Dimensionare fundatii pahar

Date de intrare

Caracteristici stalp
Materiale
Rc 20.00 N/mm2
Beton C30/37
Rt 1.33 N/mm2

Armatura PC52 Ra 300.00 N/mm2


GruapreaFundamentala Gruparea Speciala
NSTGF 581.00 KN NSTGS 240.00 KN
MSTGS 313.50 KNm
QSTGS 36.88 KN

bst 0.50 m Armare PC52 Nr. Bare 12


lst 0.50 m 16 mm
hst 8.50 m

Caracteristici fundatie Df 1.50 m Caracteristici teren


Materiale pconv med 200.00 KN/m2
Rc 13.33 N/mm2 K1 0.10
Beton C20/25 2
Rt 1.00 N/mm CB 34.00 KN/m2
CD -25.00 KN/m2
Armatura PC52 Ra 300.00 N/mm2 pconv 209.00 KN/m2

la 0.70 m Hf 0.40 m
lb 0.70 m D 0.10 m
bp 0.30 m
l1 0.70 m 0.77 m L 2.70 m
b1 0.70 m 0.77 m B 2.70 m
1) Determinarea inaltimii paharului

nanc 0.07
la0 12
la 27.79

la 0.44 m
ef
la 0.28 m

Hp > 0.60 m Hp 0.60 m


2) Verificarea grosimii fundului paharului (GF si GS)

Hf 0.40 m
U 3.60 m

Gruparea Fundamentala Gruparea Speciala


NST montaj 76.78 KN NST montaj 56.88 KN

68.25 < 1080.00 KN 50.56 < 1080.00 KN

NST max 581.00 KN NST max 240.00 KN

As 1.20 m As 1.20 m
mbt 0.30 mbt 0.30
N1cap 360.00 KN N1cap 360.00 KN

516.44 < 1440.00 KN 213.33 < 1440.00 KN


3) Verificarea paharului in plan orizontal (GS)

NST 240 KN
MST 313.5 KNm

M1 218.80 KNm
P 492.72 KN
Np 246.36 KN

Mr 15.52 KNm
Mr 6.90 KNm
Dimensionarea armaturii orizontale la incovoiere
Sectiunea de calcul 0.30 x 0.27
a 0.035 m

x 0.02 < 0.07 m

Aaonec 224.94 mm2 Aaomin 33.75 mm2

Verificarea paharului la eforturi principale de compresiune

Np 246.36 KN
33.21 grad
Cb 449.84 KN

ld 0.17 m
hd 0.24 m

n 0.92 11.25 < Rd max 9.20 N/mm2

Dimensionarea armaturii orizontale la intindere centrica


Aaonec 821.19 mm2 Aaomin 135.00 mm2
4) Verificarea paharului in plan vertical (GS)

Dimensionarea armaturii orizontale la fortei taietoare


246.36 < 195.00 KN

Aavnec 227.41 mm2 Aavmin 292.50 mm2

Dimensionarea armaturii orizontale la incovoiere la baza paharului


N1cap 360 KN
Mcalc 335.63 KNm

a 0.035 m
x 0.02 < 0.07 m

Aavnec 518.76 mm2 Aavmin 292.50 mm2


Detalierea armarii paharului

5) Dimensionarea talpii fundatiei (GF si GS)


GrupareaFundamentala Gruparea Speciala
Nmax 694.48 KN Nmax 353.48 KN
Mmax 350.38 KNm

e0 0.99 m
hza 1.08 m

Aza/At 0.40 > 0.50

Pmax 95.26 < 250.80 KN/m2 Pmax 243.28 < 292.60


6) Calculul armaturii din talpa fundatiei

Dimensionarea armaturii de la partea inferioara la incovoiere


P1 85.05 KN/m2
Mmax 126.04 KNm

a 0.050 m
x 0.01 m

Aa tfnec 941.86 > 1012.50 mm2

Dimensionarea armaturii de la partea superioara la incovoiere


Mmax 8.60 KNm Armatura se dispune constructiv.

Calculul efortului tangangentila la baza paharului


t 0.27 < 0.75 N/mm2