
Page 21 01.2008 Th. Connor

About 2nd harmonic About 0.5 nominal frequency (subharmonic)


For internal use only. / Copyright Siemens AG 2008. All rights reserved.

PTD SE PTI

Ferro resonances

Example in three phase system: Stable ferro resonance of 2nd harmonic level No disturbance of phase to phase voltage URS Possible configurations: Single phase voltage transformer with bus bar or short cable Energising reactor via short cable
For internal use only. / Copyright Siemens AG 2008. All rights reserved.

Page 22

01.2008

Th. Connor

PTD SE PTI

Earth fault compensation

Petersen coil

Ires

Ires - Residual current

Earth fault compensation

Transient overvoltages kt 2.7 Voltage rise of the fault-free phases cf 3 Ires = f (Detuning, Harmonics, quality factor of the coil ) Transient earth faults Operation under permanent earth fault possible Extinction limit

For internal use only. / Copyright Siemens AG 2008. All rights reserved.

Page 23

01.2008

Th. Connor

PTD SE PTI

Fault current calculation System with earth fault compensation

Positive sequence

Negative sequence

Zero sequence

For internal use only. / Copyright Siemens AG 2008. All rights reserved.

Page 24

01.2008

Th. Connor

PTD SE PTI

Estimation of residual current

Line type Overhead lines

Voltage level 110 kV 20 kV 10 kV

Residual current Ires approx. 5 % of ICE approx. 8 % of ICE approx. 8 % of ICE


i.e. 8 A per 100 A coil current

Cables

110 kV 20 kV 10 kV

i.e. 3 A per 100 A coil current

approx. 2 % of ICE approx. 3 % of ICE approx. 3 % of ICE

For internal use only. / Copyright Siemens AG 2008. All rights reserved.

Page 25

01.2008

Th. Connor

PTD SE PTI

Reappearing of phase voltage

Exact tuning v = 0 Tuning v = -10

For internal use only. / Copyright Siemens AG 2008. All rights reserved.

Page 26

01.2008

Th. Connor

PTD SE PTI

Solid earthing

Ik1 Ik1 short-circuit current


Solid earthing

Transient overvoltages kt < 1.8 Voltage rise of the fault-free phases cf 1.4 Ik1 = f (Short-circuit capacity, zero-sequence impedance) Ik1 ~ Ik3 Selective fault clearing

For internal use only. / Copyright Siemens AG 2008. All rights reserved.

Page 27

01.2008

Th. Connor

PTD SE PTI

Fault current calculation Solid earthing

Positive sequence

Negative sequence

Zero sequence

I k1 = 3I0 =

3 UN Z1 + Z2 + Z0

For internal use only. / Copyright Siemens AG 2008. All rights reserved.

Page 28

01.2008

Th. Connor

PTD SE PTI

Vector diagram for system with solid earthing

UL1

UL1 = 0

UL2 Normal operation 1-phase short circuit

UL2

For internal use only. / Copyright Siemens AG 2008. All rights reserved.

Page 29

01.2008

Th. Connor

PTD SE PTI

Examples for zero-sequence impedances of lines


Line type Overhead lines 110 kV 20 kV 10 kV Cables
Oil cable XLPE cable Lead-sheath cable XLPE cable Lead-sheath cable XLPE cable

Voltage level Zero sequence Zero sequence resistance R'0 reactance X'0

0.4 ... 0.2 /km 0.6 ... 0.2 /km 0.6 ... 0.2 /km

1.0 ... 1.5 /km 1.5 /km 1.6 /km

110 kV 110 kV 20 kV 20 kV 10 kV 10 kV

0.8 ... 0.4 /km 0.6 ... 0.5 /km 0.6 ... 0.4 /km 0.6 ... 0.4 /km 2.0 ... 1.1 /km 3.2 ... 1.4 /km

0.4 ... 0.2 /km 0.3 ... 0.2 /km 0.4 ... 0.3 /km 0.3 ... 0.2 /km 0.5 ... 0.2 /km 0.9 ... 0.3 /km

For internal use only. / Copyright Siemens AG 2008. All rights reserved.

Page 30

01.2008

Th. Connor

PTD SE PTI

Low-impedance neutral earthing

Ik1 Ik1 1-phase short-circuit current


Low-impedance neutral earthing

Transient overvoltages for earthing via resistor kt 1.8 Transient overvoltages for earthing via reactor kt 2.7 Voltage rise of the fault-free phases cf 3 Ik1 = f (Neutral impedance, fault location) Ik1 << Ik3 Selective fault clearing

For internal use only. / Copyright Siemens AG 2008. All rights reserved.

Page 31

01.2008

Th. Connor

PTD SE PTI

Fault current calculation Low-impedance neutral earthing

Positive sequence

Negative sequence

Zero sequence

I k1 = 3I0 =

3 UN Z1 + Z2 + Z0

For internal use only. / Copyright Siemens AG 2008. All rights reserved.

Page 32

01.2008

Th. Connor

PTD SE PTI

High-impedance neutral earthing

IF IF - Earth fault current


High-impedance neutral earthing

Transient overvoltages kt 2.7 Voltage rise of the fault-free phases cf 3 IF =

I +I
R

2 CE

IR ICE

Selective fault clearing possible

For internal use only. / Copyright Siemens AG 2008. All rights reserved.

Page 33

01.2008

Th. Connor

PTD SE PTI

Fault current calculation System with high-impedance neutral earthing

Positive sequence

Negative sequence

Zero sequence

For internal use only. / Copyright Siemens AG 2008. All rights reserved.

Page 34

01.2008

Th. Connor

PTD SE PTI

Practical aspects

Methods applied Criteria for comparison High voltage systems Medium voltage systems Isolated neutral Resonant grounding Low impedance neutral grounding

For internal use only. / Copyright Siemens AG 2008. All rights reserved.

Page 35

01.2008

Th. Connor

PTD SE PTI

Neutral earthing practice in Germany


380/220 kV 110 kV Interconnected systems Regional systems City system (cable) 20 kV Regional & urban network Urban cable network 10 kV Small network Large network Urban cable network Industry 5 ... 20 kV Small systems Large systems NE EFC (Bavaria NG) NE with limitation EFC or EFC with SE NE IS EFC or EFC with SE NE IS EFC IK1 = 1.5 ... 2 kA ICE = 20 ... 100 A ICE 500 A IK1 = 1 ... 2 kA ICE = 5 ... 30 A ICE 300 A
EFC = Earth fault compensation

IK1 IK3

IK1 = 5 ... 10 kA

NE = Low-impedance neutral earthing

IS = Isolated neutral

SE = Short time earthing

For internal use only. / Copyright Siemens AG 2008. All rights reserved.

Page 36

01.2008

Th. Connor

PTD SE PTI

Criteria for comparison of methods

Voltage stress Current stress Destruction at the fault location Potential rise Inductive interference; EMC Operational aspects Fault detection Fault localisation Amount of switching required Fail safe situation Investment costs Development in the future
For internal use only. / Copyright Siemens AG 2008. All rights reserved.

Page 37

01.2008

Th. Connor

PTD SE PTI

Earth fault transients and voltage rise

Isolated neutral Earth fault compensation ICE = 100 A


Fault duration min ... h

Low-impedance neutral earthing Ik1 = 1.5 kA Neutral resistor

Fault duration ms
For internal use only. / Copyright Siemens AG 2008. All rights reserved.

Page 38

01.2008

Th. Connor

PTD SE PTI

Fault current and voltage rise during earth fault

U / ULE IK1 / IK3


1.8

1.6

1.4

1.2

Voltages of the fault-free phases U / ULE

1.0

0.8

0.6

0.4

Fault current IK1 / IK3

0.2

0 0 2 4 6 8 10

Z0 / Z1

Solid Effective neutral earthing Low-impedance neutral earthing

Isolated neutral Earth fault compensation High-impedance neutral earthing


For internal use only. / Copyright Siemens AG 2008. All rights reserved.

Page 39

01.2008

Th. Connor

PTD SE PTI

Fault current and voltage rise during earth fault

N S

Neutral earthing with voltage rise below 1.4 Neutral earthing with voltage rise exceeding 1.4

W Low impedance neutral earthing K I Earth fault compensation Isolated neutral

For internal use only. / Copyright Siemens AG 2008. All rights reserved.

Page 40

01.2008

Th. Connor

PTD SE PTI

Neutral earthing in high voltage networks

IK1 IK3

IK1< IK3

IK1< IK3

For internal use only. / Copyright Siemens AG 2008. All rights reserved.

Page 41

01.2008

Th. Connor

PTD SE PTI

Required protection for transmission systems

Low-impedance neutral earthing (110 kV ... 380 kV) Overhead line Distance protection, Overcurrent protection (Back-up) 1-phase auto reclosure Cable Differential protection, Distance protection , Overcurrent protection (Back-up) Earth fault compensation (110 kV) Overhead line Transient earth fault relay Cable For internal use only. / Copyright Siemens AG 2008. All rights reserved.

Page 42

01.2008

Th. Connor

PTD SE PTI

Operational aspects System with isolated neutral

3I0A

3I0B

ICE

3I0C 3I0E 3I0D

For internal use only. / Copyright Siemens AG 2008. All rights reserved.

Page 43

01.2008

Th. Connor

PTD SE PTI

Determination of zero sequence voltage

L1 L2 L3

UN
3

UL1 + UL2 + UL3 = 3 U0


100V
3

58 V Normal operation 100 V Earth fault


3 U0

Open delta winding

100V 3

100 V Earth fault

For internal use only. / Copyright Siemens AG 2008. All rights reserved.

Page 44

01.2008

Th. Connor

PTD SE PTI

Determination of earth fault current Holmgreen

L1 L2 L3

IL1 + IL2 + IL3= 3 I0

Relay

For internal use only. / Copyright Siemens AG 2008. All rights reserved.

Page 45

01.2008

Th. Connor

PTD SE PTI

Operational aspects System with earth fault compensation

Icoil 3I0A

3I0B

Ires

3I0C 3I0E

Icoil

3I0D

For internal use only. / Copyright Siemens AG 2008. All rights reserved.

Page 46

01.2008

Th. Connor

PTD SE PTI

Petersen coil details

Type of coil Fixed coil Tapped coil Plunger coil 1:3 1:10

Connection point to network neutral Feeding transformer Neutral busbar Earthing transformer

Plunger coil with controller Location of coil in the network Central compensation Distributed coils in the network

For internal use only. / Copyright Siemens AG 2008. All rights reserved.

Page 47

01.2008

Th. Connor

PTD SE PTI

Earth fault compensation Types of Petersen coil


Plunger coils for medium voltage

Fixed coil for 110 kV

For internal use only. / Copyright Siemens AG 2008. All rights reserved.

Page 48

01.2008

Th. Connor

PTD SE PTI

Tuning of Petersen coil

IE Uneutral

Earth fault current


in case of fault

Overhead line

Voltage of neutral point


in normal operation Cable
under-compensated over-compensated

tuning

For internal use only. / Copyright Siemens AG 2008. All rights reserved.

Page 49

01.2008

Th. Connor

PTD SE PTI

Double earth fault current distribution

L3 L1 L2

L3 L2 L1

L3 L2 L1

IEE IK2 =

3
2

IK3

For internal use only. / Copyright Siemens AG 2008. All rights reserved.

Page 50

01.2008

Th. Connor

PTD SE PTI

Directional earth fault relay

U0

U0

Ires ICE ICE Icoil

Capacitive directional earth fault relay

Wattmetric directional earth fault relay

For internal use only. / Copyright Siemens AG 2008. All rights reserved.

Page 51

01.2008

Th. Connor

PTD SE PTI

Required protection relays for earth fault detection


Signalling relay for zero sequence voltage Central earth fault detection relay Directional earth fault relay
Overcurrent relay with directional earth fault relay Distance relay with directional earth fault relay Differential relay + Back-up overcurrent relay with directional earth fault relay

Transient earth fault relay

For internal use only. / Copyright Siemens AG 2008. All rights reserved.

Page 52

01.2008

Th. Connor

PTD SE PTI

Determination of residual current Window type current transformer

3 I0 = IL1 + IL2 + IL3

L1 L2 L3

I Fault

I Sheath I Earth

For internal use only. / Copyright Siemens AG 2008. All rights reserved.

Page 53

01.2008

Th. Connor

PTD SE PTI

Transient earth fault relay

L1

L2

L3

t [ms]
For internal use only. / Copyright Siemens AG 2008. All rights reserved.

Page 54

01.2008

Th. Connor

PTD SE PTI

Transient earth fault relay Fault indication survey

For internal use only. / Copyright Siemens AG 2008. All rights reserved.

Page 55

01.2008

Th. Connor

PTD SE PTI

Increase of residual current

3I0ZA

3I0ZA

3I0ZB

3I0ZA

IAdditional

Ires

+ IAdditional

For internal use only. / Copyright Siemens AG 2008. All rights reserved.

Page 56

01.2008

Th. Connor

PTD SE PTI

Pulsating residual current

Icoil ICE

Ires

IPulse

IPulse

For internal use only. / Copyright Siemens AG 2008. All rights reserved.

Page 57

01.2008

Th. Connor

PTD SE PTI

Detection by 5th harmonic

ICoil ICE

Ires

For internal use only. / Copyright Siemens AG 2008. All rights reserved.

Page 58

01.2008

Th. Connor

PTD SE PTI

Combined method Earth fault compensation with phase grounding

Icoil 3I0A

3I0B

Ires

3I0C 3I0E

Icoil

3I0D

For internal use only. / Copyright Siemens AG 2008. All rights reserved.

Page 59

01.2008

Th. Connor

PTD SE PTI

Combined method Earth fault compensation with phase grounding

3I0A

3I0B

3I0C 3I0E

Icoil

3I0D

Ires

Icoil

3I0

For internal use only. / Copyright Siemens AG 2008. All rights reserved.

Page 60

01.2008

Th. Connor

PTD SE PTI

Combined method Earth fault compensation with phase grounding

L3 L1 Load current L2

L3 L2 L1

L3 L2 L1

Induced loop current

For internal use only. / Copyright Siemens AG 2008. All rights reserved.

Page 61

01.2008

Th. Connor

PTD SE PTI

Combined method Residual current compensation

Icoil 3I0A

3I0B

Ires = 0

3I0C 3I0E

Icoil

3I0D

Ires

For internal use only. / Copyright Siemens AG 2008. All rights reserved.

Page 62

01.2008

Th. Connor

PTD SE PTI

Earth fault trial in 20 kV network


System circuit
110/20kV

150 2

3I0 in A
0

0.40

0.45

0.50

0.55

t/sec.

Residual current

1.6

1.2 150 2 1 pu 0.8 0 0.4

3I0 in A

0.0 0.40 0.45 0.50 0.55 t/sec. 0 1 2 3 4 5 6 7 8 9 10 12 f/fg 14

3I0 in the feeding cable

Harmonic analysis of residual current

For internal use only. / Copyright Siemens AG 2008. All rights reserved.

Page 63

01.2008

Th. Connor

PTD SE PTI

Earth fault trial in compensated network Voltages and current at the fault location
U [kV]

20 kV

110 kV
t [ms]

Ires

Ires [A]

Ires [A]

t [ms]

t [ms]

For internal use only. / Copyright Siemens AG 2008. All rights reserved.

Page 64

01.2008

Th. Connor

PTD SE PTI

Operational aspects System with low-impedance neutral earthing

3I0 = IK1

IK1

Ineutral IK1 >> ICE Fault current indicator

For internal use only. / Copyright Siemens AG 2008. All rights reserved.

Page 65

01.2008

Th. Connor

PTD SE PTI

Comparison of neutral resistor and reactor

UR US UT IR t

UR US UT IR t

Neutral resistor

Neutral reactor

For internal use only. / Copyright Siemens AG 2008. All rights reserved.

Page 66

01.2008

Th. Connor

PTD SE PTI

Short circuit trial Voltages at medium- and low-voltage level


U [kV]

t [ms]

10 kV

U [V]

0.4 kV
t [ms]

For internal use only. / Copyright Siemens AG 2008. All rights reserved.

Page 67

01.2008

Th. Connor

PTD SE PTI

Low-impedance neutral earthing Design types of neutral resistors

For internal use only. / Copyright Siemens AG 2008. All rights reserved.

Page 68

01.2008

Th. Connor

PTD SE PTI

Low-impedance neutral earthing Connection possibilities for a neutral resistor

110 kV

110 kV

110 kV

10 (20) kV

10 (20) kV

10 (20) kV

For internal use only. / Copyright Siemens AG 2008. All rights reserved.

Page 69

01.2008

Th. Connor

PTD SE PTI

Low-impedance neutral earthing Design types of earthing transformers

Earthing transformer for 6 kV

Earthing transformer with increased zero sequence impedance for 10 kV

For internal use only. / Copyright Siemens AG 2008. All rights reserved.

Page 70

01.2008

Th. Connor

PTD SE PTI

Required protection for low-impedance neutral earthing

3phase protection equipment necessary Overcurrent relay sensitive earth fault detection 0.1 IN Distance protection Overcurrent pick-up Earth fault for loop selection Impedance pick-up in meshed networks Transformer differential protection Suppression of neutral current

For internal use only. / Copyright Siemens AG 2008. All rights reserved.

Page 71

01.2008

Th. Connor

PTD SE PTI

Test circuit for measurements

Remote station

Feeding station

Current source

Test voltage Active power

UE
V

Test current Sheath current

Earth current

Uind

Z0

For internal use only. / Copyright Siemens AG 2008. All rights reserved.

Page 72

01.2008

Th. Connor

PTD SE PTI

Combined method Short term neutral earthing for detection

IK1

Fault current indicator

Ires/ IK1/ Ires

Short term earthing for detection

tSE < tprotection

For internal use only. / Copyright Siemens AG 2008. All rights reserved.

Page 73

01.2008

Th. Connor

PTD SE PTI

Combined method Reverse short term neutral earthing

IK1

Fault current indicator

IK1/ Ires

Short term earthing for detection

tSE < tprotection

For internal use only. / Copyright Siemens AG 2008. All rights reserved.

Page 74

01.2008

Th. Connor

PTD SE PTI

Combined method Short term neutral earthing for trip

IK1

Fault current indicator

Ires/ IK1

Short term earthing for trip

tSE > tprotection

For internal use only. / Copyright Siemens AG 2008. All rights reserved.

Page 75

01.2008

Th. Connor

PTD SE PTI

Comparison of neutral earthing schemes France - Germany

Cable system
France Germany France

Overhead line system


Germany

Ik1 max = 1000A

Ik1 max = 300A

Ik1 max = 2000A

Trip

For internal use only. / Copyright Siemens AG 2008. All rights reserved.

Page 76

01.2008

Th. Connor

PTD SE PTI