Professional Documents
Culture Documents
Vessel Sizing
and Level
Instrumentation
When sizing process vessels, it is important to
consider instrumentation. Consistent, safe
and reliable results depend on it
installed can adversely affect the usable vessel volume by reducing the
span that is visible to the operator
and the control system.
This article presents best practices
in vessel sizing and level-instrument
selection and installation. Practical
examples demonstrate the recommended holistic approach.
Vessel sizing
Chad Schaffer
Burns & McDonnell
1,000 gal/min
Orion Instruments
Figure 3.
A magnetic
level gage can
address the limitations associated with simple
gage glasses
Figure 1. In Method 1, vessels are sized based on flowrates and residence time
1,000 gal/min
H LL
5,000 gal liquid between HLL and LLL
LLL
1,000 gal/min
Figure 2. Method 2 recommends sizing based on residence time between the highlevel limit (HLL) and low-level limit (LLL) of operation
ing a small amount of time optimizing the design with some additional
knowledge can pay big dividends in
how much operating range is actually
available in the vessel.
Level transmitters and switches provide a method for the level in the vessel to be read remotely. They are used
to provide automatic level control and
alarms to indicate upset conditions
and trigger operator response. They
can also be used to automatically
bring the process to a safe state if the
operating limits are reached. Many
transmitter and switch technologies
are available, and no single technology
will suit all applications.
31
Level bridle
Cover Story
The measuring range of a transmitter is typically specified to be the same
as or slightly less than (usually 46 in.)
the measuring range of the local level
gage. This allows the output of the
transmitter to be directly compared to
the visual indicator to check its calibration and ensure it is functioning
properly. The transmitter range should
rarely exceed the gage visible range,
since this makes verifying the high and
low limits of the transmitter in situ difficult, if not impossible. Conversely, any
vessel volume that is viewable by the
local gage but not measurable by the
transmitter is generally not available
for use in the operating range.
The working operating range of the
liquid level should not extend past the
alarm points, and by definition cannot
extend past the shutdown points.
Typically the vessel percent full as
read by the level instrument correlates
to percent of level instrument span,
and does not equate to percent of actual vessel volume. A vessel strapping
table should be developed and used to
convert percent level readings to percent of vessel volume. Most modern
control systems can be programmed
with an equation to convert automatically, if desired.
The alarm and shutdown setpoints
for high level generally should be no
greater than 90% of the transmitter
span. Similarly, the alarm and shutdown setpoints for low level should be
no less than 10% of the transmitter
span. The reason for this is to ensure
that these critical points can be read
by the transmitter under all operating conditions.
For example, when using a differential-pressure-style level transmitter, a
10% decrease in the density of the process fluid such as might occur in vessels containing fluid mixtures of varying composition or temperature can
result in the vessel being completely
full (filled above the top transmitter
connection), but the transmitter may
indicate only 90% output. This is because the weight of the liquid column
between the transmitter connections is
less than that for which the transmitter was designed, and the liquid above
the top connection exerts its weight
on both the top and the bottom connections equally, so it does not create
32
Gage
glasses
Level
transmitter
Figure 4. This level bridle with gage glasses and level transmitter on a vertical vessel depicts a common (but generally not recommended) installation practice
Level bridles
Magnetic
level gage
Each instrument is
directly connected
to the vessel with
its own nozzles,
eliminating the
problems associated
with level bridles
and allowing greater
operating range
Level
transmitter
Figure 5. This installation is similar to that shown in Figure 4, with
a staggering of the instrument connection elevations
Practical examples
33
Cover Story
this additional 15% usable volume can
allow for greater tolerance to a process
upset without resulting in an alarm or
a shutdown condition simply by allowing the operator and the control system to view and utilize a greater portion of the vessel.
Also important, the total installed
cost of this system is expected to be
less than that in the previous example,
because it requires no bridle piping,
fewer valves, fewer total welds (but
more shop welds are required for the
additional vessel nozzles) and fewer instruments. It also takes up less physical space that might have otherwise
increased the access platform size.
Final notes
Ultra-Clean
The new cGMP-drum
offers process reliability by
validated cleaning procedures
Details of the Ultra-Clean line:
Sanitary welded edging
Geometry of beads and bottom
optimized for clean discharge
of product and for drum cleaning
Body, base and lid in stainless
steel AISI 316
FDA-approved silicone elastomer
seal ring, USP Class VI
Choose from a range
of 20 different sizes
Compliant with FDA and cGMP
guidelines
Circle 11 on p. 50 or go to adlinks.che.com/40264-11
34
Edited by Dorothy Lozowski
Author
Chad E. Schaffer is an
associate
process
instrumentation and controls engineer in the Process & Industrial Division at Burns
& McDonnell (9400 Ward
Parkway, Kansas City, MO
64114; Phone: 816-822-3114;
Email: cschaffer@burnsmcd.
com), an employee-owned engineering and construction
management firm. He has
implemented projects for clients in the refining,
chemicals, biofuels, gas processing and power
generation industries. Schaffer is a senior member of AIChE and ISA, a member of the Process
Industry Practices (PIP) Process Control Function
Team, the ISA 84 working group and the Center
for Chemical Process Safety Technical Steering
Committee. He received his B.S.Ch.E. from the
University of Kansas in 1996, is a registered professional engineer in multiple states, and is a Certified Functional Safety Expert (CFSE).