1MRK504141-BEN A en Product Guide Transformer Protection RET670 2.0 PDF
1MRK504141-BEN A en Product Guide Transformer Protection RET670 2.0 PDF
Contents
1. Application.....................................................................3
13. Monitoring...................................................................36
2. Available functions........................................................10
14. Metering......................................................................38
3. Differential protection....................................................23
4. Impedance protection..................................................25
5. Current protection........................................................28
6. Voltage protection........................................................31
7. Frequency protection....................................................31
8. Multipurpose protection................................................32
10. Control........................................................................33
12. Logic...........................................................................35
Disclaimer
The information in this document is subject to change without notice and should not be construed as a commitment by ABB. ABB assumes no responsibility for any
errors that may appear in this document. Drawings and diagrams are not binding.
Copyright 2014 ABB.
All rights reserved.
Trademarks
ABB and Relion are registered trademarks of the ABB Group. All other brand or product names mentioned in this document may be trademarks or registered
trademarks of their respective holders.
ABB
1. Application
RET670 provides fast and selective protection, monitoring
and control for two- and three-winding transformers,
autotransformers, step-up transformers and generatortransformer block units, phase shifting transformers, special
railway transformers and shunt reactors. The IED is designed
to operate correctly over a wide frequency range in order to
accommodate power system frequency variations during
disturbances and generator start-up and shut-down.
RET670 has a fast, low-impedance differential protection
function with very low requirements on the CTs. It is suitable
for differential applications with multi-breaker arrangements
with up to six restraint CT inputs. The differential protection
function is provided with a 2nd harmonic and waveform-block
restraint feature to avoid tripping for CT saturation and
transformer inrush current, and 5th harmonic restraint to
avoid tripping for transformer overexcitation.
The differential function offers a high sensitivity for low-level
internal faults by using a sensitive differential protection
feature based on an amplitude measurement and directional
comparison of the negative sequence components.
Multiple low impedance restricted earth-fault protection
functions are available as a sensitive and fast main protection
against winding earth faults. This function includes a internal/
external fault discriminator for additional security.
Additionally, a high impedance differential protection function
is available. It can be used for different applications including
restricted earth fault protection as winding protection,
autotransformer differential protection, shunt reactor
protection, T-feeder protection, busbar protection and
generator differential protection.
Tripping and alarm signals from pressure relief, Buchholz and
temperature devices can be sent directly to RET670 via
binary input channels for alarm and back-up purposes. The
binary inputs are highly stabilized against disturbances to
prevent incorrect operation due to, for example, DC system
capacitive discharges or DC earth faults.
Distance protection functionality is available as back-up
protection for faults within the transformer and in the
connected power system.
Positive, negative and zero sequence overcurrent functions,
which can optionally be made directional and/or voltage
controlled, provide further alternative backup protection.
Thermal overload, overexcitation, over/under voltage and over/
under frequency protection functions are also available.
Breaker failure protection for each transformer breaker allows
high speed back-up tripping of surrounding breakers.
ABB
WA1
WA2
W1_QB1
W1_QB2
RET670 A30 2 Winding Transformer in single
breaker arrangement 12AI (9I+3U)
W1_QA1
10
94
DFR/SER DR
DRP RDRE
SMP PTRC
W1_CT
50BF 3I>BF
CC RBRF
51
4(3I>)
OC4 PTOC
MET
W1_NCT
51N
50N
IN>>
EF PIOC
MET
C MMXU
TCM YLTC
W1
3I>>
PH PIOC
84
50
Isqi
C MSQI
4(IN>)
EF4 PTOC
87N
IdN/I
REF PDIF
87T
W2_NCT
3Id/I>
T2W PDIF
W2
87N
IdN/I
REF PDIF
W2_CT
50BF
3I>BF
CC RBRF
51
3I>
>
49
OC4 PTOC
MET
TR PTTR
MET
Isqi
C MSQI
C MMXU
W2_VT
MET
Usqi
10
94
MET
W2_QA1
SMP PTRC
WA1
MET
59
27
2(3U<)
27
MET
P/Q
CV MMXN
FUF SPVC
EF4 PTOC
2(3U>)
U>/I<
4(IN>)
51N_67N
V MMXU
V MSQI
3U<
MET W/Varh
OV2 PTOV
UV2 PTUV
LOV PTUV
ETP MMTR
87
63
71
UN
VN MMXU
TCL YLTC
52PD
46
Iub>
BRC PTOC
60
Ud>
85
85
VDC PTOV
EC PSCH
21
68
ECRW PSCH
INd/I
CCS SPVC
Control
Q CBAY
S SIMG
S SIML
PD
CC PDSC
Optional Functions
87
Id>
HZ PDIF
81
f<
21
Z<
ZMH PDIS
81
81
f>
SA PTUF
SA PTOF
Control
S XCBR
21
Z<
ZGV PDIS
Z<
ZMQ PDIS
Control
Q CRSV
21
df/dt <>
SA PFRC
Z<
ZMM PDIS
2(I>/U<)
CV GAPC
60
S SCBR
21
Z<
ZMMA PDIS
Zpsb
ZM RPSB
Ud>
VD SPVC
21
46I2
4(I2>)
NS4 PTOC
90
TR1 ATCC
21
FDPS PDIS
67N
IN>
SDE PSDE
90
TR8 ATCC
21
FMPS PDIS
37
P<
GUP PDUP
3
Control
S CILO
21
Z<_>
ZDA RDIR
32
P>
GOP PDOP
3
Control
S CSWI
21D
Z<_>
ZDM RDIR
24
U/f>
OEX PVPH
3
Control
S XSWI
21D
Z<_>
ZD RDIR
Z<
ZMQA PDIS
ZSM GAPC
IEC05000848-3-en.vsd
IEC05000848 V4 EN
Figure 1.
ABB
WA1
WA2
RET670 B30 - 2 Winding Transformer in multi
breaker arrangement 24AI (9I+3U, 9I+3U)
W1_QB1
94
W1_QB2
10
SMP PTRC
DFR/DER DR
DRP RDRE
W1_CT2
50BF 3I> BF
CC RBRF
W1_QA1
94
W1_QA2
52PD
PD
CC PDSC
10
SMP PTRC
W1_CT1
50BF 3I> BF
CC RBRF
50N
QB61
QB62
PD
CC PDSC
IN>>
EF PIOC
84
52PD
51
4(3I>)
OC4 PTOC
W1_NCT
W1
51N
3I>>
PH PIOC
MET
TCM YLTC
QB9
50
MET
Isqi
C MSQI
C MMXU
4(IN>)
EF4 PTOC
87N
W2_NCT
IdN/I
87T
REF PDIF
3Id/I>
T2W PDIF
W2
87N
IdN/I
REF PDIF
W2_CT
50BF 3I> BF
CC RBRF
51
4(3I>)
OC4 PTOC
>
49
TR PTTR
MET
MET
Isqi
C MSQI
C MMXU
W2_VT
MET
Usqi
V MSQI
94
MET
51N_67N
V MMXU
10
SMP PTRC
59
2(3U>)
OV2 PTOV
27
U>/I<
4(IN>)
EF4 PTOC
2(3U<)
UV2 PTUV
FUF SPVC
27
3U<
LOV PTUV
MET
P/Q
CV MMXN
MET W/Varh
ETP MMTR
W2_WA1_VT
W2_QA1
MET
UN
VN MMXU
25
SC/VC
SES RSYN
MET
UN
VN MMXU
WA1
TCL YLTC
46
Iub>
BRC PTOC
60
Ud>
85
87
85
VDC PTOV
EC PSCH
21
68
ECRW PSCH
INd/I
CCS SPVC
Control
Q CBAY
63
71
S SIMG
S SIML
Optional Functions
87
Id>
HZ PDIF
81
f<
21
Z<
ZMH PDIS
81
81
f>
SA PTUF
SA PTOF
Control
S XCBR
21
Z<
ZGV PDIS
Z<
ZMQ PDIS
Control
Q CRSV
21
df/dt <>
SA PFRC
Z<
ZMM PDIS
2(I>/U<)
CV GAPC
60
S SCBR
21
Z<
ZMMA PDIS
Zpsb
ZM RPSB
Ud>
VD SPVC
21
46I2
4(I2>)
NS4 PTOC
90
TR1 ATCC
21
FDPS PDIS
67N
IN>
SDE PSDE
90
TR8 ATCC
21
FMPS PDIS
37
P<
GUP PDUP
3
Control
S CILO
21
Z<_>
ZDA RDIR
32
P>
GOP PDOP
3
Control
S CSWI
21D
Z<_>
ZDM RDIR
24
U/f>
OEX PVPH
3
Control
S XSWI
21D
Z<_>
ZD RDIR
Z<
ZMQA PDIS
ZSM GAPC
IEC05000849-3-en.vsd
IEC05000849 V4 EN
Figure 2.
ABB
WA1
WA2
W1_QB1
W1_QB2
RET670 A40 3 Winding Transformer in single
breaker arrangement 24AI (9I+3U, 9I+3U)
W1_QA1
10
94
SMP PTRC
DFR/SER DR
DRP RDRE
W1_CT
50BF
3I>BF
CC RBRF
51
4(3I>)
OC4 PTOC
MET
W1_NCT
51N
50N
IN>>
EF PIOC
MET
C MMXU
TCM YLTC
W1
3I>>
PH PIOC
84
50
Isqi
C MSQI
4(IN>)
EF4 PTOC
87N
W3
IdN/I
REF PDIF
W2_NCT
87T
3Id/I>
T3W PDIF
W2
87N
IdN/I
REF PDIF
W3_VT_3U0
10
94
SMP PTRC
59N
2(U0>)
ROV2 PTOV
MET
UN
51N_67N
4(IN>)
EF4 PTOC
VN MMXU
W3_CT
50BF
3I>BF
CC RBRF
51
4(3I>)
>
49
OC4 PTOC
TR PTTR
51
49
W2_CT
50BF
3I>BF
CC RBRF
W3_QA1
MET
W2_VT
Usqi
V MSQI
WA1
MET
SMP PTRC
59
>
51N_67N
MET
2(3U>)
27
MET
4(IN>)
2(3U<)
U>/I<
27
Isqi
C MSQI
MET
P/Q
CV MMXN
FUF SPVC
UV2 PTUV
Isqi
C MSQI
C MMXU
EF4 PTOC
OV2 PTOV
MET
C MMXU
TR PTTR
V MMXU
10
94
W2_WA1_VT
3I>
OC4 PTOC
MET
3U<
LOV PTUV
MET W/Varh
ETP MMTR
W2_QA1
MET
UN
25
VN MMXU
WA1
SC/VC
SES RSYN
MET
UN
VN MMXU
TCL YLTC
52PD
46
Iub>
BRC PTOC
60
Ud>
85
87
85
VDC PTOV
EC PSCH
21
68
ECRW PSCH
INd/I
CCS SPVC
Control
Q CBAY
63
71
S SIMG
S SIML
PD
CC PDSC
Optional Functions
87
Id>
HZ PDIF
81
f<
21
Z<
ZMH PDIS
81
81
f>
SA PTUF
SA PTOF
Control
S XCBR
21
Z<
ZGV PDIS
Z<
ZMQ PDIS
Control
Q CRSV
21
df/dt <>
SA PFRC
Z<
ZMM PDIS
2(I>/U<)
CV GAPC
60
S SCBR
21
Z<
ZMMA PDIS
Zpsb
ZM RPSB
Ud>
VD SPVC
21
46I2
4(I2>)
NS4 PTOC
90
TR1 ATCC
21
FDPS PDIS
67N
IN>
SDE PSDE
90
TR8 ATCC
21
FMPS PDIS
37
P<
GUP PDUP
3
Control
S CILO
21
Z<_>
ZDA RDIR
32
P>
GOP PDOP
3
Control
S CSWI
21D
Z<_>
ZDM RDIR
24
U/f>
OEX PVPH
3
Control
S XSWI
21D
Z<_>
ZD RDIR
Z<
ZMQA PDIS
ZSM GAPC
IEC05000850-3-en.vsd
IEC05000850 V4 EN
Figure 3.
ABB
WA1
WA2
RET670 B40 - 3 Winding Transformer in multi
breaker arrangement 24AI (9I+3U, 9I+3U)
W1_QB1
94
W1_QB2
10
SMP PTRC
DFR/DER DR
DRP RDRE
W1_CT2
50BF 3I> BF
CC RBRF
W1_QA1
94
W1_QA2
52PD
PD
CC PDSC
10
SMP PTRC
W1_CT1
50BF 3I> BF
CC RBRF
50N
QB61
QB62
PD
CC PDSC
IN>>
EF PIOC
84
52PD
51
4(3I>)
OC4 PTOC
W1_NCT
W1
51N
3I>>
PH PIOC
MET
TCM YLTC
QB9
50
MET
Isqi
C MSQI
C MMXU
4(IN>)
EF4 PTOC
W3
87N
W2_NCT
IdN/I
87T
REF PDIF
3Id/I>
T3W PDIF
W2
87N
IdN/I
REF PDIF
W3_VT_3U0
94
10
SMP PTRC
W3_CT
50BF 3I> BF
CC RBRF
W2_CT
50BF 3I> BF
CC RBRF
W3_QA1
59N
2(U0>)
ROV2 PTOV
51
4(3I>)
MET
UN
VN MMXU
>
49
OC4 PTOC
TR PTTR
51
49
4(3I>)
OC4 PTOC
51N_67N
4(IN>)
EF4 PTOC
MET
MET
C MMXU
>
TR PTTR
MET
Isqi
C MSQI
MET
Isqi
C MSQI
C MMXU
W2_VT
MET
Usqi
V MSQI
MET
51N_67N
V MMXU
U>/I<
4(IN>)
EF4 PTOC
FUF SPVC
MET
P/Q
CV MMXN
WA1
W2_WA1_VT
W2_QA1
94
10
SMP PTRC
MET
WA1
UN
VN MMXU
59
2(3U>)
OV2 PTOV
25
SC/VC
SES RSYN
27
2(3U<)
UV2 PTUV
MET
27
3U<
LOV PTUV
MET W/Varh
ETP MMTR
UN
VN MMXU
TCL YLTC
46
Iub>
BRC PTOC
60
Ud>
85
87
85
VDC PTOV
EC PSCH
21
68
ECRW PSCH
INd/I
CCS SPVC
Control
Q CBAY
63
71
S SIMG
S SIML
Optional Functions
87
Id>
HZ PDIF
81
f<
21
Z<
ZMH PDIS
81
81
f>
SA PTUF
SA PTOF
Control
S XCBR
21
Z<
ZGV PDIS
Z<
ZMQ PDIS
Control
Q CRSV
21
df/dt <>
SA PFRC
Z<
ZMM PDIS
2(I>/U<)
CV GAPC
60
S SCBR
21
Z<
ZMMA PDIS
Zpsb
ZM RPSB
Ud>
VD SPVC
21
46I2
4(I2>)
NS4 PTOC
90
TR1 ATCC
21
FDPS PDIS
67N
IN>
SDE PSDE
90
TR8 ATCC
21
FMPS PDIS
37
P<
GUP PDUP
3
Control
S CILO
21
Z<_>
ZDA RDIR
32
P>
GOP PDOP
3
Control
S CSWI
21D
Z<_>
ZDM RDIR
24
U/f>
OEX PVPH
3
Control
S XSWI
21D
Z<_>
ZD RDIR
Z<
ZMQA PDIS
ZSM GAPC
IEC05000851-3-en.vsd
IEC05000851 V4 EN
Figure 4.
ABB
W1_QB2
RET670 A10 Transformer backup protection
12AI (9I+3U)
W1_QA1
10
94
SMP PTRC
DFR/SER DR
DRP RDRE
W1_CT
50BF
3I>BF
CC RBRF
51
4(3I>)
OC4 PTOC
50
3I>>
PH PIOC
50N
IN>>
EF PIOC
MET
C MMXU
51N
4(IN>)
EF4 PTOC
MET
Isqi
C MSQI
W1
W3
W2
10
94
SMP PTRC
W3_CT
50BF
3I>BF
CC RBRF
W2_CT
50BF
3I>BF
CC RBRF
W2_VT
51N
4(IN>)
EF4 PTOC
51
51N
3I>
OC4 PTOC
MET
C MMXU
4(IN>)
MET
C MMXU
EF4 PTOC
MET
UN
VN MMXU
MET
Isqi
C MSQI
MET
Isqi
C MSQI
>
49
TR PTTR
SMP PTRC
W2_WA1_VT
WA1
4(3I>)
10
94
W3_QA1
51
OC4 PTOC
25
SC/VC
MET
UN
VN MMXU
SES RSYN
W2_QA1
WA1
Other Functions available from the function library
87
Id>
87N
HZ PDIF
MET
UN
IdN/I
REF PDIF
MET
V MSQI
P/Q
CV MMXN
46
Iub>
67N
IN>
BRC PTOC
SDE PSDE
63
71
S SIMG
27
S SIML
3U<
LOV PTUV
60
Ud>
MET W/Varh
VDC PTOV
ETP MMTR
81
81
MET
V MMXU
Control
Q CBAY
Optional Functions
46I2
4(I2>)
NS4 PTOC
27
2(3U<)
UV2 PTUV
59
2(3U>)
OV2 PTOV
59N
2(U0>)
ROV2 PTOV
81
f<
SA PTUF
f>
SA PTOF
df/dt<>
SA PFRC
60
Ud>
VD SPVC
S SCBR
IEC07000191-3-en.vsd
IEC07000191 V4 EN
Figure 5.
ABB
84
84
DFR/SER DR
TCM YLTC
W1
MET
UN
TCM YLTC
DRP RDRE
MET
VN MMXU
Usqi
V MSQI
MET
W1
V MMXU
TRF1
TRF2
W2
MET
MET
V MMXU
Usqi
V MSQI
MET
W2
UN
VN MMXU
TRF1_W2_VT
MET
MET
Isqi
C MSQI
C MMXU
MET
P/Q
CV MMXN
90
TR8 ATCC
TRF1_W2_CT
90
MET
TR8 ATCC
P/Q
MET
CV MMXN
Isqi
C MSQI
MET
TRF2_W2_VT
C MMXU
TRF2_W2_CT
TRF2_W2_QA1
TRF1_W2_QA1
QA11
90
TCL YLTC
TR1 ATCC
63
71
S SIMG
87
S SIML
INd/I
CCS SPVC
46
Iub>
BRC PTOC
27
3U<
60
Ud>
LOV PTUV
VDC PTOV
46I2
67N
94
10
SMP PTRC
MET W/Varh
ETP MMTR
Control
Q CBAY
Optional Functions
50
3I>>
PH PIOC
59N
2(U0>)
ROV2 PTOV
51_67
4(3I>)
OC4 PTOC
3
Control
S CILO
50N
IN>>
EF PIOC
3
Control
S CSWI
51N_67N
4(IN>)
EF4 PTOC
3
Control
4(I2>)
NS4 PTOC
3
S XSWI
Control
S XCBR
IN>
SDE PSDE
3
Control
Q CRSV
27
2(3U<)
UV2 PTUV
60
59
2(3U>)
OV2 PTOV
Ud>
VD SPVC
IEC07000192 V3 EN
Figure 6.
ABB
2. Available functions
Main protection functions
2
0-3
= option quantities
3-A03
10
ABB
1
1
3-A02
3-A02
3-A02
2-B
1-A01
2-B
1-A01
RET670 (A25)
RET670 (B40)
RET670
RET670 (A40)
Transformer
RET670 (B30)
Function description
RET670 (A30)
ANSI
RET670 (A10)
IEC 61850
Differential protection
T2WPDIF
87T
1-2
T3WPDIF
87T
1-2
HZPDIF
87
0-6
3-A02
REFPDIF
87N
0-3
LDRGFC
11REL
0-1
Impedance protection
ZMQPDIS,
ZMQAPDIS
21
0-5
4-B12
4-B12
4-B12
4-B12
ZDRDIR
21D
0-2
2-B12
2-B12
2-B12
2-B12
ZMCAPDIS
21
ZMCPDIS,
ZMCAPDIS
21
0-5
ZDSRDIR
21D
Directional impedance
quadrilateral, including series
compensation
0-2
FDPSPDIS
21
0-2
2-B12
2-B12
2-B12
2-B12
ZMHPDIS
21
0-5
4-B13
4-B13
4-B13
4-B13
ZMMPDIS,
ZMMAPDIS
21
0-5
4-B13
4-B13
4-B13
4-B13
ZDMRDIR
21D
0-2
2-B13
2-B13
2-B13
2-B13
ZDARDIR
0-1
1-B13
1-B13
1-B13
1-B13
ZSMGAPC
0-1
1-B13
1-B13
1-B13
1-B13
2-B13
2-B13
2-B13
2-B13
FMPSPDIS
21
0-2
ZMRPDIS,
ZMRAPDIS
21
0-5
FRPSPDIS
21
0-2
ZMFPDIS
21
01
ABB
11
ZMFCPDIS
21
01
ZMRPSB
68
0-1
0-1
PSLPSCH
PSPPPAM
78
0-1
OOSPPAM
78
Out-of-step protection
01
0-1
01
PPLPHIZ
ZGVPDIS
12
21
1-B12
1-B13
1-B12
1-B13
1-B12
1-B13
1-B12
1-B13
1-B14
1-B14
1-B14
1-B14
RET670 (A25)
RET670 (B40)
RET670
RET670 (A40)
Transformer
RET670 (B30)
Function description
RET670 (A30)
ANSI
RET670 (A10)
IEC 61850
ABB
RET670 (A40)
RET670 (B40)
RET670 (A25)
Transformer
RET670 (B30)
Function description
RET670 (A30)
ANSI
RET670 (A10)
IEC 61850
PHPIOC
50
0-8
2-C19
OC4PTOC
51_671)
0-8
2-C19
EFPIOC
50N
Instantaneous residual
overcurrent protection
0-8
2-C19
EF4PTOC
51N
67N2)
0-8
2-C19
NS4PTOC
46I2
0-8
2-C42
2-C42
2-C42
3-C43
3-C43
2-C19
SDEPSDE
67N
0-3
1-C16
1-C16
1-C16
1-C16
1-C16
LCPTTR
26
02
LFPTTR
26
02
TRPTTR
49
0-6
1B
1-C05
1B
1-C05
2B
1-C05
2B
1-C05
CCRBRF
50BF
0-6
CCPDSC
52PD
0-2
GUPPDUP
37
0-2
1-C17
1-C17
1-C17
1-C17
GOPPDOP
32
0-2
1-C17
1-C17
1-C17
1-C17
BRCPTOC
46
RET670
Current protection
CBPGAPC
0-6
NS2PTOC
46I2
0-2
VRPVOC
51V
0-3
Voltage protection
UV2PTUV
27
0-3
1-D01
1B
1-D01
1B
1-D01
1B
2-D02
1B
2-D02
2-D02
OV2PTOV
59
0-3
1-D01
1B
1-D01
1B
1-D01
1B
1-D02
1B
1-D02
2-D02
ROV2PTOV
59N
0-3
1-D01
1B
1-D01
1B
1-D01
1B
1-D02
1B
1-D02
2-D02
OEXPVPH
24
Overexcitation protection
0-2
1-D03
1-D03
2-D04
2-D04
ABB
13
LOVPTUV
27
RET670 (A25)
RET670 (B40)
60
RET670
RET670 (A40)
VDCPTOV
Transformer
RET670 (B30)
Function description
RET670 (A30)
ANSI
RET670 (A10)
IEC 61850
0-2
Frequency protection
SAPTUF
81
Underfrequency protection
0-6
6-E01
6-E01
6-E01
6-E01
6-E01
SAPTOF
81
Overfrequency protection
0-6
6-E01
6-E01
6-E01
6-E01
6-E01
SAPFRC
81
Rate-of-change frequency
protection
0-6
6-E01
6-E01
6-E01
6-E01
6-E01
0-9
6-F02
6-F02
6-F02
6-F02
Multipurpose filter
0-6
Multipurpose protection
CVGAPC
General calculation
SMAIHPAC
1)
2)
14
67 requires voltage
67N requires voltage
ABB
1-B, 2H01
1-B, 3H02
1-B, 4H03
1-H09
1-H09
1-H09
1-H09
1-H09
RET670 (A25)
RET670 (B40)
RET670
RET670 (A40)
Transformer
RET670 (B30)
Function description
RET670 (A30)
ANSI
RET670 (A10)
IEC 61850
Control
SESRSYN
25
0-6
APC30
0-1
QCBAY
Apparatus control
1+5/APC30
1+5/
APC30
1+5/
APC30
1+5/
APC30
1+5/
APC30
1+5/
APC30
LOCREM
1+5/APC30
1+5/
APC30
1+5/
APC30
1+5/
APC30
1+5/
APC30
1+5/
APC30
LOCREMCTRL
1+5/APC30
1+5/
APC30
1+5/
APC30
1+5/
APC30
1+5/
APC30
1+5/
APC30
TR1ATCC
90
0-4
1-H11
1-H11
1-H11,
2-H16
1-H11,
2-H16
2
2-H16
TR8ATCC
90
0-4
1-H15
1-H15
1-H15,
2-H18
1-H15,
2-H18
2
2-H18
TCMYLTC
84
0-4
TCLYLTC
84
0-4
SLGAPC
15
15
15
15
15
15
15
VSGAPC
20
20
20
20
20
20
20
DPGAPC
16
16
16
16
16
16
16
SPC8GAPC
AUTOBITS
SINGLECMD
VCTRSEND
GOOSEVCTRR
CV
I103CMD
I103GENCMD
50
50
50
50
50
50
50
I103POSCMD
50
50
50
50
50
50
50
I103IEDCMD
ABB
15
RET670 (A25)
RET670 (B40)
RET670
RET670 (A40)
Transformer
RET670 (B30)
I103USRCMD
Function description
RET670 (A30)
ANSI
RET670 (A10)
IEC 61850
87
0-5
0-4
60
0-4
1-G03
1-G03
1-G03
1-G03
1-G03
1-G03
94
Tripping logic
1-6
TMAGAPC
12
12
12
12
12
12
12
ALMCALH
WRNCALH
INDCALH
40-280
40-280
40-280
40-280
40-280
40-280
40-280
ANDQT, ORQT,
INVERTERQT,
XORQT,
SRMEMORYQT
,
RSMEMORYQT
, TIMERSETQT,
PULSETIMERQ
T, INVALIDQT,
INDCOMBSPQT
, INDEXTSPQT
01
SLGAPC,
VSGAPC, AND,
OR,
PULSETIMER,
GATE,
TIMERSET,
XOR, LLD,
SRMEMORY,
INV
01
FXDSIGN
B16I
18
18
18
18
18
18
18
BTIGAPC
16
16
16
16
16
16
16
IB16
18
18
18
18
18
18
18
FUFSPVC
VDSPVC
Logic
SMPPTRC
16
ABB
RET670 (A40)
RET670 (B40)
RET670 (A25)
Transformer
RET670 (B30)
Function description
RET670 (A30)
ANSI
RET670 (A10)
IEC 61850
ITBGAPC
16
16
16
16
16
16
16
TEIGAPC
12
12
12
12
12
12
12
CVMMXN,
CMMXU,
VMMXU,
CMSQI, VMSQI,
VNMMXU
Measurements
AISVBAS
EVENT
Event function
20
20
20
20
20
20
20
DRPRDRE,
A1RADR,
A2RADR,
A3RADR,
A4RADR,
B1RBDR,
B2RBDR,
B3RBDR,
B4RBDR,
B5RBDR,
B6RBDR
Disturbance report
SPGAPC
64
64
64
64
64
64
64
SP16GAPC
16
16
16
16
16
16
16
MVGAPC
24
24
24
24
24
24
24
BINSTATREP
RANGE_XP
66
66
66
66
66
66
66
RET670
Monitoring
SSIMG
63
21
21
21
21
21
21
21
SSIML
71
SSCBR
0-6
3-M13
2-M12
4-M14
3-M13
6-M15
I103MEAS
I103MEASUSR
I103AR
I103EF
I103FLTPROT
ABB
17
RET670 (A40)
RET670 (B40)
RET670 (A25)
Transformer
RET670 (B30)
Function description
RET670 (A30)
ANSI
RET670 (A10)
IEC 61850
I103IED
I103SUPERV
I103USRDEF
20
20
20
20
20
20
20
L4UFCNT
30
30
30
30
30
30
30
PCFCNT
Pulse-counter logic
16
16
16
16
16
16
16
ETPMMTR
RET670
Metering
18
ABB
Communication
RET670 (A40)
RET670 (B40)
RET670 (A25)
Transformer
RET670 (B30)
Function description
RET670 (A30)
ANSI
RET670 (A10)
IEC 61850
LONSPA, SPA
ADE
HORZCOMM
PROTOCOL
RS485PROT
RS485GEN
RS485
DNPGEN
DNPGENTCP
CHSERRS485
CH1TCP,
CH2TCP,
CH3TCP,
CH4TCP
CHSEROPT
MST1TCP,
MST2TCP,
MST3TCP,
MST4TCP
DNPFREC
IEC61850-8-1
GOOSEINTLK
RCV
59
59
59
59
59
59
59
GOOSEBINR
CV
16
16
16
16
16
16
16
GOOSEDPRC
V
64
64
64
64
64
64
64
GOOSEINTRC
V
32
32
32
32
32
32
32
GOOSEMVRC
V
60
60
60
60
60
60
60
GOOSESPRC
V
64
64
64
64
64
64
64
RET670
Station communication
ABB
19
RET670 (A40)
RET670 (B40)
RET670 (A25)
Transformer
RET670 (B30)
Function description
RET670 (A30)
ANSI
RET670 (A10)
IEC 61850
GOOSEVCTR
CONF
VCTRSEND
GOOSEVCTR
RCV
MULTICMDRC
V,
MULTICMDSN
D
60/10
60/10
60/10
60/10
60/10
60/10
60/10
FRONT,
LANABI,
LANAB,
LANCDI,
LANCD
GATEWAY
OPTICAL103
RS485103
AGSAL
LD0LLN0
SYSLLN0
LPHD
PCMACCS
SECALARM
FSTACCS
ACTIVLOG
ALTRK
Service Tracking
SINGLELCCH
PRPSTATUS
0-1
1-P03
1-P03
1-P03
1-P03
1-P03
1-P03
RET670
Remote communication
20
ABB
RET670
RET670 (A40)
RET670 (B40)
RET670 (A25)
Transformer
RET670 (B30)
Function description
RET670 (A30)
ANSI
RET670 (A10)
IEC 61850
6/36
6/36
6/36
6/36
6/36
6/36
6/36
6/3/3
6/3/3
6/3/3
6/3/3
6/3/3
6/3/3
6/3/3
Scheme communication
ECPSCH
85
0-1
ECRWPSCH
85
0-1
1)
ABB
21
Description
INTERRSIG
SELFSUPEVLST
TIMESYNCHGEN
SYNCHBIN,
SYNCHCAN,
SYNCHCMPPS,
SYNCHLON,
SYNCHPPH,
SYNCHPPS,
SYNCHSNTP,
SYNCHSPA,
SYNCHCMPPS
Time synchronization
TIMEZONE
Time synchronization
DSTBEGIN,
DSTENABLE, DSTEND
IRIG-B
Time synchronization
SETGRPS
ACTVGRP
TESTMODE
CHNGLCK
SMBI
SMBO
SMMI
SMAI1 - SMAI20
3PHSUM
ATHSTAT
Authority status
ATHCHCK
Authority check
AUTHMAN
Authority management
FTPACCS
SPACOMMMAP
SPATD
DOSFRNT
DOSLANAB
DOSLANCD
DOSSCKT
GBASVAL
PRIMVAL
ALTMS
ALTIM
Time management
22
ABB
Description
ALTRK
Service tracking
ACTIVLOG
FSTACCS
Field service tool access via SPA protocol over ethernet communication
PCMACCS
SECALARM
Component for mapping security events on protocols such as DNP3 and IEC103
DNPGEN
DNPGENTCP
CHSEROPT
MSTSER
OPTICAL103
RS485103
IEC61850-8-1
HORZCOMM
LONSPA
LEDGEN
3. Differential protection
Transformer differential protection T2WPDIF/T3WPDIF
The Transformer differential protection, two-winding T2WPDIF
and Transformer differential protection, three-winding
T3WPDIF are provided with internal CT ratio matching, vector
group compensation and settable zero sequence current
elimination.
The function can be provided with up to six three-phase sets
of current inputs. All current inputs are provided with
percentage bias restraint features, making the IED suitable for
two- or three-winding transformer in multi-breaker station
arrangements.
Two-winding applications
two-winding power
transformer
xx05000048.vsd
IEC05000048 V1 EN
xx05000049.vsd
two-winding power
transformer with
unconnected delta
tertiary winding
IEC05000049 V1 EN
xx05000050.vsd
IEC05000050 V1 EN
two-winding power
transformer with two
circuit breakers and
two CT-sets on one
side
two-winding power
transformer with two
circuit breakers and
two CT-sets on both
sides
xx05000051.vsd
IEC05000051 V1 EN
Three-winding applications
ABB
23
three-winding power
transformer with all
three windings
connected
xx05000052.vsd
IEC05000052 V1 EN
three-winding power
transformer with two
circuit breakers and
two CT-sets on one
side
xx05000053.vsd
IEC05000053 V1 EN
Autotransformer with
two circuit breakers
and two CT-sets on
two out of three sides
xx05000057.vsd
IEC05000057 V1 EN
Figure 7.
YNdx
CT
CT
CB
CB
CB
CB
Autotransformer
CT
IED
CT
CB
CB
CT
IEC05000058-2 V1 EN
Figure 8.
ABB
Forward
operation
R
Reverse
operation
en05000034.vsd
IEC05000034 V1 EN
Figure 9.
4. Impedance protection
FunctionalityDistance measuring zone, quadrilateral
characteristic ZMQPDIS, ZMQAPDIS (21)
The line distance protection is a five four zone full scheme
protection with three fault loops for phase-to-phase faults and
three fault loops for phase-to-earth faults for each of the
independent zones. Individual settings for each zone in
resistive and reactive reach gives flexibility for use as back-up
protection for transformer connected to overhead lines and
cables of different types and lengths.
ZMQPDIS together with Phase selection with load
encroachment FDPSPDIS has functionality for load
encroachment, which increases the possibility to detect high
resistive faults on heavily loaded lines.
ABB
ABB
28
5. Current protection
Instantaneous phase overcurrent protection PHPIOC
The instantaneous three phase overcurrent function has a low
transient overreach and short tripping time to allow use as a
high set short-circuit protection function.
ABB
Unbalanced loads
Line to line faults
Line to earth faults
Broken conductors
Malfunction of one or more poles of a circuit breaker or a
disconnector
31
8. Multipurpose protection
General current and voltage protection CVGAPC
The protection module is recommended as a general backup
protection with many possible application areas due to its
flexible measuring and setting facilities.
The built-in overcurrent protection feature has two settable
current levels. Both of them can be used either with definite
time or inverse time characteristic. The overcurrent protection
steps can be made directional with selectable voltage
polarizing quantity. Additionally they can be voltage and/or
current controlled/restrained. 2nd harmonic restraining facility
is available as well. At too low polarizing voltage the
overcurrent feature can be either blocked, made non
directional or ordered to use voltage memory in accordance
with a parameter setting.
Additionally two overvoltage and two undervoltage steps,
either with definite time or inverse time characteristic, are
available within each function.
The general function suits applications with underimpedance
and voltage controlled overcurrent solutions. The general
function can also be utilized for generator transformer
protection applications where positive, negative or zero
sequence components of current and voltage quantities are
typically required.
32
ABB
33
12. Logic
ABB
35
36
13. Monitoring
Measurements CVMMXN, CMMXU, VNMMXU, VMMXU,
CMSQI, VMSQI
The measurement functions are used to get on-line
information from the IED. These service values make it
possible to display on-line information on the local HMI and
on the Substation automation system about:
measured voltages, currents, frequency, active, reactive
and apparent power and power factor
measured analog values from merging units
primary phasors
positive, negative and zero sequence currents and
voltages
mA, input currents
pulse counters
Supervision of mA input signals
The main purpose of the function is to measure and process
signals from different measuring transducers. Many devices
used in process control represent various parameters such as
frequency, temperature and DC battery voltage as low current
values, usually in the range 4-20 mA or 0-20 mA.
Alarm limits can be set and used as triggers, e.g. to generate
trip or alarm signals.
The function requires that the IED is equipped with the mA
input module.
Disturbance report DRPRDRE
Complete and reliable information about disturbances in the
primary and/or in the secondary system together with
continuous event-logging is accomplished by the disturbance
report functionality.
Disturbance report DRPRDRE, always included in the IED,
acquires sampled data of all selected analog input and binary
signals connected to the function block with a, maximum of
40 analog and 96 binary signals.
The Disturbance report functionality is a common name for
several functions:
Event list
Indications
Event recorder
Trip value recorder
Disturbance recorder
37
IEC13000239-1-en.vsd
IEC13000239 V1 EN
Figure 10.
ABB
bus use the IEC 61850-9-2LE protocol (OEM rear port C, D).
The module has one or two optical ports with ST connectors.
Serial and LON communication module SLM, supports SPA/
IEC 60870-5-103, LON and DNP 3.0
The serial and LON communication module (SLM) is used for
SPA, IEC 60870-5-103, DNP3 and LON communication. The
module has two optical communication ports for plastic/
plastic, plastic/glass or glass/glass. One port is used for serial
communication (SPA, IEC 60870-5-103 and DNP3 port) and
one port is dedicated for LON communication.
Line data communication module LDCM
Each module has one optical port, one for each remote end
to which the IED communicates.
Alternative cards for Long range (1550 nm single mode),
Medium range (1310 nm single mode) and Short range (850
nm multi mode) are available.
Galvanic X.21 line data communication module X.21-LDCM
The galvanic X.21 line data communication module is used for
connection to telecommunication equipment, for example
leased telephone lines. The module supports 64 kbit/s data
communication between IEDs.
Examples of applications:
Line differential protection
Binary signal transfer
Galvanic RS485 serial communication module
The Galvanic RS485 communication module (RS485) is used
for DNP3.0 and IEC 60870-5-103 communication. The
module has one RS485 communication port. The RS485 is a
balanced serial communication that can be used either in 2wire or 4-wire connections. A 2-wire connection uses the
same signal for RX and TX and is a multidrop communication
with no dedicated Master or slave. This variant requires
however a control of the output. The 4-wire connection has
separated signals for RX and TX multidrop communication
with a dedicated Master and the rest are slaves. No special
control signal is needed in this case.
GPS time synchronization module GTM
This module includes a GPS receiver used for time
synchronization. The GPS has one SMA contact for
connection to an antenna. It also includes an optical PPS STconnector output.
IRIG-B Time synchronizing module
The IRIG-B time synchronizing module is used for accurate
time synchronizing of the IED from a station clock.
The Pulse Per Second (PPS) input shall be used for
synchronizing when IEC 61850-9-2LE is used.
Electrical (BNC) and optical connection (ST) for 0XX and 12X
IRIG-B support.
ABB
G
H
J
xx08000165.vsd
E
IEC08000165 V1 EN
Figure 12.
IEC08000163-2-en.vsd
IEC08000163 V2 EN
Figure 11.
IEC06000182-2-en.vsd
IEC06000182 V2 EN
Figure 13.
Case size
(mm)
6U, 1/2 x 19
265.9
223.7
242.1
255.8
205.7
190.5
203.7
228.6
6U, 3/4 x 19
265.9
336.0
242.1
255.8
318.0
190.5
316.0
228.6
6U, 1/1 x 19
265.9
448.3
242.1
255.8
430.3
190.5
428.3
465.1
228.6
482.6
ABB
41
Mounting alternatives
19 rack mounting kit
Flush mounting kit with cut-out dimensions:
1/2 case size (h) 254.3 mm (w) 210.1 mm
3/4 case size (h) 254.3 mm (w) 322.4 mm
1/1 case size (h) 254.3 mm (w) 434.7 mm
Wall mounting kit
42
ABB
Connection diagrams
The connection diagrams are delivered on the IED
Connectivity package DVD as part of the product delivery.
ABB
43
The specified value of an influencing factor to which are referred the characteristics of the equipment
Nominal range
The range of values of an influencing quantity (factor) within which, under specified conditions, the equipment meets the
specified requirements
Operative range
The range of values of a given energizing quantity for which the equipment, under specified conditions, is able to perform its
intended functions according to the specified requirements
Rated value
Nominal range
Current
Ir = 1 or 5 A
(0.2-40) Ir
Operative range
(0-100) x Ir
Permissive overload
4 Ir cont.
100 Ir for 1 s *)
Burden
Ac voltage
Ur = 110 V
Operative range
(0340) V
Permissive overload
420 V cont.
450 V 10 s
Burden
Frequency
fr = 50/60 Hz
*)
44
0.5288 V
5%
ABB
Table 3. TRM - Energizing quantities, rated values and limits for measuring transformer modules
Quantity
Rated value
Nominal range
Current
Ir = 1 or 5 A
(0-1.8) Irat Ir = 1 A
(0-1.6) Irat Ir = 5 A
Permissive overload
1.1 Ir cont.
1.8 Ir for 30 min at Ir = 1 A
1.6 Ir for 30 min at Ir = 5 A
Burden
Ac voltage
Ur = 110 V
Operative range
(0340) V
Permissive overload
420 V cont.
450 V 10 s
Burden
Frequency
fr = 50/60 Hz
0.5288 V
5%
Rated value:
Nominal range:
Input resistance
Input range
5, 10, 20mA
0-5, 0-10, 0-20, 4-20mA
Power consumption
each mA-board
each mA input
2W
0.1 W
Rated value
Number of channels
Standard
Type of fiber
Wave length
1300 nm
Optical connector
Type ST
Communication speed
Auxiliary DC voltage
Table 6. PSM - Power supply module
Quantity
Rated value
Nominal range
EL = (24 - 60) V
EL = (90 - 250) V
EL 20%
EL 20%
Power consumption
50 W typically
ABB
45
Rated value
Nominal range
Binary inputs
16
DC voltage, RL
24/30 V
48/60 V
110/125 V
220/250 V
RL 20%
RL 20%
RL 20%
RL 20%
Power consumption
24/30 V, 50mA
48/60 V, 50mA
110/125 V, 50mA
220/250 V, 50mA
220/250 V, 110mA
10 pulses/s max
Debounce filter
Settable 120ms
Table 8. BIM - Binary input module with enhanced pulse counting capabilities
Quantity
Rated value
Nominal range
Binary inputs
16
DC voltage, RL
24/30 V
48/60 V
110/125 V
220/250 V
RL 20%
RL 20%
RL 20%
RL 20%
Power consumption
24/30 V
48/60 V
110/125 V
220/250 V
10 pulses/s max
40 pulses/s max
46
ABB
Rated value
Nominal range
Binary inputs
DC voltage, RL
24/30 V
48/60 V
110/125 V
220/250 V
RL 20%
RL 20%
RL 20%
RL 20%
Power consumption
24/30 V, 50 mA
48/60 V, 50 mA
110/125 V, 50 mA
220/250 V, 50 mA
220/250 V, 110 mA
10 pulses/s max
40 pulses/s max
Debounce filter
Settable 1-20 ms
Table 10. IOM - Binary input/output module contact data (reference standard: IEC 61810-2)
Function or quantity
Binary outputs
10
250 V AC, DC
250 V DC
1000 V rms
800 V DC
8A
10 A
12 A
8A
10 A
12 A
30 A
10 A
0.4 A
0.4 A
0.2 s
1.0 s
30 A
10 A
220250 V/0.4 A
110125 V/0.4 A
4860 V/0.2 A
2430 V/0.1 A
250 V/8.0 A
250 V/8.0 A
48 V/1 A
110 V/0.4 A
125 V/0.35 A
220 V/0.2 A
250 V/0.15 A
48 V/1 A
110 V/0.4 A
125 V/0.35 A
220 V/0.2 A
250 V/0.15 A
10 nF
ABB
47
Table 11. IOM with MOV and IOM 220/250 V, 110mA - contact data (reference standard: IEC 61810-2)
Function or quantity
Binary outputs
IOM: 10
IOM: 2
250 V AC, DC
250 V DC
250 V rms
250 V rms
8A
10 A
12 A
8A
10 A
12 A
30 A
10 A
0.4 A
0.4 A
0.2 s
1.0 s
30 A
10 A
220250 V/0.4 A
110125 V/0.4 A
4860 V/0.2 A
2430 V/0.1 A
250 V/8.0 A
250 V/8.0 A
48 V/1 A
110 V/0.4 A
220 V/0.2 A
250 V/0.15 A
48 V/1 A
110 V/0.4 A
220 V/0.2 A
250 V/0.15 A
10 nF
Table 12. SOM - Static Output Module (reference standard: IEC 61810-2): Static binary outputs
Function of quantity
Rated voltage
48 - 60 VDC
Number of outputs
~300 k
~810 k
No galvanic separation
No galvanic separation
Continuous
5A
5A
1.0s
10A
10A
0.2s
30A
30A
1.0s
10A
10A
48V / 1A
110V / 0.4A
60V / 0.75A
125V / 0.35A
220V / 0.2A
250V / 0.15A
Operating time
48
<1ms
<1ms
ABB
Table 13. SOM - Static Output module data (reference standard: IEC 61810-2): Electromechanical relay outputs
Function of quantity
250V AC/DC
Number of outputs
1000V rms
8A
1.0s
10A
30A
1.0s
10A
48V / 1A
110V / 0.4A
125V / 0.35A
220V / 0.2A
250V / 0.15A
Table 14. BOM - Binary output module contact data (reference standard: IEC 61810-2)
Function or quantity
Binary outputs
24
250 V AC, DC
1000 V rms
8A
10 A
12 A
30 A
10 A
250 V/8.0 A
48 V/1 A
110 V/0.4 A
125 V/0.35 A
220 V/0.2 A
250 V/0.15 A
Influencing factors
Table 15. Temperature and humidity influence
Parameter
Reference value
Nominal range
Influence
+20 C
-10 C to +55 C
0.02% /C
Relative humidity
Operative range
10%-90%
0%-95%
10%-90%
Storage temperature
-40 C to +85 C
ABB
49
Reference value
Within nominal
range
Influence
max. 2%
Full wave rectified
15% of EL
0.01% /%
20% of EL
0.01% /%
24-60 V DC 20%
Interruption interval
050 ms
90-250 V DC 20%
No restart
0 s
Restart time
<300 s
Influence
fr 2.5 Hz for 50 Hz
1.0% / Hz
fr 3.0 Hz for 60 Hz
Frequency dependence for distance protection operate value
fr 2.5 Hz for 50 Hz
2.0% / Hz
fr 3.0 Hz for 60 Hz
Harmonic frequency dependence (20% content)
2.0%
12.0%
5.0%
50
ABB
Reference standards
2.5 kV
IEC 60255-26
2.5 kV
2-4 kV
IEEE/ANSI C37.90.1
Electrostatic discharge
Direct application
Indirect application
15 kV air discharge
8 kV contact discharge
8 kV contact discharge
IEC 60255-26
Electrostatic discharge
Direct application
Indirect application
15 kV air discharge
8 kV contact discharge
8 kV contact discharge
IEEE/ANSI C37.90.1
4 kV
150-300 V, 50 Hz
15 Hz-150 kHz
1000 A/m, 3 s
100 A/m, cont.
1000 A/m
100 A/m
IEC 60255-26
1.4-2.7 GHz
Radiated electromagnetic field disturbance
20 V/m
80-1000 MHz
IEEE/ANSI C37.90.2
10 V, 0.15-80 MHz
IEC 60255-26
Radiated emission
30-5000 MHz
IEC 60255-26
Radiated emission
30-5000 MHz
Conducted emission
0.15-30 MHz
IEC 60255-26
Reference standard
Dielectric test
IEC 60255-27
Insulation resistance
ABB
51
Reference standard
IEC 60068-2-1
IEC 60068-2-1
IEC 60068-2-2
IEC 60068-2-2
IEC 60068-2-14
IEC 60068-2-78
IEC 60068-2-30
According to
Immunity
EN 6025526
Emissivity
EN 6025526
EN 6025527
Reference standards
Class II
IEC 60255-21-1
Class I
IEC 60255-21-1
Class I
IEC 60255-21-2
Class I
IEC 60255-21-2
Bump test
Class I
IEC 60255-21-2
Seismic test
Class II
IEC 60255-21-3
52
ABB
Differential protection
Table 23. Transformer differential protection T2WPDIF, T3WPDIF
Function
Range or value
Accuracy
Operating characteristic
Adaptable
1.0% of Ir for I Ir
1.0% of I for I > Ir
Reset ratio
> 90%
Minimum pickup
(5-60)% of IBase
1.0% of Ir
(5.0-100.0)% of fundamental
differential current
1.0% of Ir
(5.0-100.0)% of fundamental
differential current
5.0% of Ir
Y or D
011
Min = 20 ms
Max = 30 ms
Min = 10 ms
Max = 25 ms
Min = 10 ms
Max = 20 ms
Min = 15 ms
Max = 30 ms
2 ms typically at 0 to 5 x Id
Range or value
Accuracy
Operate characteristic
Adaptable
1.0% of Ir for I Ir
1.0% of I for I > Ir
Reset ratio
>95%
Minimum pickup
(4.0-100.0)% of IBase
1.0% of Ir
Directional characteristic
2.0 degrees
Min = 15 ms
Max = 30 ms
Min = 15 ms
Max = 30 ms
1.0% of Ir
ABB
53
Range or value
Accuracy
Operate voltage
(10-900) V
I=U/R
1.0% of Ir at I Ir
Reset ratio
>95% at (30-900) V
U>Trip2/SeriesResistor 200 W
Operate time at 0 to 10 x Ud
Min = 5 ms
Max = 15 ms
Reset time at 10 to 0 x Ud
Min = 75 ms
Max = 95 ms
2 ms typically at 0 to 10 x Ud
Operate time at 0 to 2 x Ud
Min = 25 ms
Max = 35 ms
Reset time at 2 to 0 x Ud
Min = 50 ms
Max = 70 ms
15 ms typically at 0 to 2 x Ud
1.0% of I at I > Ir
Range or value
Accuracy
(1-100)% of lBase
1.0% of Ir
(1-100)% of lBase
1.0% of Ir
(1-100)% of UBase
0.5% of Ur
(1-100)% of UBase
0.5% of Ur
(0.000-60.000) s
0.2% or 40 ms
whichever is greater
(0.000-60.000) s
0.2% or 40 ms
whichever is greater
(0.000-60.000) s
0.2% or 40 ms
whichever is greater
(0.000-60.000) s
0.2% or 40 ms
whichever is greater
54
ABB
Impedance protection
Table 27. Distance measuring zone, Quad ZMQPDIS
Function
Range or value
Accuracy
Number of zones
(5-1000)% of IBase
(10-1000)% of IBase
(0.10-3000.00) /
phase
(0.01-1000.00) /
phase
(0.10-9000.00) /
phase
(0.01-3000.00) /
phase
(0.10-9000.00) /loop
(0.10-3000.00) /loop
Dynamic overreach
<5% at 85 degrees
measured with CVTs
and 0.5<SIR<30
(0.000-60.000) s
Operate time
25 ms typically
IEC 60255-121
Reset ratio
105% typically
Min = 20 ms
Max = 35 ms
ABB
55
Table 28. Distance measuring zone, quadrilateral characteristic for series compensated lines ZMCPDIS, ZMCAPDIS
Function
Range or value
Accuracy
Number of zones
(5-1000)% of IBase
(10-1000)% of IBase
(0.10-3000.00) /phase
(0.10-1000.00) /phase
(0.01-9000.00) /phase
(0.01-3000.00) /phase
(0.10-9000.00) /loop
(0.10-3000.00) /loop
Dynamic overreach
(0.000-60.000) s
Operate time
25 ms typically
IEC 60255-121
Reset ratio
105% typically
Min = 20 ms
Max = 35 ms
Table 29. Phase selection, quadrilateral characteristic with fixed angle FDPSPDIS
Function
Range or value
Accuracy
(5-500)% of IBase
1.0% of Ir at I Ir
1.0% of I at I > Ir
(0.503000.00) /phase
(0.101000.00) /phase
(0.509000.00) /phase
(0.503000.00) /phase
(1.009000.00) /loop
(0.503000.00) /loop
(1.003000.00) /phase
(5-70) degrees
Reset ratio
105% typically
56
ABB
Range or value
Accuracy
(1030)% of IBase
(0.0053000.000) W/phase
(1090) degrees
(0.0053000.000) /phase
(0.003.00)
(-180180) degrees
Dynamic overreach
(0.000-60.000) s
Operate time
22 ms typically
IEC 60255-121
Reset ratio
105% typically
Min = 30 ms
Max = 45 ms
Table 31. Full-scheme distance protection, quadrilateral for earth faults ZMMPDIS
Function
Range or value
Accuracy
Number of zones
(10-30)% of IBase
(0.50-3000.00) W/phase
(0.10-1000.00) /phase
(0.50-9000.00) /phase
(0.50-3000.00) /phase
(1.00-9000.00) W/loop
Dynamic overreach
(0.000-60.000) s
Operate time
25 ms typically
IEC 60255-121
Reset ratio
105% typically
Min = 20 ms
Max = 35 ms
ABB
57
Range or value
Accuracy
(1.003000.00) W/phase
(570) degrees
Table 33. Distance measuring zone, quadrilateral characteristic, separate settings ZMRPDIS, ZMRAPDIS
Function
Range or value
Accuracy
Number of zones
(5-1000)% of IBase
(10-1000)% of IBase
(0.10-3000.00) /
phase
(0.01-1000.00) /
phase
(0.10-9000.00) /
phase
(0.01-3000.00) /
phase
(0.10-9000.00) /loop
(0.10-3000.00) /loop
Dynamic overreach
<5% at 85 degrees
measured with CVTs
and 0.5<SIR<30
(0.000-60.000) s
Operate time
25 ms typically
IEC 60255-121
Reset ratio
105% typically
Min = 20 ms
Max = 35 ms
58
ABB
Table 34. Phase selection with load encroachment, quadrilateral characteristic FRPSPDIS
Function
Range or value
Accuracy
(5-500)% of IBase
1.0% of Ir at I Ir
1.0% of I at I > Ir
(0.503000.00) /phase
(0.101000.00) /phase
(0.509000.00) /phase
(0.503000.00) /phase
(1.009000.00) /loop
(0.503000.00) /loop
(1.003000.00) /phase
(5-70) degrees
Reset ratio
105% typically
Range or value
Accuracy
Number of zones
3 selectable
directions, 3 fixed
directions
(5-6000)% of IBase
1.0% of Ir
Dynamic overreach
< 5% at 85 deg
measured with CVTs
and 0.5 < SIR < 30
(0.000-60.000) s
Operate time
16 ms typically
IEC 60255-121
Min = 20 ms
Max = 35 ms
Reset ratio
105% typically
ABB
59
Range or value
Accuracy
Reactive reach
(0.10-3000.00) W/phase
Resistive reach
(0.101000.00) W/loop
(0.000-60.000) s
(0.000-60.000) s
(5-30)% of IBase
1.0% of Ir
Range or value
Accuracy
Permitted maximum
operating time difference
between higher and lower
zone
(0.000 60.0000) s
(0.000 60.0000) s
(0.000 60.0000) s
(0.000 60.0000) s
(0.000 60.0000) s
Range or value
Accuracy
Impedance reach
2.0% of Ur/Ir
(1 - 20)
Range or value
Accuracy
Impedance reach
5.0 degrees
5.0 degrees
(1 - 20)
60
ABB
Range or value
Accuracy
(1 - 100)% of UBase
0.5% of Ur
< 105%
(5 - 300)% of UBase
0.5% of Ur for U Ur
0.5% of U for U > Ur
> 95%
1.0% of Ir for I Ir
1.0% of I for I > Ir
> 95%
(0.000 - 60.000) s
(0.000 - 60.000) s
(0.000 - 60.000) s
Operating mode
No Filter, NoPref
Cyclic: 1231c, 1321c
Acyclic: 123a, 132a, 213a, 231a, 312a, 321a
Range or value
Number of zones
(3.0 - 200.0)% of Zr
Forward reach
where Zr=UBase/
3IBase
(3.0 - 200.0)% of Zr
Reverse reach
where Zr=UBase/
3IBase
Accuracy
5.0% of set
impedance
Conditions:
Voltage range: (0.1 1.1) x Ur
Current range: (0.5 30) x Ir
5.0% of set
impedance
Conditions:
Voltage range: (0.1 1.1) x Ur
Current range: (0.5 30) x Ir
Impedance angle
(5 - 90) degrees
Reset ratio
105% typically
Min = 15 ms
Independent time
delay to operate at
1.2 to 0.8 x set
impedance
ABB
Max = 35 ms
(0.000 60.000) s
0.2% or 40 ms
whichever is greater
61
Current protection
Table 42. Instantaneous phase overcurrent protection PHPIOC
Function
Range or value
Accuracy
Operate current
(5-2500)% of lBase
1.0% of Ir at I Ir
1.0% of I at I > Ir
Reset ratio
Min. = 15 ms
Max. = 25 ms
Min. = 15ms
Max. = 25ms
10 ms typically at 0 to 2 x Iset
Min. = 5ms
Max. = 15 ms
Min. = 25ms
Max. = 40 ms
2 ms typically at 0 to 10 x Iset
Dynamic overreach
< 5% at t = 100 ms
Setting range
Accuracy
Operate current
(5-2500)% of lBase
1.0% of Ir at I Ir
1.0% of I at I > Ir
Reset ratio
(1-10000)% of lBase
1.0% of Ir at I Ir
1.0% of I at I > Ir
(40.065.0) degrees
2.0 degrees
(40.089.0) degrees
2.0 degrees
(5100)% of fundamental
2.0% of Ir
(0.000-60.000) s
0.2 % or 35 ms whichever is
greater
(0.000-60.000) s
2.0 % or 40 ms whichever is
greater
16 curve types
Min. = 15 ms
Min. = 15 ms
10 ms typically at 0 to 2 x Iset
15 ms typically
62
Max. = 30 ms
Max. = 30 ms
ABB
Range or value
Accuracy
Operate current
(5-2500)% of lBase
1.0% of Ir at I Ir
1.0% of I at I > Ir
Reset ratio
Min. = 15 ms
Max. = 25 ms
Min. = 15 ms
Max. = 25 ms
10 ms typically at 0 to 2 x Iset
Min. = 5 ms
Max. = 15 ms
Min. = 25 ms
Max. = 35 ms
2 ms typically at 0 to 10 x Iset
Dynamic overreach
< 5% at t = 100 ms
Table 45. Four step residual overcurrent protection EF4PTOC technical data
Function
Range or value
Accuracy
Operate current
(1-2500)% of lBase
1.0% of Ir at I Ir
1.0% of I at I > Ir
Reset ratio
2.0 degrees
(1100)% of lBase
(0.000-60.000) s
0.2% or 35 ms whichever is
greater
16 curve types
(5100)% of fundamental
2.0% of Ir
(1100)% of UBase
0.5% of Ur
(2-100)% of IBase
1.0% of Ir
(0.50-1000.00) W/phase
(0.503000.00) W/phase
Min = 15 ms
Max = 30 ms
Min = 15 ms
Max = 30 ms
10 ms typically at 0 to 2 x Iset
15 ms typically
ABB
63
Range or value
Accuracy
(1-2500)% of lBase
1.0% of Ir at I Ir
Reset ratio
(0.000-60.000) s
0.2% or 35 ms whichever is
greater
16 curve types
1.0% of Ir at I Ir
2.0 degrees
(1100)% of IBase
1.0% of I at I > Ir
1.0% of I at I > Ir
2.5% of I at I > Ir
Minimum polarizing voltage
(1100)% of UBase
0.5% of Ur
(2-100)% of IBase
1.0% of Ir
(0.50-1000.00) W/phase
(0.503000.00) W/phase
Min = 15 ms
Max = 30 ms
Min = 15 ms
Max = 30 ms
10 ms typically at 0 to 2 x Iset
15 ms typically
Transient overreach
<10% at = 100 ms
64
ABB
Table 47. Sensitive directional residual overcurrent and power protection SDEPSDE
Function
Range or value
Accuracy
(0.25-200.00)% of lBase
1.0% of Ir at I Ir
directional residual
overcurrent
Operate level for 3I03U0
1.0% of I at I > Ir
(0.25-200.00)% of SBase
1.0% of Sr at S Sr
1.0% of S at S > Sr
(0.25-200.00)% of lBase
residual overcurrent
1.0% of Ir at Ir
1.0% of I at I > Ir
(1.00-400.00)% of lBase
(1.00-200.00)% of UBase
(0.25-200.00)% of lBase
(1.00-300.00)% of UBase
Min = 40 ms
Min = 40 ms
Min = 115 ms
Min = 25 ms
Inverse characteristics
16 curve types
2.0 degrees
(0 to 90) degrees
2.0 degrees
ABB
1.0% of Ir at I Ir
1.0% of I at I > Ir
0.5% of Ur at U Ur
0.5% of U at U > Ur
1.0% of Ir at I Ir
1.0% of I at I > Ir
0.5% of Ur at U Ur
0.5% of U at U > Ur
Max = 65 ms
Max = 65 ms
Max = 165 ms
Max = 65 ms
65
Range or value
Accuracy
Reference current
(2-400)% of IBase
1.0% of Ir
Reference temperature
(0-300)C, (0 - 600)F
1.0C, 2.0F
Operate time:
Alarm temperature
(0-200)C, (0-400)F
2.0C, 4.0F
Operate temperature
(0-300)C, (0-600)F
2.0C, 4.0F
(0-300)C, (0-600)F
2.0C, 4.0F
2
2
I - Ip
t = t ln
2 2 TTrip - TAmb 2
I ref
I - Ip - T
ref
(Equation 1)
EQUATION13000039 V2 EN
Range or value
Accuracy
(30250)% of IBase
1.0% of Ir
Operate time:
I 2 - I p2
t = t ln
I 2 - I ref 2
EQUATION1356 V2 EN
occurs
Time constant = (1500)
minutes
(Equation 2)
Operate current
(50250)% of IBase
1.0% of Ir
66
ABB
Range or value
Accuracy
(5-200)% of lBase
1.0% of Ir at I Ir
1.0% of I at I > Ir
> 95%
(2-200)% of lBase
1.0% of Ir at I Ir
1.0% of I at I > Ir
> 95%
(5-200)% of lBase
1.0% of Ir at I Ir
1.0% of I at I > Ir
Reset ratio
> 95%
10 ms typically
15 ms maximum
(0.000-60.000) s
0.2% or 15 ms whichever is
greater
(0.000-60.000) s
0.2% or 15 ms whichever is
greater
(0.000-60.000) s
0.2% or 20 ms whichever is
greater
(0.000-60.000) s
0.2% or 20 ms whichever is
greater
(0.000-60.000) s
0.2% or 15 ms whichever is
greater
Range or value
Accuracy
Operate current
(0100)% of IBase
1.0% of Ir
(0.000-60.000) s
Range or value
Accuracy
Power level
for Step 1 and Step 2
(0.0500.0)% of SBase
1.0% of Sr at S Sr
1.0% of S at S > Sr
where
S r = 1.732 U r I r
Characteristic angle
for Step 1 and Step 2
(-180.0180.0) degrees
2.0 degrees
(0.01-6000.00) s
ABB
67
Range or value
Accuracy
Power level
for Step 1 and Step 2
(0.0500.0)% of SBase
1.0% of Sr at S Sr
Characteristic angle
for Step 1 and Step 2
(-180.0180.0) degrees
Min =10 ms
1.0% of S at S > Sr
2.0 degrees
Max = 25 ms
Reset time, start at 2 to 0.5 x Sr and k=0.000
Min = 35 ms
Max = 55 ms
(0.01-6000.00) s
Range or value
Accuracy
(5100)% of IBase
1.0% of Ir
1.0% of Ir
(0.000-60.000) s
(0.010-60.000) s
Min = 25 ms
Max = 35 ms
Min = 5 ms
Max = 20 ms
68
ABB
Range or value
Accuracy
(10-900)% of lBase
2.0% of Ir at I Ir
2.0% of I at I > Ir
Min = 5 ms
Max = 20 ms
Min = 25 ms
Max = 40 ms
2 ms typically at 0 to 2 x Iset
1 ms typically at 0 to 10 x Iset
10 ms typically
(5-100)% of IBase
1.0% of Ir
(4-1000)% of IBase
1.0% of Ir at I Ir
1.0% of I at I > Ir
(10-900)%
1.0% of Sr at S Sr
1.0% of S at S > Sr
(10-500)%
(80-200)%
20% or 200 ms
whichever is greater
(0.05-6000.00) s
20% or 200 ms
whichever is greater
(0.05-60.00) s
20% or 200 ms
whichever is greater
(0.00-6000.00) s
0.2% or 30 ms
whichever is greater
(0.00-6000.00) s
0.2% or 60 ms
whichever is greater
(1.00-6000.00) s
0.2% or 60 ms
whichever is greater
(0.00-6000.00) s
0.2% or 35 ms
whichever is greater
ABB
0.5% of Ur at U Ur
0.5% of U at U > Ur
0.5% of Ur at U Ur
0.5% of U at U > Ur
69
Table 56. Negative sequence time overcurrent protection for machines NS2PTOC
Function
Range or value
Accuracy
(3-500)% of IBase
1.0% of Ir at I Ir
1.0% of I at I > Ir
Reset ratio
>95%
Min. = 15 ms
Max. = 30 ms
Min. = 15 ms
Max. = 30 ms
Time characteristics
Definite or Inverse
K=1.0-99.0
5.0% or 40 ms whichever is
greater
10.0% or 40 ms whichever is
greater
(0.000-60.000) s
5.0% or 40 ms whichever is
greater
(0.00-6000.00) s
0.2% or 35 ms whichever is
greater
(0.00-6000.00) s
0.2% or 35 ms whichever is
greater
(0.00-6000.00) s
0.2% or 35 ms whichever is
greater
I 22t = K
70
I 22t = K
ABB
Voltage protection
Table 57. Two step undervoltage protection UV2PTUV
Function
Range or value
Accuracy
(1.0100.0)% of UBase
0.5% of Ur
Absolute hysteresis
(0.050.0)% of UBase
0.5% of Ur
(150)% of UBase
0.5% of Ur
Inverse time characteristics for step 1 and step 2, see table 119
(0.00-6000.00) s
(0.000-60.000) s
(0.00060.000) s
Min= 15 ms
Max= 30 ms
Min= 15 ms
Max= 30 ms
Min= 5 ms
Max= 25 ms
Min= 15 ms
Max= 35 ms
15 ms typically
ABB
71
Range or value
Accuracy
(1.0-200.0)% of UBase
0.5% of Ur at U Ur
0.5% of U at U > Ur
Absolute hysteresis
(0.050.0)% of UBase
0.5% of Ur at U Ur
0.5% of U at U > Ur
(0.00 - 6000.00) s
0.2% or 45 ms whichever is
greater
(0.000-60.000) s
0.2% or 45 ms whichever is
greater
(0.000-60.000) s
Min. = 15 ms
Max. = 30 ms
Min. = 15 ms
Max. = 30 ms
Min. = 20 ms
Max. = 35 ms
Min. = 5 ms
Max. = 25 ms
10 ms typically at 0 to 2 x Uset
15 ms typically
72
ABB
Range or value
Accuracy
(1.0-200.0)% of UBase
0.5% of Ur at U Ur
0.5% of U at U > Ur
(0.050.0)% of UBase
Absolute hysteresis
0.5% of Ur at U Ur
0.5% of U at U > Ur
Inverse time characteristics for low and high step, see table 120
(0.006000.00) s
0.2% or 45 ms whichever is
greater
(0.00060.000) s
0.2% or 45 ms whichever is
greater
(0.000-60.000) s
0.2% or 45 ms whichever is
greater
Min. = 15 ms
Max. = 30 ms
Min. = 15 ms
Max. = 30 ms
Min. = 20 ms
Max. = 35 ms
Min. = 5 ms
Max. = 25 ms
10 ms typically at 0 to 2 x Uset
15 ms typically
Range or value
Accuracy
(100180)% of (UBase/frated)
0.5% of U
0.5% of Ur at U Ur
0.5% of U at U > Ur
(100200)% of (UBase/frated)
0.5% of U
Curve type
IEEE : t =
(0.18 k )
( M - 1) 2
EQUATION1319 V1 EN
(Equation 3)
where M = (E/f)/(Ur/fr)
Minimum time delay for inverse
function
(0.00060.000) s
(0.009000.00) s
(0.009000.00)
ABB
73
Range or value
Accuracy
(2.0100.0) % of UBase
0.5% of Ur
(1.0100.0) % of UBase
0.5% of Ur
(0.00060.000)s
(0.00060.000)s
(0.00060.000)s
Range or value
Accuracy
Operate voltage
(1100)% of UBase
0.5% of Ur
(0.05060.000) s
(0.00060.000) s
(0.00060.000) s
(0.00060.000) s
74
ABB
Frequency protection
Table 63. Underfrequency protection SAPTUF
Function
Range or value
Accuracy
(35.00-75.00) Hz
2.0 mHz
fn = 50 Hz
fn = 60 Hz
Min. = 80 ms
Max. = 95 ms
Min. = 65 ms
Max. = 80 ms
Min. = 15 ms
Max. = 30 ms
(0.000-60.000)s
(0.000-60.000)s
Settings:
UNom=(50-150)% of Ubase
to fset - 0.02 Hz
Reset time, definite time function at fset - 0.02 Hz to
fset + 0.02 Hz
Voltage dependent time delay
UMin=(50-150)% of Ubase
Exponent=0.0-5.0
tMax=(0.01060.000)s
tMin=(0.01060.000)s
U - UMin
t=
UNom - UMin
Exponent
(Equation 4)
EQUATION1182 V1 EN
U=Umeasured
Table 64. Overfrequency protection SAPTOF
Function
Range or value
Accuracy
(35.00-90.00) Hz
2.0 mHz
fn = 50Hz
Min. = 80 ms
Max. = 95 ms
fn = 60 Hz
Min. = 65 ms
Max. = 80 ms
Min. = 15 ms
Max. = 30 ms
(0.000-60.000)s
0.2% 100 ms
whichever is greater
(0.000-60.000)s
ABB
75
Range or value
Accuracy
(-10.00-10.00) Hz/s
10.0 mHz/s
(45.00-65.00) Hz
2.0 mHz
(0.000-60.000) s
(0.200-60.000) s
(0.000-60.000) s
76
ABB
Multipurpose protection
Table 66. General current and voltage protection CVGAPC
Function
Range or value
Accuracy
Base current
(1 - 99999) A
Base voltage
(0.05 - 2000.00) kV
(2 - 5000)% of IBase
(2 - 150)% of IBase
(0.00 - 6000.00) s
0.2% or 35 ms whichever is
greater
(0.00 - 6000.00) s
0.2% or 35 ms whichever is
greater
Min = 15 ms
Max = 30 ms
Min = 15 ms
Max = 30 ms
Min = 15 ms
Max = 30 ms
Min = 15 ms
Max = 30 ms
0.5% of Ur
0.5% of Ur for U Ur
Overcurrent:
Undercurrent:
0.5% of Ur for U Ur
0.5% of U for U > Ur
ABB
77
Range or value
Accuracy
(0.00 - 6000.00) s
0.2% or 35 ms whichever is
greater
(0.00 - 6000.00) s
0.2% or 35 ms whichever is
greater
Min = 15 ms
Max = 30 ms
Min = 15 ms
Max = 30 ms
Min = 15 ms
Max = 30 ms
Min = 15 ms
Max = 30 ms
Overvoltage:
Undervoltage:
2.0 degrees
(1 to 90) degrees
2.0 degrees
> 95%
< 105%
> 95%
< 105%
10 ms typically at 0 to 2 x Iset
15 ms typically
10 ms typically at 2 to 0 x Iset
15 ms typically
15 ms typically
15 ms typically
Overcurrent:
Undercurrent:
Overvoltage:
Undervoltage:
78
ABB
Range or value
Accuracy
Start overcurrent
1.0% of Ir at IIr
1.0% of I at I>Ir
> 95%
Min = 15 ms
Max = 30 ms
Min = 15 ms
Max = 30 ms
(0.00 - 6000.00) s
0.2% or 35 ms whichever is
greater
13 curve types
ANSI/IEEE C37.112
IEC 60255151
5.0% or 40 ms whichever is
greater
0.10 k 3.00
1.5 x Iset I 20 x Iset
See Table and Table
(0.00 - 60.00) s
0.2% or 35 ms whichever is
greater
1.0% of Ur
Start undervoltage
0.5% of Ur
< 105%
Min = 15 ms
Max = 30 ms
Reset time start undervoltage at 0 to 2 x Uset
Min = 15 ms
Max = 30 ms
Independent time delay to operate, undervoltage at 2 to 0 x Uset
(0.00 - 6000.00) s
0.2% or 35 ms whichever is
greater
0.25% of Ur
Overcurrent:
Critical impulse time
Impulse margin time
10 ms typically at 0 to 2 x Iset
Undervoltage:
Critical impulse time
Impulse margin time
ABB
15 ms typically
15 ms typically
79
Range or value
Accuracy
Operate current
(10-200)% of IBase
10.0% of Ir at I Ir
10.0% of I at I > Ir
>90%
Block current
(20-500)% of IBase
5.0% of Ir at I Ir
5.0% of I at I > Ir
Range or value
Accuracy
(1-100)% of UBase
0.5% of Ur
(1100)% of IBase
0.5% of Ir
(1-100)% of UBase
0.5% of Ur
(1100)% of IBase
0.5% of Ir
(1-100)% of UBase
10.0% of Ur
(1100)% of IBase
10.0% of Ir
(1-100)% of UBase
0.5% of Ur
(1100)% of IBase
0.5% of Ir
(1-100)% of UBase
0.5% of Ur
(1100)% of IBase
0.5% of Ir
Min. = 10 ms
Max. = 25 ms
Min. = 15 ms
Max. = 30 ms
80
ABB
Range or value
Accuracy
(10.0-80.0)% of UBase
0.5% of Ur
Reset ratio
<110%
Min = 5 ms
Min = 15 ms
(10.0-80.0)% of UBase
0.5% of Ur
Reset ratio
<110%
Min = 5 ms
Min = 15 ms
ABB
Max = 15 ms
Max = 30 ms
Max = 15 ms
Max = 30 ms
81
Control
Table 71. Synchronizing, synchrocheck and energizing check SESRSYN
Function
Range or value
Accuracy
(50.0-120.0)% of UBase
0.5% of Ur at U Ur
0.5% of U at U > Ur
> 95%
(0.003-1.000) Hz
2.5 mHz
Phase angle difference limit between bus and line for synchrocheck
(5.0-90.0) degrees
2.0 degrees
Voltage difference limit between bus and line for synchronizing and
synchrocheck
(0.02-0.5) p.u
0.5% of Ur
Time delay output for synchrocheck when angle difference between bus
and line jumps from PhaseDiff + 2 degrees to PhaseDiff - 2 degrees
(0.000-60.000) s
0.2% or 35 ms whichever is
greater
(0.003-0.250) Hz
2.5 mHz
(0.050-0.500) Hz
2.5 mHz
(0.000-0.500) Hz/s
10.0 mHz/s
(0.050-60.000) s
0.2% or 15 ms whichever is
greater
(0.000-6000.00) s
0.2% or 35 ms whichever is
greater
(0.000-60.000) s
0.2% or 35 ms whichever is
greater
(50.0-120.0)% of UBase
0.5% of Ur at U Ur
0.5% of U at U > Ur
> 95%
(10.0-80.0)% of UBase
0.5% of Ur
< 105%
(50.0-180.0)% of UBase
0.5% of Ur at U Ur
0.5% of U at U > Ur
Time delay for energizing check when voltage jumps from 0 to 90% of
Urated
(0.000-60.000) s
Min = 15 ms
Max = 30 ms
Operate time for energizing function when voltage jumps from 0 to 90%
of Urated
Min = 70 ms
Max = 90 ms
82
ABB
Range or value
Accuracy
Transformer reactance
(0.1200.0), primary
Time delay for lower command when fast step down mode is activated
(1.0100.0) s
(85.0120.0)% of UBase
0.25 % of Ur
(0.29.0)% of UBase
(0.19.0)% of UBase
(80180)% of UBase
0.5% of Ur
(70120)% of UBase
0.5% of Ur
(50120)% of UBase
0.5% of Ur
(31000) s
0.2% or 600 ms
whichever is greater
(11000) s
0.2% or 600 ms
whichever is greater
(3120) s
0.2% or 600 ms
whichever is greater
Line resistance
(0.00150.00), primary
Line reactance
(-150.00150.00), primary
(-20.020.0)% of UBase
(-20.020.0)% of UBase
(306000) s
0.2% or 600 ms
whichever is greater
(0100)% of I1Base
(5250)% of I1Base
1.0% of Ir at IIr
1.0% of I at I>Ir
(030) operations/hour
(0100) operations/day
(1120) minutes
(330) operations/window
(-9999.999999.99) MW
1.0% of Sr
(-9999.999999.99) MVAr
1.0% of Sr
(16000) s
0.2% or 600 ms
whichever is greater
(163)
(0.00025.000) mA
ABB
83
Range or value
Accuracy
(160) s
0.2% or 200 ms
whichever is greater
(1120) s
0.2% or 200 ms
whichever is greater
(0.510.0) s
0.2% or 200 ms
whichever is greater
84
ABB
Scheme communication
Table 73. Scheme communication logic for residual overcurrent protection ECPSCH
Function
Range or value
Accuracy
Scheme type
Permissive Underreaching
Permissive Overreaching
Blocking
Communication scheme
coordination time
(0.000-60.000) s
Table 74. Current reversal and weak-end infeed logic for residual overcurrent protection ECRWPSCH
Function
Range or value
Accuracy
Off
Echo
Echo & Trip
(5-70)% of UBase
0.5% of Ur
(0.000-60.000) s
(0.000-60.000) s
(0.00060.000) s
ABB
85
Logic
Table 75. Tripping logic common 3-phase output SMPPTRC
Function
Range or value
Accuracy
Trip action
(0.000-60.000) s
(0.020-0.500) s
(0.000-60.000) s
Range or value
Accuracy
fast
medium
normal
LogicAND
60
60
160
LogicOR
60
60
160
LogicXOR
10
10
20
LogicInverter
30
30
80
LogicSRMemory
10
10
20
LogicRSMemory
10
10
20
LogicGate
10
10
20
LogicTimer
10
10
20
(0.00090000.000) s
0.5% 10 ms
LogicPulseTimer
10
10
20
(0.00090000.000) s
0.5% 10 ms
LogicTimerSet
10
10
20
(0.00090000.000) s
0.5% 10 ms
LogicLoopDelay
10
10
20
(0.00090000.000) s
0.5% 10 ms
Boolean 16 to Integer
Boolean 16 to integer
with Logic Node
Integer to Boolean 16
Integer to Boolean 16
with Logic Node
Table 77. Elapsed time integrator with limit transgression and overflow supervision TEIGAPC
Cycle time (ms)
Function
Elapsed time integration
86
Range or value
Accuracy
0 ~ 999999.9 s
0 ~ 999999.9 s
100
0 ~ 999999.9 s
ABB
Monitoring
Table 78. Measurements CVMMXN
Function
Range or value
Accuracy
Frequency
(0.95-1.05) fr
2.0 mHz
Voltage
(0.1-1.5) Ur
0.5% of Ur at UUr
0.5% of U at U > Ur
Connected current
(0.2-4.0) Ir
0.5% of Ir at I Ir
0.5% of I at I > Ir
Active power, P
Reactive power, Q
1.0% of Sr at S Sr
1.0% of S at S > Sr
Conditions:
0.8 x Ur < U < 1.2 Ur
0.02
Range or value
Accuracy
(0.1-4.0) Ir
0.3% of Ir at I 0.5 Ir
0.3% of I at I > 0.5 Ir
(0.1-4.0) Ir
Range or value
Accuracy
Voltage
(10 to 300) V
0.5% of U at U 50 V
0.2% of U at U > 50 V
Phase angle
(10 to 300) V
0.5 at U 50 V
0.2 at U > 50 V
Range or value
Accuracy
Voltage
(5 to 175) V
0.5% of U at U 50 V
0.2% of U at U > 50 V
Phase angle
(5 to 175) V
0.5 at U 50 V
0.2 at U > 50 V
ABB
87
Range or value
Accuracy
(0.14.0) Ir
0.3% of Ir at I 0.5 Ir
(0.11.0) Ir
(0.11.0) Ir
Phase angle
(0.14.0) Ir
Range or value
Accuracy
(10 to 300) V
0.3% of U at U 50 V
0.2% of U at U > 50 V
(10 to 300) V
0.3% of U at U 50 V
0.2% of U at U > 50 V
(10 to 300) V
0.3% of U at U 50 V
0.2% of U at U > 50 V
Phase angle
(10 to 300) V
0.3 at U 50 V
0.2 at U > 50 V
Range or value
Accuracy
mA measuring function
5, 10, 20 mA
0-5, 0-10, 0-20, 4-20 mA
(-20.00 to +20.00) mA
(-20.00 to +20.00) mA
(-20.00 to +20.00) mA
(-20.00 to +20.00) mA
(0.0-20.0) mA
Range or value
Accuracy
Counter value
0-65535
88
ABB
Range or value
Accuracy
Pre-fault time
(0.059.90) s
Post-fault time
(0.110.0) s
Limit time
(0.510.0) s
1 ms
30 + 10 (external + internally
derived)
96
30
96
150
Maximum total recording time (3.4 s recording time and maximum number of
channels, typical value)
Sampling rate
1 kHz at 50 Hz
1.2 kHz at 60 Hz
Recording bandwidth
(5-300) Hz
Function
Buffer capacity
1000
Resolution
1 ms
Accuracy
Function
Buffer capacity
96
100
Function
Buffer capacity
150
100
Resolution
1 ms
Accuracy
Depending on time
synchronizing
ABB
89
Value
Maximum number of analog inputs
30
100
Value
Maximum number of analog inputs
40
96
100
Maximum total recording time (3.4 s recording time and maximum number
of channels, typical value)
90
ABB
Metering
Table 92. Pulse-counter logic PCFCNT
Function
Setting range
Accuracy
Input frequency
(13600) s
Range or value
Accuracy
Energy metering
ABB
91
Station communication
Table 94. IEC 61850-8-1 communication protocol
Function
Value
Protocol
IEC 61850-8-1
100BASE-FX
Protocol
IEC 6085103
9600 or 19200 Bd
Protocol
DNP3.0
30019200 Bd
Protocol
TCP/IP, Ethernet
100 Mbit/s
Value
Protocol
IEC 61850-9-2LE
100BASE-FX
Value
Protocol
LON
Communication speed
1.25 Mbit/s
Value
Protocol
SPA
Communication speed
Slave number
1 to 899
Value
Protocol
IEC 60870-5-103
Communication speed
9600, 19200 Bd
Range or value
Optical connector
Fibre diameter
92
ABB
Range or value
Optical connector
Fibre diameter
Range or value
Connector, X.21
Standard
CCITT X21
Communication speed
64 kbit/s
Insulation
1 kV
100 m
Range or value
Communication speed
240019200 bauds
External connectors
Table 103. IEC 62439-3 Edition 1 and Edition 2 parallel redundancy protocol
Function
Value
Protocol
IEC 61850-8-1
Communication speed
100 Base-FX
ABB
93
Remote communication
Table 104. Line data communication module
Characteristic
Range or value
Type of LDCM
Type of fibre
Graded-index
multimode
62.5/125 m
Singlemode 9/125 m
Singlemode 9/125 m
820 nm
865 nm
792 nm
1310 nm
1330 nm
1290 nm
1550 nm
1580 nm
1520 nm
13 dB (typical
distance about 3
km *)
9 dB (typical
distance about 2
km *)
22 dB (typical
distance 80 km *)
Optical connector
Type ST
Type FC/PC
Type FC/PC
Protocol
C37.94
C37.94
implementation **)
Data transmission
Synchronous
Synchronous
Synchronous
2 Mb/s / 64 kbit/s
2 Mb/s / 64 kbit/s
2 Mb/s / 64 kbit/s
Clock source
Internal or derived
from received
signal
Internal or derived
from received signal
94
ABB
Hardware
IED
Table 105. Case
Material
Steel sheet
Front plate
Surface treatment
Finish
Table 106. Water and dust protection level according to IEC 60529
Front
IP20
Rear side
Weight
6U, 1/2 x 19
10 kg
6U, 3/4 x 19
15 kg
6U, 1/1 x 19
18 kg
Connection system
Table 108. CT and VT circuit connectors
Connector type
250 V AC, 20 A
4 mm2 (AWG12)
2 x 2.5 mm2 (2 x AWG14)
250 V AC, 20 A
4 mm2 (AWG12)
Connector type
Rated voltage
250 V AC
300 V AC
3 mm2 (AWG14)
ABB
95
Value
Recording manner
List size
Value
1 ms
Time tagging error with synchronization once/min (minute pulse synchronization), events and sampled
measurement values
1.0 ms typically
1.0 ms typically
Range or value
Accuracy
Receiver
1s relative UTC
<30 minutes
<15 minutes
<5 minutes
Value
26 db @ 1.6 GHz
50 ohm
Lightning protection
Accuracy
+/-1s
96
ABB
Rated value
Electrical connector:
Electrical connector IRIG-B
BNC
Pulse-width modulated
5 Vpp
Amplitude modulated
low level
high level
1-3 Vpp
3 x low level, max 9 Vpp
Supported formats
Accuracy
Input impedance
100 k ohm
Optical connector:
Optical connector PPS and IRIG-B
Type ST
Type of fibre
Supported formats
Accuracy
+/- 1s
ABB
97
Inverse characteristic
Table 115. ANSI Inverse time characteristics
Function
Range or value
Accuracy
Operating characteristic:
ANSI/IEEE C37.112 ,
2.0% or 40 ms
whichever is greater
A
t=
+ B k + tDef
P
I - 1
EQUATION1249-SMALL V2 EN
Reset characteristic:
t =
(I
tr
2
-1
EQUATION1250-SMALL V1 EN
I = Imeasured/Iset
ANSI Extremely Inverse
98
ABB
Range or value
Accuracy
Operating characteristic:
t =
A
P
k
( I - 1)
EQUATION1251-SMALL V1 EN
I = Imeasured/Iset
IEC Normal Inverse
A=0.14, P=0.02
A=13.5, P=1.0
IEC Inverse
A=0.14, P=0.02
A=80.0, P=2.0
A=0.05, P=0.04
A=120, P=1.0
Programmable characteristic
Operate characteristic:
t =
A
P
(I - C )
+ B k
EQUATION1370-SMALL V1 EN
Reset characteristic:
t =
(I
TR
PR
- CR
EQUATION1253-SMALL V1 EN
I = Imeasured/Iset
Table 117. RI and RD type inverse time characteristics
Function
Range or value
Accuracy
t =
0.339 -
0.236
I
EQUATION1137-SMALL V1 EN
I = Imeasured/Iset
RD type logarithmic inverse characteristic
t = 5.8 - 1.35 In
I
k
EQUATION1138-SMALL V1 EN
I = Imeasured/Iset
ABB
99
Range or value
Accuracy
Type A curve:
5.0% or 45 ms
whichever is greater
t =
U -U >
U>
EQUATION1436-SMALL V1 EN
U> = Uset
U = Umeasured
k = (0.05-1.10) in steps of 0.01
Type B curve:
t =
k 480
32 U - U > - 0.5
U >
2.0
- 0.035
EQUATION1437-SMALL V1 EN
Type C curve:
t =
k 480
32 U - U > - 0.5
U >
3.0
- 0.035
EQUATION1438-SMALL V1 EN
Programmable curve:
t =
kA
B U - U >
U >
-C
+D
EQUATION1439-SMALL V1 EN
100
ABB
Range or value
Accuracy
Type A curve:
5.0% or 45 ms
whichever is greater
t =
U < -U
U<
EQUATION1431-SMALL V1 EN
U< = Uset
U = Umeasured
Type B curve:
t =
k 480
32 U < -U - 0.5
U <
2.0
+ 0.055
EQUATION1432-SMALL V1 EN
U< = Uset
U = Umeasured
Programmable curve:
kA
+D
t =
P
U < -U
-C
B
U <
EQUATION1433-SMALL V1 EN
U< = Uset
U = Umeasured
ABB
101
Range or value
Accuracy
Type A curve:
k = (0.05-1.10) in steps of
0.01
t =
U -U >
U>
EQUATION1436-SMALL V1 EN
U> = Uset
U = Umeasured
k = (0.05-1.10) in steps of
0.01
Type B curve:
t =
k 480
32 U - U > - 0.5
U >
2.0
- 0.035
EQUATION1437-SMALL V1 EN
Type C curve:
t =
k = (0.05-1.10) in steps of
0.01
k 480
32 U - U > - 0.5
U >
3.0
- 0.035
EQUATION1438-SMALL V1 EN
Programmable curve:
t =
kA
B U - U >
U >
EQUATION1439-SMALL V1 EN
102
-C
+D
k = (0.05-1.10) in steps of
0.01
A = (0.005-200.000) in
steps of 0.001
B = (0.50-100.00) in steps
of 0.01
C = (0.0-1.0) in steps of 0.1
D = (0.000-60.000) in
steps of 0.001
P = (0.000-3.000) in steps
of 0.001
ABB
2.0
X00
Differential protection
Impedance protection
Current protection
C
Voltage protection
D
Control
Langu
age
B
1
Casing
and
Mountin
g
Conne
ction
and
power
0
-
H
M
I
Frequency protection
00
Multipurpose
protection
General
calculation
Scheme communication
K
Logic
Monitoring
Analog input
Station communication
Binary input/output
RET670*
X00
RET670*
Software version
2.0
Configuration alternatives
RET670 Transformer protection
F00
N00
Selection:
ACT configuration
No ACT configuration downloaded
X00
ABB
8
0
10
11
12
13
14
103
Function
identification
Ordering no
Positi
on
Available
qty
T2WPDIF
1MRK005904-FA
0-2
T3WPDIF
1MRK005904-GA
0-2
HZPDIF
1MRK005904-HA
0-6
REFPDIF
1MRK005904-LA
0-3
LDRGFC
1MRK005904-TA
14
0-1
Selected
qty
Notes and
rules
Note:
One, and
only one
PDIF must
be
ordered.
104
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
ABB
Function
identification
Ordering no
Positi
on
Available
qty
Selec
ted
qty
Notes
and
rules
Note: One, and only one alternative can be selected. Selected qty is 0 for other functions in an unselected alternative.
Alternative 1 Distance protection, quadrilateral
Distance protection zone, quadrilateral characteristic
ZMQPDIS,
ZMQAPDIS
1MRK005907-AA
0-5
ZDRDIR
1MRK005907-BA
0-2
FDPSPDIS
1MRK005907-CA
0-2
FDPSPDIS
1MRK005907-CA
0-2
ZMCPDIS,
ZMCAPDIS
1MRK005907-DA
0-5
ZDSRDIR
1MRK005907-EA
0-2
Alternative 3 Distance protection, mho (mho for phase - phase fault and mho in parallel with quad for earth fault)
Fullscheme distance protection, mho characteristic
ZMHPDIS
1MRK005907-FA
0-5
ZMMPDIS,
ZMMAPDIS
1MRK005907-GA
0-5
ZDMRDIR
1MRK005907-HA
0-2
ZDARDIR
1MRK005907-KA
0-1
ZSMGAPC
1MRK005907-LA
10
0-1
FMPSPDIS
1MRK005907-MA
11
0-2
ZDRDIR
1MRK005907-BA
0-2
ZMRPDIS,
ZMRAPDIS
1MRK005907-NA
12
0-5
FRPSPDIS
1MRK005907-PA
13
0-2
ZMFPDIS
1MRK005907-SA
14
0-1
ZMFCPDIS
1MRK005907-RA
15
0-1
ZDMRDIR
1MRK005907-HA
0-2
FDPSPDIS
1MRK005907-CA
0-2
ZDARDIR
1MRK005907-KA
0-2
FMPSPDIS
1MRK005907-MA
11
0-1
ZMRPSB
1MRK005907-UA
16
0-1
PSLPSCH
1MRK005907-VA
18
0-1
PoleSlip/Out-of-step protection
PSPPPAM
1MRK005908-CA
19
0-1
Out-of-step protection
OOSPPAM
1MRK005908-GA
20
0-1
PPLPHIZ
1MRK005908-DA
22
0-1
ZGVPDIS
1MRK005907-TA
25
0-1
Alternative 6 High speed distance protection for series compensated lines, quadrilateral
Directional distance protection with phase selection, series
compensation
Optional with alternative 1
Directional impedance element for mho characteristic
Optional for alternative 3
Phase selection, quadrilateral characteristic with fixed angle
Optional for alternatives 1, 2 and 4
ABB
00
10
11
12
13
00
14
15
16
17
18
19
20
21
22
23
105
Function
identification
Ordering no
Positi
on
Available
qty
PHPIOC
1MRK005910-AA
0-8
OC4PTOC
1MRK005910-BA
0-8
EFPIOC
1MRK005910-DA
0-8
EF4PTOC
1MRK005910-EA
0-8
NS4PTOC
1MRK005910-FA
0-8
SDEPSDE
1MRK005910-GA
0-3
LCPTTR
1MRK005911-BA
0-2
LFPTTR
1MRK005911-AA
0-2
TRPTTR
1MRK005910-HA
10
0-6
CCRBRF
1MRK005910-LA
11
0-6
CCPDSC
1MRK005910-PA
14
0-2
GUPPDUP
1MRK005910-RA
15
0-2
GOPPDOP
1MRK005910-TA
16
0-2
BRCPTOC
1MRK005910-SA
17
CBPGAPC
1MRK005910-UA
18
0-6
NS2PTOC
1MRK005910-VA
19
0-2
VRPVOC
1MRK005910-XA
21
0-3
Selected
qty
Notes and
rules
Function
identification
Ordering no
Positi
on
Available
qty
UV2PTUV
1MRK005912-AA
0-3
OV2PTOV
1MRK005912-BA
0-3
ROV2PTOV
1MRK005912-CA
0-3
Overexcitation protection
OEXPVPH
1MRK005912-DA
0-2
VDCPTOV
1MRK005912-EA
0-2
LOVPTUV
1MRK005912-GA
Selected
qty
Notes and
rules
Selected
qty
Notes and
rules
Selected
Qty
Notes and
rules
00
Function
identification
Ordering no
positi
on
Available
qty
Underfrequency protection
SAPTUF
1MRK005914-AA
0-6
Overfrequency protection
SAPTOF
1MRK005914-BA
0-6
SAPFRC
1MRK005914-CA
0-6
Function
identification
Ordering no
Positi
on
Available
qty
CVGAPC
1MRK005915-AA
0-9
106
ABB
Function
identification
Ordering no
Positi
on
Available
qty
SMAIHPAC
1MRK005915-KA
0-6
Selected
qty
Notes and
rules
Selected
qty
Notes and
rules
Function
identification
Ordering no
Positi
on
Available
qty
CCSSPVC
1MRK005916-AA
0-5
FUFSPVC
1MRK005916-BA
0-4
VDSPVC
1MRK005916-CA
0-2
10
11
Function
identification
Ordering no
Positi
on
Available
qty
SESRSYN
1MRK005917-XA
0-6
APC30
1MRK005917-CX
0-1
TR1ATCC
1MRK005917-NA
0-4
TR8ATCC
1MRK005917-PA
0-4
TCMYLTC
1MRK005917-DA
10
0-4
TCLYLTC
1MRK005917-EA
11
0-4
Selected
Qty
Notes and
rules
Note: Only
one TCC
may be
selected
8
0
Function
identification
Ordering no
Positi
on
Available
qty
ECPSCH
1MRK005920-FA
0-1
ECRWPSCH
1MRK005920-GA
0-1
Ordering no
Positi
on
Available
qty
1MRK005922-ML
0-1
1MRK005922-AX
0-1
Selected
qty
Notes and
rules
Selected
qty
Notes and
rules
ABB
Function
identification
107
Function
identification
Ordering no
Positi
on
Available
qty
Selected
qty
Notes and
rules
SSCBR
1MRK005924-HA
0-18
Ordering no
Positi
on
Available
qty
Selected
qty
Notes and
rules
1MRK005930-TA
0-6
Note:
REC670
customize
d qty = 0,
REC670
61850-9-2
qty = 6
1MRK002924-YB
0-1
Note: Not
valid in
RET670
61850-9-2
LE product
Note:
Requires
2channel
OEM
Function
identification
PRP
B1
X0
A12
Selected
Casing
1/2 x 19" case
E
Selected
108
ABB
Selection
19" rack mounting kit for 1/2 x 19" case of 2xRHGS6 or RHGS12
F
Selected
Selection
Compression terminals
Ringlug terminals
B
Selected
C
Selected
ABB
109
Selection
X0
Compression terminals
Ringlug terminals
Maximum qty=1
Maximum qty=1
12
13
14
15
16
17
18
X0
Compression terminals
Ringlug terminals
Maximum qty=1
Maximum qty=1
12
13
14
15
16
17
18
Selected
BIM
IOM
BOM/
SOM
MIM
Maximum in case
14
14 (max 4 BOM+SOM
+MIM)
11
11 (max 4 BOM+SOM
+MIM)
8 (max 4 BOM+SOM+1
MIM)
5 (max 4 BOM+SOM+1
MIM)
110
ABB
No board in slot
B1
B1
B1
B1
B1
B1
B1
B1
B1
C1
C1
C1
C1
C1
C1
C1
C1
BIM 16 inputs,
RL110-125 VDC, 50 mA
D1
D1
D1
D1
D1
D1
D1
BIM 16 inputs,
RL220-250 VDC, 50 mA
E1
E1
E1
E1
E1
E1
E2
E2
E2
E2
E2
BIMp 16 inputs,
RL110-125 VDC, 30 mA,
for pulse counting
BIM 16 inputs,
RL220-250 VDC, 30 mA,
for pulse counting
X161
X121
X151
X111
X141
X101
X131
X91
X51
X81
X41
X71
X31
Selection
X61
Binary input/output
modules
B1
B1
B1
B1
B1
C1
C1
C1
C1
C1
C1
D1
D1
D1
D1
D1
D1
D1
E1
E1
E1
E1
E1
E1
E1
E1
E2
E2
E2
E2
E2
E2
E2
E2
E2
L1
L1
L1
L1
L1
L1
L1
L1
L1
L1
L1
L1
L1
L1
M1
M1
M1
M1
M1
M1
M1
M1
M1
M1
M1
M1
M1
M1
N1
N1
N1
N1
N1
N1
N1
N1
N1
N1
N1
N1
N1
N1
P1
P1
P1
P1
P1
P1
P1
P1
P1
P1
P1
P1
P1
P1
P2
P2
P2
P2
P2
P2
P2
P2
P2
P2
P2
P2
P2
P2
ABB
111
Selection
T1
T1
T1
T1
T1
T1
T1
T1
T1
T1
T1
T1
T1
T1
T2
T2
T2
T2
T2
T2
T2
T2
T2
T2
T2
T2
T2
T2
Selected.
X302
X303
X322
X323
X313
Selection
X312
Selected
X301
X311
E
Selected.
112
ABB
Guidelines
Carefully read and follow the set of rules to ensure problem-free order management.
Please refer to the available functions table for included application functions.
PCM600 can be used to make changes and/or additions to the delivered factory configuration of the pre-configured.
To obtain the complete ordering code, please combine code from the tables, as given in the example below.
Example code: RET670 *2.0-A30X00- A02H02-B1A3-AC-KB-B-A3X0-DAB1RGN1N1XXXXXXX-AXFXXX-AX. Using the code of each position #1-12 specified as
RET670*1-2 2-3 3 3 3 3 3 3 3 3 3 3 3 3-4 4-5-6-7 7-8-9 9 9 9-10 10 10 10 10 10 10 10 10 10 10-11 11 11 11 11 11-12 12
#
RET670*
- 2
- 3
- 4
- 5
- 7
- 8
- 10
- 11
- 12
Position
SOFTWARE
#1
Version number
2.0
Version no
Selection for position #1.
Configuration alternatives
#2
Back-up
A10
A25
A30
B30
A40
B40
ACT configuration
ABB standard configuration
X00
Selection for position #2.
ABB
113
Software options
#3
No option
X
00
A
01
114
ABB
Software options
High impedance differential protection - 3
blocks
#3
B
12
B
13
B
14
A
02
C
05
C
17
C
19
C
42
C
43
D
01
D
02
D
03
D
04
E
01
H
01
H
02
H
03
H
09
H
11
H
15
H
16
H
18
M
12
M
15
M
16
M
17
ABB
115
P
03
Software options
#3
#4
B1
X0
A12
Selection for position #4.
Casing
#5
#6
19" rack mounting kit for 1/2 x 19" case of 2xRHGS6 or RHGS12
F
Selection for position #6.
#7
Compression terminals
90-250 VDC
B
Selection for position #7.
#8
C
Selection for position #8.
116
ABB
#9
Compression terminals
Ringlug terminals
X0
Compression terminals
Ringlug terminals
12
13
ABB
117
#10
X131
X121
X71
X111
X61
X101
X51
No board in slot
X91
X41
X31
X81
Make BIM with 50 mA inrush current the primary choice. BIM with 50 mA inrush current fulfill additional standards. As a consequence the EMC withstand
capability is further increased.
BIM with 30 mA inrush current is still available.
For pulse counting, for example kWh metering, the BIM with enhanced pulse counting capabilities must be used.
Note: 1BIM and 1 BOM included.
B
1
B
1
B
1
B
1
B
1
B
1
B
1
B
1
B
1
B
1
C
1
C
1
C
1
C
1
C
1
C
1
C
1
C
1
C
1
C
1
D
1
D
1
D
1
D
1
D
1
D
1
D
1
D
1
D
1
D
1
E
1
E
1
E
1
E
1
E
1
E
1
E
1
E
1
E
1
E
1
E
2
E
2
E
2
E
2
E
2
E
2
E
2
E
2
E
2
E
2
L1
L1
L1
L1
L1
L1
L1
L1
L1
M
1
M
1
M
1
M
1
M
1
M
1
M
1
M
1
M
1
N
1
N
1
N
1
N
1
N
1
N
1
N
1
N
1
N
1
P
1
P
1
P
1
P
1
P
1
P
1
P
1
P
1
P
1
P
2
P
2
P
2
P
2
P
2
P
2
P
2
P
2
P
2
T1
T1
T1
T1
T1
T1
T1
T1
T1
T2
T2
T2
T2
T2
T2
T2
T2
T2
118
ABB
Remote end communication, DNP serial comm. and time synchronization modules
X302
X303
X322
X323
X313
#11
X312
#12
X311
X301
E
Selection for position #12.
ABB
119
Quantity:
Quantity:
Quantity:
Quantity:
Quantity:
Test switch
The test system COMBITEST intended for use with the IED
670 products is described in 1MRK 512 001-BEN and 1MRK
001024-CA. Please refer to the website:
www.abb.com/substationautomation for detailed information.
Due to the high flexibility of our product and the wide variety
of applications possible the test switches needs to be
selected for each specific application.
The normally open "In test mode" contact 29-30 on the RTXP
test switches should be connected to the input of the test
function block to allow activation of functions individually
during testing.
Quantity:
Quantity:
Quantity:
Quantity:
120
ABB
Quantity:
Quantity:
RK 795 101-MA
RK 795 101-MB
Quantity:
Quantity:
RK 795 101-CB
RK 795 101-DC
Combiflex
Key switch for settings
Key switch for lock-out of settings via LCD-HMI
Quantity:
Quantity:
Quantity:
Quantity:
Quantity:
Note: To connect the key switch, leads with 10 A Combiflex socket on one end must be used.
Side-by-side mounting kit
Manuals
Note: One (1) IED Connect CD containing user documentation (Operation manual, Technical manual,
Installation manual, Commissioning manual, Application manual and Getting started guide), Connectivity
packages and LED label template is always included for each IED.
ABB
Quantity:
121
User documentation
IEC
Quantity:
ANSI
Quantity:
IEC
Quantity:
ANSI
Quantity:
IEC
Quantity:
ANSI
Quantity:
IEC
Quantity:
IEC
Quantity:
IEC
Quantity:
IEC
Quantity:
IEC
Quantity:
ANSI
Quantity:
ANSI
Quantity
IEC
Quantity:
ANSI
Quantity:
IEC
Quantity:
ANSI
Quantity:
Technical manual
Commissioning manual
122
ABB
IEC
Quantity:
ANSI
Quantity:
IEC
Quantity:
Reference information
For our reference and statistics we would be pleased to be provided with the following application data:
Country:
End user:
Station name:
Voltage level:
Related documents
kV
Identify number
Identify number
Operation manual
Application manual
Engineering manual
Commissioning manual
Installation manual
Product guide
Technical manual
Accessories guide
ABB
123