RESPONSE SHEET TO GASCO DOCUMENT REVIEW COMMENTS GASCO TRANSMITTAL NUMBER
DATE
REVIEW CODE
08/08/2016
S/N
1.0
Section/Page Ref.
COMPANY Comments
1. Cable penetration and spares shall be
properly sealed to provide protection from fire, gas, smoke; chemical, liquid etc.MAR shall be submitted accordingly. 2. Core cutting of concrete wall for MCT opening shall cut the reinforcement bars, which are placed 150mm c/c both ways, inside and outside face of the wall. Therefore contractor shall submit the design calculations to ensure that cutting of reinforcement shall not compromise structural integrity of wall. 3. Separate method statement for core cutting of concrete wall shall be submitted for companys review & approval.
DOCUMENT No.
DOCUMENT TITLE
REVISION
5623-PP-GEN-15003
Method Statement For Multi
Cable Transit (MCT) Installation
CONTRACTOR Response
1. Comment incorporated.MAR attached
2. Sketch attached as per specification. 3. Core cutting methodology elaborated in this document.