Professional Documents
Culture Documents
Fire Water Demand Calculations Annexure-1
Fire Water Demand Calculations Annexure-1
Client
JOINT OPERATION
Project
SUG Facilities
JO-MP/AE-734-PR-804
1 OF 2
L (M) /
D(M)
1
W(M) /
H(M)
No.
Area (M2)
Appln. Density
(lpm/m2)
Total Flow
(lpm)
a) Manifold #1
14.000
3.500
49.000
49.000
2.940
b) Manifold #2
20.000
3.000
60.000
60.000
3.600
c) Manifold #3
21.000
3.000
63.000
63.000
3.780
d) Manifold #4
21.000
3.000
63.000
63.000
3.780
70.000
6.000
420.000
420.000
25.200
f) Separator area
35.000
30.000
1050.000
1050.000
63.000
90.000
69.500
6255.000
6255.000
375.300
10.000
10.000
100.000
100.000
6.000
55.000
94.000
5170.000
5170.000
310.200
7.000
7.315
199.350
199.350
11.961
15.000
12.200
751.626
751.626
45.098
25.000
9.000
225.000
225.000
13.500
10.000
7.000
70.000
70.000
4.200
12.000
12.000
144.000
144.000
8.640
24.000
10.000
240.000
240.000
14.400
174.000
6.000
1044.000
1044.000
62.640
18.000
3.400
61.200
61.200
3.672
2.000
2.000
4.000
4.000
0.240
12.200
13.400
1260.972
1260.972
75.658
r) V-103
Annexure - 1
Client
JOINT OPERATION
Project
SUG Facilities
JO-MP/AE-734-PR-804
2 OF 2
II
L (M) /
DIA
(M)
a)
HEIGHT
(M)
No.
Area (M2)
Foam Appln.
Density
(gpm/ft2)
Foam
Appln.
Density
(lpm/m2)
Total Flow
(M3/Hr.)
28.042
15.240
1342.572
0.15
6.11
8205.633
492.338
28.042
15.240
617.583
0.15
6.11
3774.591
226.475
11980.224
718.813
b)
Total Water
Flow (lpm)
24.994
15.850
1244.506
0.15
6.11
7606.265
456.376
24.994
15.850
490.623
0.15
6.11
2998.624
179.917
10604.889
636.293
c)
9.345
25.574
238.989
0.3
12.22
2921.342
175.281
d)
4.367
24.384
1116.912
0.25
10.19
11377.380
682.643
Water Requirements for Foam System Demands: Various Locations and Equipment
III
L (M) /
DIA
(M)
HEIGHT
(M)
No.
Area (M )
2
Foam Appln.
Density
(gpm/ft2)
Foam
Appln.
Density
(lpm/m2)
Total Water
Flow (lpm)
Total Flow
(M3/Hr.)
a)
28.042
15.240
617.583
0.12
4.89
2929.083
175.745
b)
24.900
15.800
486.955
0.12
4.89
2309.536
138.572
5238.619
894.558
Total Largest Water Demand shall be for Tank T-201 on fire (II (a) + III (a)
m3/hr
FOAM SYSTEM
Tank No.
T-201
T-01
Basis:
Height, H
(m)
15.240
15.850
Diameter, D
(m)
28.042
24.994
Volume
(m3)
9412
7776
1
2
3
4
5
Tank Type
Considering largest tank on fire at a time
Type of Foam
Foam Conc.
%
Fluid in Tank
0.120
=
4.890
Application Rate x
x D2
4
3019.76 lpm =
181.19 m3/hr
4983 liters
Considering 5% excess
5250 liters
1387 USGPM
V =
6 m/s
0.103 m
100 NB
CS Sch 40
Actual Pipe ID
102.26 mm
FOAM TANK
Page 3
6.128
FOAM TANK
m/s
Page 4
Summary:
1
1000
1400
usgpm
usgpm
FOAM TANK
Page 5
FOAM TANK
Page 6
FOAM SYSTEM
Tank No.
T-201
T-01
Basis:
1
2
3
4
5
Height, H
(m)
15.240
15.850
Diameter, D
(m)
28.042
24.994
Tank Type
Considering largest tank on fire at a time
Type of Foam
Foam Conc.
%
Fluid in Tank
Volume
(m3)
9412.24
7776.17
Application Rate x
=
x D2
4
3019.76 lpm =
2
a
nos.
nos.
nos.
1006.59 lpm
175
100
120
181.19 m3/hr
2
nos.
(Ref: Table 3-2.3.2.1 of NFPA 11)
2
nos. (Section 15550, Point No. 1.04 J)
(Section 15550, Point No. 1.04 D)
psi
psi
psi
psi
Considered Foam Chamber Inlet Presssure, P
100
psi
7.031
kg/cm2g
(as per foam chamber manufcturer's brochure, inlet pressure should be 3 kg/cm2g (min).
K Factor for the above Foam Chamber Capacity & Pressure
K =
Q / ( P ) 0.5
=
380
Page 7
80
NB
Page 8
FOAM SYSTEM
Tank No.
T-01
Basis:
1
2
3
4
5
Height, H
(m)
15.850
Diameter, D
(m)
24.994
Tank Type
Considering largest tank on fire at a time
Type of Foam
Foam Conc.
%
Fluid in Tank
Volume
(m3)
7776.17
Application Rate x
=
x D2
4
2398.90 lpm =
2
a
nos.
nos.
nos.
799.63 lpm
175
100
120
143.93 m3/hr
2
nos.
(Ref: Table 3-2.3.2.1 of NFPA 11)
2
nos. (Section 15550, Point No. 1.04 J)
(Section 15550, Point No. 1.04 D)
psi
psi
psi
psi
Considered Foam Chamber Inlet Presssure, P
100
psi
7.031
kg/cm2g
(as per foam chamber manufcturer's brochure, inlet pressure should be 3 kg/cm2g (min).
K Factor for the above Foam Chamber Capacity & Pressure
K =
Q / ( P ) 0.5
=
302
Page 9
80
NB
Page 10
Annexure - 1
Line sizing for SUG Facilities Fire
Fighting system
Client
JOINT OPERATION
Project
SUG Facilities
Doc. No.
JO-MP/AE-734-PR-804
Sheet No.
2 OF 2
Line sizing
Equipment
a)
Tank SG-T-201
718.81
3.500
269.51
359.41
3.500
190.57
Line size
considered
12" NB,
Sch 40
Line ID
(mm)
Actual
velocity
(m/s)
303.280
2.764
202.740
3.093
8" NB,
Sch 40
b)
Tank SG-T-001
636.29
3.500
253.57
10" NB,
Sch 40
254.510
3.474
c)
682.64
3.500
262.64
12" NB,
Sch 40
303.280
2.625
181.19
3.500
135.31
154.080
2.699
143.93
3.500
120.60
154.080
2.144
90.59
3.500
95.68
102.260
3.064
71.97
3.500
85.28
102.260
2.434
6" NB,
6" NB,
4" NB,
4" NB,
Sch 40
Sch 40
Sch 40
Sch 40
tank dia
tank ht
appl. Density
dist of ring header from tank outside
water reqd
riser
24.9936 m
15.8496 m
1 m
2 nos