Agenda
Choose the best surge protection.
Install overvoltage protection.
Choose the best upstream protection for a surge arrester.
Installation rules.
Electrical overvoltage,
unique characteristics
Sources
Lightning
Overvoltage
generated by
operations or
incidents on the
network.
Characteristics
Ultra-rapid transient
phenomenon. Unit
of measurement =
kV/ s
Highly destructive
energy.
Lightning
Voltage
Operations
Repetitive
phenomenon
leading to
premature aging.
Malfunction which
may even result in
permanent damage.
Irms
overvoltage which
exposes the electrical installations to a serious risk of:
malfunction,
destruction of equipment,
unavailability of production tools,
etc.
With LPS*
Type of
surge
arrester
T1: only used
Distance of
the loads <
30m
when LPS is
present
T2: used
systematically.
T3: only used in
Distance of
the loads
> 30m**
T2
T3
T3
T3
T3
T1 +
T2
T3
addition to a
T2 (as lower
discharge
capacity), if the
loads are more
than 30m from the
incoming T2 surge
arrester
T2
(the most
common)
Mainboard
Case
No.2
T2
Distance of more than 30
metres
Mainboard
T2 = type 2 surge arrester
T3
T2
Floor
switchboard
Mainboard
To summarise
10
Lightning
current
Sensitive equipments
* SPD = Surge Protection Device.
Schneider Electric Surge Protection 03/2010
11
12
to be
exposed to a permanent overvoltage
upstream by a disconnection
circuit breaker.
Schneider Electric Surge Protection 03/2010
SPD
13
14
C60L
C60L
NG125N
NG125N
15kA
C60H
C60H
C60H
C60H
6kA
C60N
C60N
C60N
C60N
8kA
20kA
40kA
65kA
Lightning current
E.g. the best disconnection circuit breaker for a breaking capacity of 15kA
and Imax of 40kA is a C60H.
Electric.
15
16
Safe
Efficient
Easy selection
Quick PF and
Quick PRD
Schneider Electric Surge Protection 03/2010
17
Installation rules
18
frequency
1 metre of cable crossed by a lightning current generates an overvoltage of 1,000V.
1000V
U spd
1000V
500V
Load
Uload =
USPD + 2000V
U spd
Load
Uload =
USPD + 500kV
19
L 50cm
L1
L2
L2
L3
L3
Intermediate
Main earth earth terminal
bar
L > 50cm
Mandatory in Standard IEC 60364-5-534:
L (length of cables) < 50cm,
cable cross-section S < 4mm(Type 2) and S< 16mm (Type 1).
Schneider Electric Surge Protection 03/2010
Main earth
bar
L = L1 + L2 + L3
20
L1+L2+L3 < 50 cm
L2 ~ 0cm
L3 ~ 5cm
21
L1+L2+L3 < 50 cm
L3 ~ 15cm
22
with standard
IEC 60439-1.
Schneider Electric Surge Protection 03/2010
23
Circuit
protection
Protection of sensitive
equipment
Against temporary
failure (overvoltage, lightning)