Transformer Losses Calculation
Transformer Losses Calculation
1000
11000
415
VA
Volts
Volts
1930
5.76
8000
369
219.16
215.33
Watts
Amps
Watts
Volts
M Ohms
Ohms
Amb temperature
Total Connected Load on Transformer
% Loading of Transformer
34
1000
100%
Deg c
VA
Jignesh.Parmar
www.electricalnotes.wordpress.com
Formulas
HV Full load current = VA / (1.732xVolt)
LV Full load current = VA / (1.732xVolt)
HV Side I2R losses = IR x1.5
LV Side IR losses = IR x0.5x3
TEST ENGINEER
TEST ENGINEER
TEST ENGINEER
Regulation-Efficiency Calcualation
:IR Losses Calculation:
HV Full load current :
LV Full load current :
HV Side I2R losses
LV Side IR losses
Total I R lossses @ Amb temp
Total Stray losses @ Amb temp
I R lossses @75 c temp
Stray losses @ 75 c temp
Total Full load losses at @75 c
Total Impedance at ambient temp
Total Resistance at amb temp
Total Reactance (X) :
Resistance at@ 75 c
0.05
1.39
0.890
0.64
1.53
7998.47
1.76
6940.61
6942.37
12176.29
553.96
12163.68
638.39
Amps
Amps
Watts
Watts
Watts
Watts
Watts
Watts
Watts
Ohms
Ohms
Ohms
Ohms
Impedance at 75 c
Percentage Impedance
Percentage Resistance
12180.42
3.36
0.18
Ohms
%
%
Percentage Reactance
3.35
:Regulation Calculation:
Regulation at P.F of
Regulation at P.F of
Unity
0.8
0.18
2.17
0.6
:Efficiency Calculation:
Efficiency at P.F of
At Transformer Loading
At Transformer Loading
At Transformer Loading
At Transformer Loading
At Transformer Loading
Efficiency at P.F of
At Transformer Loading
At Transformer Loading
At Transformer Loading
At Transformer Loading
At Transformer Loading
Unity
125%
100%
75%
50%
25%
0.8
125%
100%
75%
50%
25%
39.28
34.11
27.98
20.57
11.47
%
%
%
%
%
34.13
29.29
23.71
17.16
9.39
%
%
%
%
%