You are on page 1of 1

LOOP TEST SHEET

System:
Loop Number
Alarm Settings
Actual alarm values
Alarms needing reset
Post test statement

P&ID:
L=
L=

LL =
LL =

Project:
Description
H=
H=

Signed

The loop is installed as shown on the P&ID and loop


diagram
The loop will perform as designed
Field Labelling
Motor push buttons
Motors
Control/On-Off Valves
Instruments and cabel
Orifice Plates
Junction Box
Marshalling Cabinet
DCS/PLC Panel
Local Panels
General electrical wiring
Other

MCC Room
Starters and push buttons
Lighting suitable
Accessibility of terminations
Fuse/breaker lock box available
Heating adequate
Cooling adequate
Cabinet air fan acceptable?
Labels on cabinet door correct
Wires labeled
Cables labelled
Other

DCS and or I/O Room


DCS/PLC panels labelled
Termination panel access suitable
Termination drawing suitable
Fuse in place

HH =
HH =

YES

NO

YES

NO

OK N/A Instrument
Air Isolation correct
Accessible
Location correct per Loop diagram and P&ID
Input continuity check
Calibration
Range check with Control system
Loop direct/reverse action
Serial number correct
State change OK on control system

Control- On/Off valves


Position
0% =
Position
25% =
Position
50% =
Position
75% =
Position
100% =

mA =
mA =
mA =
mA =
mA =

Valve positioner operates correctly


State change OK on control system
Fail position checked

Interlock tested
Documentation
Interlock data on loop and P&ID correct
All loop diagram data correct
Master copy red lines for final mark up
Control room has copy until as built issued

Motor
Megged/rating
Rotation
State change OK on control system

Signed for Instrument/Control / Electrical


Signed for process

Date
Date

You might also like