Professional Documents
Culture Documents
Pump Sizing
Pump Sizing
CLIENT:
DSN BY:
COMMENTS:
COUNTY:
CHK BY:
___________
DATE:
10/5/16
DATE:__________
99.5
86.6
ft
ft
DISCHARGE PIPE
Discharge Pipe Length
Equivalent Length of Pipe Fittings
Discharge Pipe Inside Diameter
Hazen-Williams Roughness, C
130.0
35.0
3.00
130
ft
ft (see tables) =============================>
in
==========================>
Hazen-Williams
Material
C
ft
Brass
130
Cast Iron
100
Concrete
100
Copper
130
ft
Fiberglass
150
ft (includes equivalent length of fittings)
PE, no joints
150
PVC
130
Steel, Smooth
100
Steel, Spiral
90
Steel, CMP
60
Other Losses
0.0
Static Head
Total Discharge Pipe Length
12.9
165.0
Pump Manufacturer
Pump Model #
Pump Curve
Flow
GPM
0
Goulds
WS15D3
Pump
Head, ft
38
System Curve
Flow
GPM
0
System
Head, ft
12.9
50
34
50
14.3
100
150
200
250
300
30
26
22
16
10
100
150
200
250
300
17.9
23.6
31.0
40.3
51.3
25.0
160
0.36
7.3
10.8
Note: Velocity will increase as static head pressure (acting against the pump) decreases
CLEAR
CELLS
Pump
System
51.3
Head, feet
50
40.3
40
38
34
30
31.0
30
26
23.6
22
20
17.9
16
14.3
12.9
10
10
0
0
50
POWER REQUIREMENTS
Hydraulic Power
100
150
200
250
1.0
0.8
WHP
WkW
74.0
1.4
1.0
%
bHP
bkW
Motor Efficiency
Motor Input Power
70.0
2.0
1.5
%
HP
kW
COST OF ELECTRICITY
Cost per kW-hr
Hours used
Total Cost
$0.100
1.0
$0.15
Dollars
Hours
Dollars
300