CONTROL OF ACTIVE POWER


AND FREQUENCY

Copyright P. Kundur
This material should not be used without the author's consent
1539pk
C- 1
Active Power and Frequency Control
The frequency of a system is dependent on active
power balance
As frequency is a common factor throughout the
system, a change in active power demand at one
point is reflected throughout the system
Because there are many generators supplying
power into the system, some means must be
provided to allocate change in demand to the
generators
speed governor on each generating unit provides
primary speed control function
supplementary control originating at a central
control center allocates generation
In an interconnected system, with two or more
independently controlled areas, the generation
within each area has to be controlled so as to
maintain scheduled power interchange
The control of generation and frequency is
commonly known as load frequency control (LFC)
or automatic generation control (AGC)
1539pk
C- 2
Primary Speed Controls
Isochronous speed governor
an integral controller resulting in constant speed
not suitable for multimachine systems; slight
differences in speed settings would cause them
to fight against each other
can be used only when a generator is supplying
an isolated load or when only one generator in a
system is required to respond to load changes
Governor with Speed Droop
speed regulation or droop is provided to assure
proper load sharing
a proportional controller with a gain of 1/R
If precent regulation of the units are nearly equal,
change in output of each unit will be nearly
proportional to its rating
the speed-load characteristic can be adjusted by
changing governor settings; this is achieved in
practice by operating speed-changer motor
1539pk
C- 3

r
= rotor speed Y = valve/gate position
P
m
= mechanical power

Figure 11.7 Response of generating unit with isochronous governor
Figure 11.6 Schematic of an isochronous governor
1539pk
C- 4
Figure 11.8 Governor with steady-state feedback
(a) Block diagram with steady-state feedback
(b) Reduced block diagram
Figure 11.9 Block diagram of a speed governor with droop
1539pk
C- 5
Percent Speed Regulation or Droop
100 x
100 x
change output power percent
change frequency or speed percent
R Percent
0
FL NL
|
|
.
|

\
|
e
e e
=
=
where

NL
= steady-state speed at no load

FL
= steady-state speed at full load

0
= nominal or rated speed


For example, a 5% droop or regulation means that a 5%
frequency deviation causes 100% change in valve position or
power output.
Figure 11.10 Ideal steady-state characteristics of a governor with
speed droop
1539pk
C- 6
Load Sharing by Parallel Units
1
1 1 1
R
f
P P P
A
= ' = A
2
2 2 2
R
f
P P P
A
= ' = A
1
2
2
1
R
R
P
P
=
A
A
Figure 11.12 Response of a generating unit with a governor having
speed-droop characteristics
Figure 11.11 Load sharing by parallel units with drooping
governor characteristics
1539pk
C- 7
Control of Generating Unit Power Output
Relationship between speed and load can be adjusted
by changing "load reference set point"
accomplished by operating speed-changer motor

Effect of load reference control is depicted in Figure
11.14
three characteristics representing three load
reference settings shown, each with 5% droop
at 60 Hz, characteristic A results in zero output;
characteristic B results in 50% output;
characteristic C results in 100% output

Power output at a given speed can be adjusted to any
desired value by controlling load reference

When two or more units are operating in parallel:
adjustment of droop establishes proportion of load
picked up when system has sudden changes
adjustment of load reference determines unit output
at a given frequency
1539pk
C- 8
(b) Reduced block diagram of governor
(a) Schematic diagram of governor and turbine
Figure 11.13 Governor with load reference control
Figure 11.14 Effect of speed-changer setting on governor characteristic
1539pk
C- 9
Composite System Regulating
Characteristics
System load changes with freq. With a load damping
constant of D, frequency sensitive load change:

A P
D
= D. A f
When load is increased, the frequency drops due to
governor droop;

Due to frequency sensitive load, the net reduction in
frequency is not as high.

As illustrated in Figure 11.17, the composite
regulating characteristic includes prime mover
characteristics and load damping.

An increase of system load by AP
L
(at nominal
frequency) results in
a generation increase of AP
G
due to governor
action, and
a load reduction of AP
D
due to load characteristic
1539pk
C- 10
The composite frequency response characteristic is normally
expressed in MW/Hz. It is also sometimes referred to as the stiffness
of the system.

The composite regulating characteristic of the system is equal to 1/
( )
D R
P
D R R R
P
f
eq
L
n
L
SS
+
A
=
+ + + +
A
= A
1
1 1 1
2 1
where
D
R f
P
R R R
R
eq SS
L
n eq
eq
+ =
A
A
=
+ + +
=
1
1 1 1
1
2
|
Figure 11.17 Composite governor and load characteristic
1539pk
C- 11
Supplementary Control of Isolated
Systems
With primary speed control, the only way a change
in generation can occur is for a frequency deviation
to exist.
Restoration of frequency to rated value requires
manipulation of the speed/load reference (speed
changer motor).
This is achieved through supplementary control as
shown in Figure 11.22
the integral action of the control ensures zero
frequency deviation and thus matches generation
and load
the speed/load references can be selected so that
generation distribution among units minimizes
operating costs
Supplementary control acts more slowly than
primary control.

This time-scale separation important for satisfactory
performance.
1539pk
C- 12
Figure 11.22 Addition of integral control on generating units
selected for AGC
1539pk
C- 13
Supplementary Control of Interconnected
Systems
The objectives of automatic generation control are
to maintain:
system frequency within desired limits
area interchange power at scheduled levels
correct time (integrated frequency)
This is accomplished by using a control signal for
each area referred to as area control error (ACE),
made up of:
tie line flow deviation, plus
frequency deviation weighted by a bias factor
Figure 11.27 illustrated calculation of ACE
Bias factor, B, set nearly equal to regulation
characteristic (I/R + D) of the area; gives good
dynamic performance
A secondary function of AGC is to allocate
generation economically
1539pk
C- 14
Figure 11.27 AGC control logic for each area
1539pk
C- 15
Figure 11.28 Functional diagram of a typical AGC system
1539pk
C- 16
Underfrequency Load Shedding
Severe system disturbances can result in cascading
outages and isolation of areas, causing formation of
islands
If an islanded area is undergenerated, it will experience
a frequency decline
unless sufficient spinning generation reserve is
available, the frequency decline will be determined by
load characteristics (Fig. 11.30)
Frequency decline could lead to tripping of steam
turbine generating units by protective relays
this will aggravate the situation further
There are two main problems associated with
underfrequency operation related to thermal units:
vibratory stress on long low-pressure turbine blades;
operation below 58.5 Hz severely restricted (Fig. 9.40)
performance of plant auxiliaries driven by induction
motors; below 57 Hz plant capability may be severely
reduced or units may be tripped off
1539pk
C- 17
Fig. 11.30 Frequency decay due to generation deficiency (AL)
Fig. 9.40 Steam turbine partial or full-load operating limitations during
abnormal frequency, representing composite worst-case limitations of five
manufacturers ANSI/IEEE-1987
1539pk
C- 18
Underfrequency Load Shedding (cont'd)
To prevent extended operation of separated areas at low
frequency, load shedding schemes are employed.
A typical scheme:
10% load shed when frequency drops to 59.2 Hz
15% additional load shed when frequency drops to 58.8 Hz
20% additional load shed when frequency reaches 58.0 Hz

A scheme based on frequency alone is generally acceptable
for generation deficiency up to 25%

For greater generation deficiencies, a scheme taking into
account both frequency drop and rate-of-change of
frequency provides increased selectivity
Ontario Hydro uses such a frequency trend relay
Fig. 11.31 Tripping logic for frequency trend relay