FCPS-24S6
FCPS-24S8
Document #51977
8/06/03 Revision:
PN: 51977:C1
C1
ECN 03-396
www.PDF-Zoo.com
Fire Alarm System Limitations
While a fire alarm system may lower insurance rates, it is not a substitute for fire insurance!
An automatic fire alarm systemtypically made up of Heat detectors do not sense particles of combustion and
smoke detectors, heat detectors, manual pull stations, audible alarm only when heat on their sensors increases at a predeter-
warning devices, and a fire alarm control panel with remote mined rate or reaches a predetermined level. Rate-of-rise
notification capabilitycan provide early warning of a develop- heat detectors may be subject to reduced sensitivity over time.
ing fire. Such a system, however, does not assure protection For this reason, the rate-of-rise feature of each detector
against property damage or loss of life resulting from a fire. should be tested at least once per year by a qualified fire pro-
The Manufacturer recommends that smoke and/or heat detec- tection specialist. Heat detectors are designed to protect
tors be located throughout a protected premise following the property, not life.
recommendations of the current edition of the National Fire IMPORTANT! Smoke detectors must be installed in the
Protection Association Standard 72-1999 (NFPA 72-1999), same room as the control panel and in rooms used by the sys-
manufacturer's recommendations, State and local codes, and tem for the connection of alarm transmission wiring, communi-
the recommendations contained in the Guide for Proper Use cations, signaling, and/or power. If detectors are not so
of System Smoke Detectors, which is made available at no located, a developing fire may damage the alarm system, crip-
charge to all installing dealers. A study by the Federal Emer- pling its ability to report a fire.
gency Management Agency (an agency of the United States Audible warning devices such as bells may not alert people
government) indicated that smoke detectors may not go off in if these devices are located on the other side of closed or
as many as 35% of all fires. While fire alarm systems are partly open doors or are located on another floor of a building.
designed to provide early warning against fire, they do not Any warning device may fail to alert people with a disability or
guarantee warning or protection against fire. A fire alarm sys- those who have recently consumed drugs, alcohol or medica-
tem may not provide timely or adequate warning, or simply tion. Please note that:
may not function, for a variety of reasons:
Strobes can, under certain circumstances, cause seizures
Smoke detectors may not sense fire where smoke cannot in people with conditions such as epilepsy.
reach the detectors such as in chimneys, in or behind walls, on
roofs, or on the other side of closed doors. Smoke detectors Studies have shown that certain people, even when they
also may not sense a fire on another level or floor of a building. hear a fire alarm signal, do not respond or comprehend the
A second-floor detector, for example, may not sense a first- meaning of the signal. It is the property owner's responsi-
floor or basement fire. bility to conduct fire drills and other training exercise to
make people aware of fire alarm signals and instruct them
Particles of combustion or smoke from a developing fire on the proper reaction to alarm signals.
may not reach the sensing chambers of smoke detectors
because: In rare instances, the sounding of a warning device can
cause temporary or permanent hearing loss.
Barriers such as closed or partially closed doors, walls, or
chimneys may inhibit particle or smoke flow. A fire alarm system will not operate without any electrical
power. If AC power fails, the system will operate from standby
Smoke particles may become cold, stratify, and not reach batteries only for a specified time and only if the batteries have
the ceiling or upper walls where detectors are located. been properly maintained and replaced regularly.
Smoke particles may be blown away from detectors by air Equipment used in the system may not be technically com-
outlets. patible with the control panel. It is essential to use only equip-
Smoke particles may be drawn into air returns before ment listed for service with your control panel.
reaching the detector. Telephone lines needed to transmit alarm signals from a
The amount of smoke present may be insufficient to alarm premise to a central monitoring station may be out of service
smoke detectors. Smoke detectors are designed to alarm at or temporarily disabled. For added protection against tele-
various levels of smoke density. If such density levels are not phone line failure, backup radio transmission systems are rec-
created by a developing fire at the location of detectors, the ommended.
detectors will not go into alarm. The most common cause of fire alarm malfunction is inade-
Smoke detectors, even when working properly, have sensing quate maintenance. To keep the entire fire alarm system in
limitations. Detectors that have photoelectronic sensing excellent working order, ongoing maintenance is required per
chambers tend to detect smoldering fires better than flaming the manufacturer's recommendations, and UL and NFPA stan-
fires, which have little visible smoke. Detectors that have ion- dards. At a minimum, the requirements of Chapter 7 of NFPA
izing-type sensing chambers tend to detect fast-flaming fires 72-1999 shall be followed. Environments with large amounts
better than smoldering fires. Because fires develop in different of dust, dirt or high air velocity require more frequent mainte-
ways and are often unpredictable in their growth, neither type nance. A maintenance agreement should be arranged
of detector is necessarily best and a given type of detector through the local manufacturer's representative. Maintenance
may not provide adequate warning of a fire. should be scheduled monthly or as required by National and/
Smoke detectors cannot be expected to provide adequate or local fire codes and should be performed by authorized pro-
warning of fires caused by arson, children playing with fessional fire alarm installers only. Adequate written records
matches (especially in bedrooms), smoking in bed, and violent of all inspections should be kept.
explosions (caused by escaping gas, improper storage of
flammable materials, etc.). Precau-L-4-2003.fm
FCC Warning
WARNING: This equipment generates, uses, and can Canadian Requirements
radiate radio frequency energy and if not installed and This digital apparatus does not exceed the Class A limits
used in accordance with the instruction manual, may for radiation noise emissions from digital apparatus set
cause interference to radio communications. It has been out in the Radio Interference Regulations of the Cana-
tested and found to comply with the limits for class A dian Department of Communications.
computing device pursuant to Subpart B of Part 15 of
FCC Rules, which is designed to provide reasonable Le present appareil numerique n'emet pas de bruits radi-
protection against such interference when operated in a oelectriques depassant les limites applicables aux appa-
commercial environment. Operation of this equipment in reils numeriques de la classe A prescrites dans le
a residential area is likely to cause interference, in which Reglement sur le brouillage radioelectrique edicte par le
case the user will be required to correct the interference ministere des Communications du Canada.
at his own expense.
Acclimate Plus, AWACS, HARSH, NOTIFIRENET, ONYX, and VeriFire are trademarks, and FlashScan, UniNet, and VIEW are
registered trademarks of NOTIFIER. NION is a trademark of NIS. NIS and Notifier Integrated Systems are trademarks and NOTIFIER is a
registered trademark of FireLite Alarms, Inc. Echelon is a registered trademark and LonWorks is a trademark of Echelon Corporation. ARCNET is a
registered trademark of Datapoint Corporation. Microsoft and Windows are registered trademarks of the Microsoft Corporation. LEXAN is a registered
trademark of GE Plastics, a subsidiary of General Electric Company.
www.PDF-Zoo.com
FCPS-24S P/N:51977:C1 8/06/03 5
It is imperative that the installer understand the requirements of the Authority Having Jurisdiction
(AHJ) and be familiar with the standards set forth by the following regulatory agencies:
Underwriters Laboratories Standards
NFPA 72 National Fire Alarm Code
Before proceeding, the installer should be familiar with the following documents.
NFPA Standards
NFPA 72 National Fire Alarm Code
NFPA 70 National Electrical Code
Underwriters Laboratories Documents:
UL 464 Audible Signaling Appliances
UL 864 Standard for Control Units for Fire Protective Signaling Systems
UL 1638 Visual Signaling Appliances
UL 1971 Signaling Devices for Hearing Impaired
Other:
NEC Article 250 Grounding
NEC Article 300 Wiring Methods
NEC Article 760 Fire Protective Signaling Systems
Applicable Local and State Building Codes
Requirements of the Local Authority Having Jurisdiction (LAHJ)
Other Notifier Documents:
Device Compatibility Document Document #15378
1.1 General
The FCPS-24S power supplies can be used as remotely mounted power supplies and battery
chargers to power four noncoded or coded NACs. The Main FACP (Fire Alarm Control Panel)
NAC(s) is connected to the remote power supply input circuit(s). When the control input circuit
activates due to reverse polarity of the NAC from the FACP, the power supply will activate its
Notification Appliance Circuits.
During the inactive or nonalarm state, the power supply supervises its NAC field wiring for short
and open conditions. AC fail, battery, charger and ground fault troubles will also be monitored by
the power supply. If an NAC or power supply fault is detected, the power supply Normally-Closed
Trouble contact will open.
If an alarm condition occurs and the NAC is activated, the supervision is disabled and the
Notification Appliance Circuit is no longer supervised. Supervision of other power supply faults
such as low battery, AC loss, ground fault and battery charger trouble will continue and may be
monitored via the Trouble relay contacts.
1.2 Features
Self-contained in a lockable cabinet
24 VDC remote power supply
Outputs are completely power-limited
Two optically-isolated input/control circuits, compatible with 12 VDC and 24 VDC control
panel NACs
Four output circuits:
Fully filtered power
Four 24 VDC Style Y (Class B) NACs
Optional ZNAC-4 Class A converter module for conversion to Style Z NACs
Alternatively, all four circuits may be configured as 24 VDC power outputs
Output circuits may be configured as resettable or nonresettable
NAC Trouble LED - blinks to indicate the number of the circuit in trouble
Maximum current available for any one output circuit: 3.0 amps
Maximum total continuous current available:
4.0 amps for FCPS-24S6
6.0 amps for FCPS-24S8
1.4 Jumpers
CAUTION! Remove all power (AC & DC) before cutting or moving any jumpers.
If the source voltage to the input circuit is a noncoded (steady voltage) input
jumpers signal, the jumper for the corresponding input circuit should be in the default
position which jumpers the bottom two pins (as illustrated in drawing at left).
Jumper positions shown
for noncoded (steady) If the source voltage to the input circuit is coded (variable voltage), the jumper
source voltage for the corresponding input circuit should be moved to jumper the top two pins.
1.6 Specifications
Refer to Figure 1.1 on page 11 for terminal locations.
Primary AC Power - TB1
120 VAC, 60 Hz, 3.2 amps maximum
Wire size: minimum #14 AWG with 600V insulation
Control Input Circuits - TB4, Terminals 3 (+) & 4 (-) and 7 (+) & 8 (-)
Trigger Input Voltage: 9 to 32 VDC
Input Current Draw in Alarm Polarity:
16 to 32 volts, 2.0 mA maximum per input
9 to 16 volts, 1.0 mA maximum per input
NAC/Output Circuits - TB2, Terminals 1 (+) & 2 (-), 3 (+) & 4 (-), 5 (+) & 6 (-) and
7 (+) & 8 (-) alarm polarity
Voltage Rating: 24 VDC filtered
Current:
Maximum for any one circuit - 3.0 amps
Maximum total continuous current for all output:
FCPS-24S6 - 4.0 amps
FCPS-24S8 - 6.0 amps
Maximum total short term current (one hour maximum) for all outputs:
FCPS-24S6 - 6.0 amps
FCPS-24S8 - 8.0 amps
Output Circuit Types:
Four Style Y NACs (require 4.7 K End-of-Line Resistors) or
Style Z NACs using the optional ZNAC-4 Class A converter module
OR
Four resettable or nonresettable 24 VDC power outputs
Refer to Notifier Device Compatibility Document for listed compatible devices
Trouble Relay Contact Rating - TB5
Fail-safe Form-C relay (normally energized, transfers with loss of power)
5.0 amps @ 24 VDC or 5.0 amps @ 30 VAC
Secondary Power (battery) Charging Circuit - JP4
Supports lead acid type batteries only
Float Charge Voltage: 27.6 VDC
Maximum Charge Current: 1.5 A
Battery fuse (F1) 15A, 30V
Maximum Battery Capacity: 18.0 AH
Power supply draws maximum standby current of 65 mA from batteries
Power-limited,
Supervised in NAC Mode with Jumpers JP5,
Nonpower-limited JP6, JP7 & JP8 in positions shown below
To Transformer #1 NAC/Out 1 +
To Transformer #2 NAC/Out 1 -
NAC/Out 2 + Trouble Relay
NAC/Out 2 - Form-C Fail-safe
Supervised NAC/Out 3 + (shown energized)
Earth NAC/Out 3 - Normally Open
AC Neutral NAC/Out 4 + Normally Closed
AC Hot NAC/Out 4 - Common
OUT4 OUT3 OUT2 OUT1
- NAC4 + - NAC3 + - NAC2 + - NAC1 + TB2
AUX TBL
EARTH NEUT HOT NO NC COM
TB5
8 7 6 5 4 3 2 1
TB1
3 2 1
J3 ZNAC-4 Connector
JP2
Auxiliary Output
500 mA Specific
AUX - 10 - Aux. Common
Application Power AUX + 9 + Aux. 24 VDC*
IN2- 8 - Control Input 2
IN2+ 7 + Control Input 2
30V
15A
OUT1- 6 - Out Common
F1 OUT1+ 5 + Out/Trouble Contact
IN1- 4 - Control Input 1
IN1+ 3 + Control Input 1
SYNC IN - 2 - Sync Input
24fs8brd.cdr
+- GND NAC AC/ ON
SYNC IN + 1 + Sync Input
AC FLT BATT TRBL CHGR
SW1
JP4 1 2 3 4 5 6 7 8 TB4
BATTERY
JP4 Supervised
- Battery SW1 *Note: Auxiliary Power
+ Battery LEDs Programming Output is power-limited
18 AH, 24 VDC Charger Trouble/AC Loss (yellow) DIP Switches but not supervised
F1 Nonpower- NAC Trouble (yellow) (change switch
Battery Fuse limited Battery Trouble (yellow) settings only
15A, 30V when all power
Ground Fault (yellow)
(AC & DC) is
AC Power (green) removed)
1.7 General
The FCPS may be used in a number of different applications. It may be used as a
remotely-mounted power supply and battery charger where it can provide up to four
coded or noncoded, synchronized or nonsynchronized NACs (Notification Appliance
Circuits). Alternatively, output #4 can be used as a door holder circuit which will
provide a steady 24 VDC output until an alarm condition or AC fail condition causes it
to drop to 0 VDC following a 60 second delay. All four outputs can also provide
power.
Style Y NAC
Note: All NAC
or Door
outputs can be
Holder Power Style Y NAC Style Y NAC Style Y NAC FCPS Trouble
converted to Style Z
Output #4 Output #3 Output #2 Output #1 Contact Output
with ZNAC-4 option
module
24 VDC Specific
AC Power Application Power
NAC Control
Input #2
Input/Output Functions are Programmable (from FACP)
by SW1 DIP Switch Settings
NAC Control
Input #1
(from FACP)
Sync. Input
24fsblok.cdr
Battery Charger
SECTION 2 Installation
Carefully unpack the system and check for shipping damage. Select a location for the
cabinet that is in a clean, dry, vibration-free area where extreme temperatures are not
encountered. The area should be readily accessible with sufficient room to easily
install and maintain the power supply. Locate the top of the cabinet approximately five
feet above the floor with the hinge mounting on the left. Determine the number of
conductors required for the devices to be installed and determine the appropriate
knockouts. All wiring must be in accordance with the National and/or Local codes for
fire alarm systems and power supplies.
Mounting Plate
EARTH
OUT4 OUT3 OUT2 OUT1
- NAC4 + - NAC3 + - NAC2 + - NAC1 + TB2
AUX TBL
NEUT H OT NO NC COM
TB5
J2
JP1
HIGH VOLTAGE
TRANSFORMER 2
CAUTION
Ground Stud J3
JP2
24fsgrnd.cdr
JP3
J1
Backbox
TRANSFORMER 1
HIGH VOLTAGE
CAUTION
AUX -
IN2-
Top
2.875 (7.3 cm)
Depth = 3.050
Backbox = 14.5 (7.75 cm)
(36.8 cm)
0.75
(1.9 cm) 2.7
9.1 (23.1 cm) (6.86cm)
10.625
(26.99 cm)
Height=15.00 Mounting Plate Pem Studs
(38.10 cm)
rcpscabb.cdr
Backbox Mounting Holes
4.7K ELR
- + Horn Strobe
- + Horn Strobe
TB2
-
OUT4
7 +
6
OUT3 OUT2
5
4
SYNC IN +
SYNC IN -
3
OUT1+
OUT1-
2
AUX +
AUX -
IN1-
OUT1
IN2+
IN1+
IN2-
J3
1
TB4
NO NC COM
24fsclsb.cdr
1 2 3 4 5 6 7 8 9 10 2
1
JP3
JP1
TB5
JP2
- +
Horn Strobes - +
Alarm Polarity
Shown - +
ZNAC-4
TB2
-
-NAC4+
- 8
OUT4
+ 7 +
ZNAC-4 Option Module
-NAC4+ -NAC3+ -NAC2+ -NAC1+ TB2 AUX TBL
8
OUT4
7
6
OUT3 OUT2
5
4
SYNC IN -
SYNC IN +
3
OUT1+
OUT1-
2
J3
AUX +
AUX -
IN1-
OUT1
IN1+
IN2+
IN2-
J3
1
TB4
3
24fsclsa.cdr
NO NC COM
1 2 3 4 5 6 7 8 9 10 2
1
FCPS-24S Circuit Board
JP3
JP1
TB5
JP2
TB1
J2
JP1
HIGH VOLTAGE
TRANSFORMER 2
JP2
CAUTION
J3
JP2
JP3
JP3
standoff standoff
J1
TRANSFORMER 1
HIGH VOLTAGE
CAUTION
AUX -
AUX -
AUX +
IN2- AUX +
IN2+
9 6 7 8 910 0
5 IN2-
4 11
30V
15A
OUT1-
8 3 12
13
1 IN2+
F1 OUT1+ 2
1 0 1514
IN1- 7 TENS
7 8
2 OUT1-
6 9
IN1+ 5
SY NC IN -
6 4
3
3 OUT1+
2
+-
JP4
AC
GN D N AC A C/
FLT B ATT T RB L C HGR
standoff
SW1
ON
1 2 3 4 5 6 7 8
SY NC IN +
TB4 standoff 5 10
ONES 4 IN1-
IN1+
B ATTERY
LOOP ADDRESS
SYNC IN -
SYNC IN +
ON
SW1
1 2 3 4 5 6 7 8 TB4
24fsmodlNOTI.cdr
Module Installation
mounting screw
1. Place addressable module over (4) standoffs and
secure with (4) supplied screws. addressable module
2. Wire module as show in illustration above.
24fsmodinstlNOTI.cdr
TB1
J3
JP2
JP3
J1
TRANSFORMER 1
HIGH VOLTAGE
CAUTION
AUX -
9
5
6 7 8 910
0 AUX +
Specific Application
4 11 IN2-
8 3
2
1 0 1514
12
13
1
IN2+ Power & SLC are
7 TENS 2
30V
15A
6
5
67 89 OUT1-
Power-limited Circuits
F1 4
3
3 OUT1+
2
10
5 ONES 4 IN1-
SYNCININ- -
SYNC
SYNCININ+ +
SYNC
+- AC
GND N AC AC/
F LT B ATT T RB L CHGR
ON
SW1
1 23 4 56 7 8 TB4
BATT ERY
JP4
24fspwrl.cdr
J2
JP1
TRANSFORMER 2
J3
JP2
JP3
J1
TRANSFORMER 1
AUX - 10
AUX + 9
IN2- 8
IN2+ 7
30V OUT1- 6
15A
F1 OUT1+ 5
IN1- 4
IN1+ 3
24fsswitc.cdr
SYNC IN - 2
SYNC IN + 1
+- AC
GND NAC AC/
FLT BATT TRBL CHGR
ON
SW1
TB4
Switches 1 through 7 shown
1 23 45 6 78
JP4
BATTERY
ON
Switch 8 shown in ON
(Closed) position
1 2 3 4 5 6 7 8
3 FCPS configured for Slave Synchronization FCPS configured for Master Synchronization
5 This switch works in conjunction with switch 6 to determine Input to Output functions
only).
SECTION 5 Applications
5.1 Controlling Four NACs With One Input and Selective Silence
In this application, the power supply has been set as a master with synchronized outputs
and selective silence (see SW1 switch settings in following illustration). All four
FCPS-24S output circuits, which are shown as NACs (Notification Appliance Circuits),
can be controlled from one input such as an addressable control module as illustrated in
Figure 5.1. The control module can be powered from the FCPS-24S auxiliary 24 VDC
power output (TB4, Terminals 9 & 10) and supervised by an EOL relay. An
addressable relay module, programmed as an alarm output and a silenceable point, can
be used as a selective silence input.
The control module is shown to demonstrate the use of a remotely mounted device
associated with an addressable fire alarm control panel. The module could be replaced
with any circuit capable of polarity reversal, such as an FACP NAC.
Horn/Strobes - + Horn/Strobes - +
Alarm Polarity Shown Alarm Polarity Shown
- + - +
TB2 TB2
-
-NAC4+
- 8 -
OUT4
-NAC4+
8
OUT4
+ 7 + 7 +
Style Y (Class B)
Style Z (Class A)
8
-NAC4+ -NAC3+ -NAC2+ -NAC1+ TB2 AUX TBL
OUT4
Output/NAC 4
Internal Trouble Contact 7
ZNAC-4 6
Output/NAC 3
OUT3 OUT2
Option Module 5
4
Output/NAC 2
SYNC IN -
SYNC IN +
3
OUT1+
OUT1-
2
AUX +
AUX -
Output/NAC 1
IN1-
OUT1
IN1+
IN2+
IN2-
J3
1
FCPS-24S
TB4
3
NO NC COM
24fsapp7.cdr
1 2 3 4 5 6 7 8 9 10 2
1 FCPS-24S has been set for
JP3
JP1
84 11
1 SLC 8 4 11
1 SLC
6 = ON Note: the Relay Module can be
3 12 3 12
13 13
7
2 2
TE NS
1 0 1514
6 7 89
2 7 TE NS
1 0 1514
6 7 89
2
6 5
3 6 5
3
7 = OFF (charger enabled) mounted on the power supply
4 4
3 3
5 2
10
4 5
2
10
4
EOL Power
ONE S ONE S
SYNC SYNC IN+ IN- OUT+ OUT- IN2+ IN2- AUX+ AUX-
1 2 3 4 5 6 7 8 9 10
TB4
5.2 Controlling Three NACs and One Door Holder With One Input
In this application, the power supply has been set as a master with synchronized
outputs. All four FCPS-24S output circuits, three NACs and one door holder, can be
controlled from one input such as an addressable control module as illustrated in Figure
5.2. The control module can be powered from the FCPS-24S auxiliary 24 VDC power
output (TB4, Terminals 9 & 10).
The control module is shown to demonstrate the use of a remotely mounted device
associated with an addressable fire alarm control panel. The module could be replaced
with any circuit capable of polarity reversal, such as an FACP Notification Appliance
Circuit.
Style Z (Class A)
Style Y (Class B)
Control Module
Figure 5.2 Controlling Three NACs and One Door Holder With One Input
End-of-Line Resistor
24fsapp5.cdr
Control Module
7 Nonresettable
FCPS-24S 6 Power Output 3
OUT3 OUT2 OUT1
5 Nonresettable
4 Power Output 2
SYNC IN +
SYNC IN -
3 Resettable
OUT1+
OUT1-
2
AUX +
AUX -
Power Output 1
IN1-
IN2+
IN1+
IN2-
J3
1
Resettable
TB4
9 0
3
NO NC COM
6 7 8 9 10
5
8 4
3
11
1
12
1 2 3 4 5 6 7 8 9 10 2 7
2 13
24fsapp4.cdr
1 0 1514
TE NS
6 7 8 9
1 64
3
5
3
5 4
2
JP3
10
JP1
TB5
ONE S
JP2
LOO P ADDRES S
SLC
EOL Power
Supervision Relay
A77-716B
24 VDC (energized)
Resettable
Power SW1 Switch Settings
1 = OFF
FACP No Sync
2 = OFF
3 = OFF (master)
4 = OFF (no AC Fail reporting delay)
5 = OFF
Split Alarm
6 = ON
7 = OFF (charger enabled)
8 = OFF (circuit 4 NAC)
SLC
OUT4
Door Holder Circuit 4
7
FCPS-24S 6
OUT3 OUT2
5 Door Holder Circuit 3
4
Door Holder Circuit 2
SYNC IN +
SYNC IN -
3
OUT1+
OUT1-
2
AUX +
AUX -
IN1-
IN2+
OUT1
IN1+
IN2-
1
TB4
3 9 0
NO NC COM
6 7 8 9 10
5
8 11
1
AUX TBL
4
12
1 2 3 4 5 6 7 8 9 10
3
2
13
7 2
2
24fsapp3.cdr
1 0 1514
TE NS
67 8 9
1 64
3
5
3
5 2
4
JP3
10
End-of-Line Resistor
JP 1
TB5
ONE S
JP2
LOO P ADDRESS
supplied with
Monitor Module
Monitor Module
SLC
Nonresettable
-24 VDC
SW1 Switch Settings
+24 VDC
1 = OFF
No Sync
2 = OFF
Alarm 3 = OFF (master)
Relay 4 = OFF (no AC Fail reporting delay)
5 = OFF
General Alarm
6 = OFF
FACP
7 = OFF (charger enabled)
8 = OFF (circuit 4 NAC)
OUT4
Trouble
Contact
7 = OFF (charger enabled)
OUT3 OUT2
SYNC IN +
8 = OFF (circuit 4 NAC)
SYNC IN -
OUT1+
AUX +
OUT1-
AUX -
FCPS-24S
IN1+
IN2+
IN2-
IN1-
OUT1
J3
TB4
3
NO NC COM
AUX TBL
1 2 3 4 5 6 7 8 9 10 2
1
JP3
JP1
TB5
ELR
JP2
Note: One Relay Module can be mounted
directly to each FCPS-24S circuit board
inside the power supply cabinet.
SW1 Switch Settings
1 & 2 = sync (any setting
24fsapp1.cdr
but OFF/OFF)
Standby Polarity Shown Internal 8
3 = ON (slave)
FACP 4
reporting delay)
SYNC IN +
SYNC IN -
3
OUT1+
OUT1-
AUX +
AUX -
2
5 = OFF
IN1+
IN2+
IN2-
IN1-
OUT1
J3
3
NO NC COM
AUX TBL
1 2 3 4 5 6 7 8 9 10 2
NAC
1 7 = OFF (charger enabled)
JP3
JP1
TB5
programmed
for Sync
-
NAC 1
+
Horn/Strobes
OUT4
Trouble 7
6 = OFF
Contact 6 7 = OFF (charger enabled)
OUT3 OUT2
5 8 = OFF (circuit 4 NAC)
4
SYNC IN +
SYNC IN -
3
OUT1+
AUX +
OUT1-
AUX -
2 to next FCPS-24S input
IN1+
IN2+
IN2-
IN1-
OUT1
1
J3
FCPS-24S (if needed)
TB4
NO NC COM
1 2 3 4 5 6 7 8 9 10 2
1
JP3
JP1
TB5
JP2
4.7K ELR
for FCPS-24S
Output
Horn/Strobes
Internal
-NAC4+ -NAC3+ -NAC2+ -NAC1+ TB 2
8
Trouble
OUT4
7
Contact 6
OUT3
OUT2
3
FACP
OUT1+
OUT1-
AUX +
AUX -
2
IN2-
IN1+
IN2+
IN1-
OUT1
J3
FCPS-24S 1
TB4
3
NO NC COM
24fsapp1.cdr
AUX TBL
1 2 3 4 5 6 7 8 9 10 2
NAC 1
programmed
JP 3
JP1
TB 5
JP2
for Synch
ELR for
- FACP NAC
SW1 Switch Settings
NAC 1 1 & 2 = sync (any setting
but OFF/OFF)
+ 3 = ON (slave)
Horn/Strobes
4 = OFF (no AC Fail
reporting delay)
5 = OFF general alarm
6 = OFF
7 = OFF (charger enabled)
8 = OFF (circuit 4 NAC)
Figure 5.7 Supervised Cascaded Connections
OUT4
Trouble 7 7 = OFF (charger enabled)
Contact 6 8 = OFF (circuit 4 NAC)
OUT3 OUT2
5
4
SYNC IN +
SYNC IN -
3
OUT1+
AUX +
OUT1- to next FCPS-24S input
AUX -
2
IN1+
IN2+
IN2-
IN1-
OUT1
1
J3
(if needed)
FCPS-24FS
TB4
NO NC COM
1 2 3 4 5 6 7 8 9 10 2
1
JP3
JP1
TB5
JP2
4.7K
ELR for
FCPS-24S
Output Horn/Strobes
(synchronized)
Internal
OUT4
Trouble 7
Contact 6
OUT3
Standby Polarity Shown 5
4
SYNC IN -
SYNC IN +
OUT2
3
OUT1+
OUT1-
AUX +
FACP
AUX -
2
IN2-
IN1+
IN2+
IN1-
OUT1
J3
FCPS-24S 1
TB4
24fsapp11.cdr
3
NO NC COM
AUX TBL
1 2 3 4 5 6 7 8 9 10 2
1
NAC
JP 3
JP1
TB 5
JP2
with no
synchronization ELR
- for FACP
SW1 Switch Settings
NAC 1 NAC 1 & 2 = sync (any setting
but OFF/OFF)
+ Horns 3 = OFF (master)
(no synchronization) 4 = OFF (no AC Fail
reporting delay)
5 = OFF general alarm
6 = OFF
7 = OFF (charger enabled)
8 = OFF (circuit 4 NAC)
Figure 5.8 Supervised Cascaded Connections
Note: The following notes apply to this illustration
1. Refer to NFPA 72, Chapter 4-4, Visible Characteristics, Public Mode.
2. Use only devices from the same manufacturer in each system.
6.1 Overview
This section contains instructions and tables for calculating power supply currents in alarm and
standby conditions. This is a four-step process, consisting of the following:
1. Calculating the total amount of AC branch circuit current required to operate the system
2. Calculating the power supply load current for non-fire and fire alarm conditions and
calculating the secondary (battery) load
3. Calculating the size of batteries required to support the system if an AC power loss occurs
4. Selecting the proper batteries for your system
Use Table 6.1 to determine the total amount of current, in AC amperes, that must be supplied to the
system
[ ] [ ] X [ ] =
[ ] [ ] X [ ] =
Following are the types of current that can be entered into Table 6.3 on page 39
Calculation Column 1 - The primary supply current load that the power supply must
support during a non-fire alarm condition, with AC power applied
Calculation Column 2 - The primary supply current load the power supply must support
during a fire alarm condition, with AC power applied
Calculation Column 3 - The standby current drawn from the batteries in a non-fire alarm
condition during a loss of AC power
Table 6.3 contains three columns for calculating current draws. For each column, calculate the
current and enter the total (in amperes) in the bottom row. When finished, copy the totals from
Calculation Column 2 and Calculation Column 3 to Table 6.4 on page 40.
Qty X (current draw) = Total Qty X (current draw) Total Qty X (current draw) = Total
=
NAC/Output #1 [ ] X[ ]=
NAC/Output #2 [ ] X[ ]=
NAC/Output #3 [ ] X[ ]=
NAC/Output #4 [ ] X[ ]=
www.PDF-Zoo.com
World Headquarters NOTIFIER is a company
12 Clintonville Road
Northford, CT 06472-1653 USA
203-484-7161
fax 203-484-7118
www.notifier.com