Transformer Size For Large Motor Starting 10-6-13
Transformer Size For Large Motor Starting 10-6-13
:Transformer Detail:
Transformer Size 400 KVA
Transformer Secondary Voltage:(v2) 460 Volt
% Impedance: (z) 5.75%
Allowable Voltage Drop in System: 10%
:Motor Detail ( Only One No of Motor):
Motor Size: 150 Kw
Volt (vm): (L-L) 460 Volt
Power Factor: 0.8
Motor KVA 120 KVA
Motor Code: (Kva/Hp) D
InRush Current at Starting:(Enter If you know otherwise leave it blank)
Enter Motor Full Load Current(Enter If you know otherwise leave it blank )
Motor Full Load Current: (ILM) 235 Amp
Locaked Rotor Current Multiplier: (Min) 4.10
Locaked Rotor Current Multiplier: (Max) 4.50
Locaked Rotor Current (L1): (Min) 965 Amp
Locaked Rotor Current (L2): (Max) 1059 Amp
Motor InRush KVA At Starting: (IrsM) 844 KVA
How many times Motor Starts per Hours 2
:Calculations:
Full Load Current of Transformer : (ILX) 502 Amp
Short Circuit Current at Transformer Secondary: (Isc) 8731 Amp
Max KVA of Transformer at Isc: Q1 6957 KVA
Motor InRush KVA At Starting:(IrsM) 844 KVA
Voltage Drop at Transformer Secondary Due to Motor inRush: (Vd) 12% 88%
Transformer Secondary Voltage 404 Volt
:Result:
(1) Motor Full Load Current <= 65% Transformer Full Load Current Yes
(2) Voltage Drop at Transformer Secondary Due to Motor inRush High
(3) Transformer Size:(20% Added due to motor starts more than once/Hour) 480 Kva
Increase Size of Transformer
Calculation Formulas:
ILX=KVA/(1.732xv2)
ILM=(Kwx1000)/(1.732xVmxP.F)
Isc=ILx/z
Q1=(v2xISCxILMx1.732)/1000
IrsM=(VmxL2x1.732)/1000
Vd=IrsM/Q1
4
4.1
4.5
rop due to Starting of Large size Motor Jignesh.Parmar www.electricalnotes.wordpress.com
:Transformer Detail:
Transformer Size 1000
Transformer Secondary Voltage:(v2) 480
% Impedance: (z) 5.75%
Allowable Voltage Drop in System: 10%
:Motors Detail ( More Than One No of Motor):
Total KW of Three Phase Motors: 300
Total KW of Single Phase Motors: 5
Volt: (L-L) 460
Volt: (L-N) 266
Power Factor: 0.8
Locaked Rotor Current: (Max) 450%
Total Three Phase Motors Full Load Current 471
Total Single Phase Motors Full Load Current 24
Total Motors Full Load Current 494
Motor InRush KVA At Starting 1772
:Calculations:
Full Load Current of Transformer : (IL) 1203
Short Circuit Current at Transformer Secondary: (Isc) 20919
Max KVA of Transformer at Isc 17391
Motor InRush KVA At Starting 1772
Voltage Drop at Transformer Secondary Due to Motor inRush 10.2%
Transformer Secondary Voltage 431
:Result:
(1) Motor Full Load Current <= 65% Transformer Full Load Current Yes
(2) Voltage Drop at Transformer Secondary Due to Motor inRush High
(3) Transformer Size: 1000
Increase Size of Transformer
sh.Parmar www.electricalnotes.wordpress.com
KVA
Volt
Kw
Kw
Volt
Volt
Amp
Amp
Amp
KVA
Amp
Amp
KVA
KVA
90%
Volt
KVA