Professional Documents
Culture Documents
Main Sewage Pumping Station A) Static Head 13.43 M: Project: Subject: Pumps Head Calculation
Main Sewage Pumping Station A) Static Head 13.43 M: Project: Subject: Pumps Head Calculation
Pipe Crown highest level - Pit minimum water level = Static Head =
Grading/Ground Level
=
=
5.00
-0.03
8.00
6.80
-7.63
-6.63
m
m
m
m
m
m
suggested
Pipe Length L=
Pipe Diameter D=
Flow (3 pumps at duty) Q=
Water Velocity V=
840.00
0.05
5.00
2.47
m
m
l/s
m/s
2,756.0400
0.1667
79.2645
8.0939
1 meter =
1 cubic meter =
1 cubic meter/hour =
1 liter/second =
Acceleration of gravity g =
Kinematic Viscosity =
ft
ft
g/m
ft/s
134,905.2563
0.0168
283.1643 ft
86.30 m
3.2810
264.2000
4.4030
15.8529
9.8
0.00001
ft
gal
gallon/minute [US]
gallon/minute [US]
m/s =
ft/s
32.1538 ft/s
7.32 m
Fitting type
32 Elbow
22.5 Elbow
11.25 Elbow
Gate Valve
Quantity
5.00
3.00
3.00
1.00
K factor
0.50
0.50
0.50
0.20
Total =
Total K factor
2.50
1.50
1.50
0.20
5.7000
1.7698 m
Pipe Diameter D=
Flow Q=
Water Velocity V=
Fitting type
90 Elbow
Tee
0.05 m
5.00 l/s
2.47 m/s
Quantity
2.00
1.00
K factor
0.50
1.70
Total K factor
1.00
1.70
Reducer
Gate Valve
Check valve
1.00
1.00
1.00
0.70
0.20
2.00
Total =
1.7388 m
0.70
0.20
2.00
5.6000
24.26
29 m