SAFETY GUIDE 9
9.1
nance programs are followed. The nominal mating the loads conservatively and by select-
rating, used as a datum for the overload rat- ing the continuous rating of the diesel genera-
ings, has been termed variously the "continu- tor set so that it exceeds the sum of the loadsI
ous," "guaranteed," or "long term" rating. The needed at any one time. A more accurate esti-
definition used throughout this guide for "con- mate of safety loads is possible during the
tinuous rating" is "that load for which the sup- operating license stage of review due to the
plier guarantees continuous operation at a high completion of the detailed designs and the
availability (expected to be about 95%) with availability of preoperational test data. This
an annual maintenance interval". The over- permits the consideration of a somewhat less
load ratings are similarly defined except that conservative approach, such as operation with
the specified maintenance intervals are shorter. safety loads within the 2000 hour overload
For example, the following are the load ratings rating of the diesel generator set. A conserva-
of a typical diesel generator set: tive estimate of safety loads based on design
or measurements taken during preoperational
Ratings Maintenance Interval
testing of engineered safety features does not,
Continuous 2500 kW Annual (8760 hr) however, represent with certainty the actual
Overload 2850 kW 2000 hr
loads experienced under accident conditions.
2950 kW 7 day
3050 kW 30 min Therefore, an adequate margin is still essential.
9.2
crease to less than 95 percent of nomi- lower. Voltage should be restored to
nal and 75 percent of nominal, respec- within 10 percent of nominal and fre-
tively. During recovery from transients quency should be restored to within 2
caused by step load increases or result- percent of nominal in less than 40 per-
ing from the disconnection of the larg- cent of each load sequence time inter-
est single load, the speed of the diesel val.
generator set should not exceed 75 per- 5. The suitability of each diesel generator
cent of the difference between nominal set of the standby power supply should
speed and the overspeed trip set point be confirmed by prototype qualification
or 115 percent of nominal, whichever is test data and preoperational tests.
9.3