Professional Documents
Culture Documents
The flows of active and reactive p power in a transmission network are fairly independent
P is closely related to frequency y Q is i closely l l related l t d to t voltage lt
y
Pe = PL + Dr
D is load damping coefficient expressed as % change in load for 1% change in frequency. y Load may be frequency dependent or independent
y
ISOCHRONOUS GOVERNOR
Constant speed p | Isochronous governor adjusts the turbine valve/gate to bring the frequency back to the nominal i l or scheduled h d l d value. l
|
ISOCHRONOUS GOVERNOR
Increase in load results in frequency q y decay y at a rate determined by the inertia of the rotor | As speed drops, Pm begins to increase and hence reduces d the th rate t at t which hi h speed d is i reducing d i
|
ISOCHRONOUS GOVERNOR
It works satisfactorily y when g generator is supplying isolated load | Only one generator in multi-gen system is required i d to t respond d | Isochronous generators cannot be used with two or more units connected to the same system
| y |
DROOP
Defintion: The ratio of speed p deviation or frequency deviation to change in valve/gate position or power output | 5% droop d or regulation l ti means that th t 5% frequency f deviation causes 100% change in valve position or power output
|
10
f R1 f R2
P2 = P2' P2 =
P R 1 = 2 P2 R1
Amount of load picked up by each unit depends on droop characteristic If % of regulation of units is nearly equal, the change in the output of each unit will be nearly in proportion to its rating
11
12
The relationship between speed and load is adjusted by changing an input reference
y
Load reference set point The output of each unit at any given system frequency can be varied only by changing LRSP.
13
LRSP has minimum effect on frequency Depends on size of other generators LRSP adjusts frequency
14
15
16
Objectives
y
Primary: a y:
|
Regulate frequency to the specified nominal value and to maintain the interchange power between control areas at the scheduled values Distribute the required change in generation among units to minimize operating costs.
17
Secondary:
|
18
19
20
21
22
With B1 = 1 and B2 = 2
y
Only the supplementary control in area 1 will respond to load change in area 1 and changes generation to bring ACE1 to zero y The change is not observable in area 2
With
y
B1 = 21 B2 = 2 2 Both supplementary controls would responds to deviation twice as fast. y Generation picked up by area 2 will be backed off
and
23